《UL 444 CRD-2015 UL Standard for Safety Communications Cables Section Paragraph Reference 7 24 (New) 8 4 6 (New) Subject New - LP ratings (Edition 4 July 11 2008).pdf》由会员分享,可在线阅读,更多相关《UL 444 CRD-2015 UL Standard for Safety Communications Cables Section Paragraph Reference 7 24 (New) 8 4 6 (New) Subject New - LP ratings (Edition 4 July 11 2008).pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION ORDISTRIBUTION WITHOUT PERMISSION FROM ULUNDERWRITERS LABORATORIES INC. CERTIFICATION REQUIREMENT DECISIONThis Certification Requirement Decision is prepared and published by Underwriters Laboratories Inc.(UL). It is normative for the a
2、pplicable UL Product Certification Program(s); however, it is currently notpart of the UL Standard(s) referenced below.Product Category (CCN): DUZXStandard Number: UL 444Standard Title: Standard for Communications CablesEdition Date: July 11, 2008Edition Number: 4Section / Paragraph Reference: 7.24
3、(New), 8.4.6 (New)Subject: New LP ratingsSupersedes prior Certification Requirement Decision issued 09-14-2015DECISION:1.4 In Canada, Type CMUC, cross-connect communications cables, “-LP” and the -CI circuit integritymarkings are not recognized by the Canadian Electrical Code, Part I.In the US, Type
4、 CMH is not recognized in the NEC.8.4.6 (NEW) (United States only)Cables that comply with the cable heating test described in Clause 7.24 are permitted to be markedwith the suffix LP (XX) where XX shall be 0.5A, 0.6A, 0.7A, 0.8A, 0.9A or 1.0A to designate thecurrent rating of each conductor in the c
5、able. If so marked, the suffix “LP” shall be addedimmediately after the cable designation. This marking is not required.7.24 (NEW) Cable Heating Test7.24.1 When tested as described in this section, the temperatures measured on the insulation and jacketof the cables, after being corrected to an ambie
6、nt of 45C, shall not exceed the temperature rating of thecable.7.24.2 The cables shall be arranged in a bundle consisting of 192 cables and electrically connected inseries to a power supply capable of providing the rated current marked as part of the LP rating. The inner37 cables shall be arranged i
7、n a hexagonal densest packing structure which represents the worst casethermal dissipation situation. The remaining cables shall be evenly distributed in a random fashion to forma 192 cable bundle. The bundle shall be placed in a 6 foot long (1.83 m) commercially availablenon-metallic conduit (Sched
8、ule 40) with the minimum diameter needed to install the bundle without puttingpressure on the cables. Each end of the conduit shall be filled with insulation.7.24.3 The temperatures shall be measured on the outer jacket and conductor insulation of the centercable at the midpoint of the cable. In add
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL444CRD2015ULSTANDARDFORSAFETYCOMMUNICATIONSCABLESSECTIONPARAGRAPHREFERENCE724NEW846NEWSUBJECTNEWLPRATINGSEDITION4JULY112008PDF

链接地址:http://www.mydoc123.com/p-1068160.html