PFI TB-1-2013 PRESSURE-TEMPERATURE RATINGS USED IN POWER PLANT PIPING SYSTEMS.pdf
《PFI TB-1-2013 PRESSURE-TEMPERATURE RATINGS USED IN POWER PLANT PIPING SYSTEMS.pdf》由会员分享,可在线阅读,更多相关《PFI TB-1-2013 PRESSURE-TEMPERATURE RATINGS USED IN POWER PLANT PIPING SYSTEMS.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、PFI Technical Bulletin TB-1 (Revised December 2013) PRESSURE-TEMPERATURE RATINGS USED IN POWER PLANT PIPING SYSTEMS Prepared by Pipe Fabrication Institute Engineering Committee All PFI Standards are advisory only. There is no agreement to adhere to any PFI Standard and their use by anyone is entirel
2、y voluntary. Copyright by PIPE FABRICATION INSTITUTE Dedicated to Technical Advancements and Standardization in the Pipe Fabrication Industry Since 1913 USA 666 Fifth Ave., #325 New York, NY 10103 CANADA 655, 32ndAve., suite 201 Lachine, QC H8T 3G6 WEB SITE www.pfi-institute.orgPFI Technical Bulleti
3、n TB-1 (Revised December 2013) PRESSURE-TEMPERATURE RATINGS USED IN POWER PLANT PIPING SYSTEMS METRIC CONVERSIONS The conversion of quantities between systems of units involves a determination of the number of significant digits to be retained. All conversions depend upon the intended precision of t
4、he original quantity and are rounded to the appropriate accuracy. Pipe sizes together with applicable wall thicknesses are not shown with metric equivalents. The SI (metric) values where included with the customary U.S. values in this Standard are the rounded equivalents of the U.S. values and are f
5、or reference only. Metric units were derived utilizing the following conversion factor: Conversion Factor inches to 25.4 millimeter The worksheets in TB-1 present both Imperial and SI calculation 1. Scope 1.1 This bulletin provides pressure ratings, in Imperial and SI units, for each pipe size and a
6、pplicable schedule, 1/8 NPS through 48 NPS. Selection of a suitable material must consider such items as service, temperature, safety, thermal shock, corrosion allowance, exposure to fire, system life and economy, using sound engineering judgment, and is not within the scope of this bulletin. 1.2 Re
7、ferencing the applicable fabrication code will provide allowable stress values, “S”, for a given material and temperature, weld joint efficiency “E”, and temperature coefficient “y”. TB-1 will also provide a minimum design thickness, when a design pressure is provided. 1.3 The following formula and
8、nomenclature are in accordance with ASME B31.1, Power Piping code, 2004 edition. The pressure ratings provided in this technical bulletin may be used for other codes that utilize the same pressure formula as shown below, however, the nomenclature may be different. It is the users responsibility to d
9、etermine if this bulletin is applicable. 2. Formulas 2.1 The following formula, as given in Paragraph 104.1.2 formula (4) of ASME B31.1, is used to calculate the pressure ratings (PSIG/kPa) provided in columns “C” through “R” of the TB-1 “Imperial Units” worksheet, (sheet 1), and “SI Units” workshee
10、t, (sheet 2). )(2)(2AtyDAtSEPmom 2.2 The following formula, as given in Paragraph 104.1.2 formula (3) of ASME B31.1 is used to calculate the minimum wall thickness required, as provided in column “S” of the TB-1 “Imperial Units” worksheet, (sheet 1), and “SI Units” worksheet, (sheet 2): APySEPDotm )
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。