1、*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 73.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 73.00 20 (February 2003)UFGS-13851N (February 2003)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION TABLE OF CONTENTSDIVISION 28 -
2、 ELECTRONIC SAFETY AND SECURITYSECTION 28 31 73.00 20EXTERIOR FIRE ALARM SYSTEM, CLOSED CIRCUIT TELEGRAPHIC TYPE02/10PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 DEFINITIONS1.3.1 Installer1.4 SYSTEM DESCRIPTION1.4.1 Design Requirements1.4.1.1 Supervisory and Alarm Power Requirements1.5 SU
3、BMITTALS1.6 QUALITY ASSURANCE1.6.1 Qualifications1.6.1.1 Installer Qualifications1.6.1.2 Installation Personnel1.6.1.3 Fire Alarm System Technician or Engineer1.6.2 Modification of References1.6.3 Regulatory Requirements1.6.3.1 Installation Certificate1.6.3.2 UL Listings/FM Approvals1.6.4 Parts Reli
4、ability1.6.5 Test Procedures1.7 DELIVERY, STORAGE AND HANDLING1.8 EXISTING CONDITIONS1.9 MAINTENANCE1.9.1 Special Tools1.9.2 Spare Parts1.9.3 Record Wiring DiagramsPART 2 PRODUCTS2.1 ALARM RECEIVING AND DECODING CONSOLE2.1.1 Display2.1.2 Memory2.1.3 Digital Clock2.1.4 PrintersSECTION 28 31 73.00 20
5、Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.1.5 Audible Trouble and Alarm Devices2.1.6 Power Supply2.1.7 Emergency Power2.1.7.1 Emergency Power Switchover2.1.7.2 Console Battery Charger2.1.8 Console Supervision2.1.9 Tie-Line Repeater2.1.1
6、0 Variable Code Transmitter2.2 AUDIBLE ALARM2.3 SOUNDING DEVICES2.4 CIRCUIT PROTECTION DEVICES2.5 STANDARD FIRE ALARM BOXES2.5.1 Master Fire Alarm Boxes2.5.2 Fire Alarm Box Mounting2.5.3 Fire Alarm Box Grounding2.5.4 Auxiliary Transmitter2.6 OVERVOLTAGE AND SURGE PROTECTION2.6.1 Power Line Surge Pro
7、tection2.6.2 Communications Link Surge Protection2.6.3 Sensor Wiring Surge Protection2.7 FIRE ALARM SYSTEM POWER SUPPLY2.7.1 AC Power2.7.2 Rectifier/Charger2.7.3 Batteries2.7.4 Electronic Inverters2.7.5 Transformers2.8 WIRING2.8.1 Wiring Within Buildings2.8.2 Cables for Fire Alarm Service2.8.2.1 Und
8、erground Cables2.8.2.2 Cables Provided in an Exterior Overhead System2.8.2.3 Identification Slabs (Markers)2.8.3 Wire Markers2.9 CONDUIT2.9.1 Rigid Steel Conduit Zinc-Coated2.9.2 Intermediate Metal Conduit (IMC)2.9.3 Electrical Metallic Tubing (EMT)2.10 OUTLET BOXES2.11 FITTINGS FOR CONDUIT AND OUTL
9、ET BOXES2.12 GROUND RODS2.13 KEYS AND LOCKS2.14 NAMEPLATES2.15 PAINTINGPART 3 EXECUTION3.1 INSTALLATION3.2 VERIFICATION OF CONDITIONS3.3 WIRING3.4 GROUNDING3.5 CABLE SPLICES3.6 SPECIAL CONNECTIONS3.6.1 Branch or “Y“ Connections for Cables3.6.2 Welded and Brazed Connections3.7 CORROSION AND FUNGUS PR
10、EVENTION3.8 FIELD QUALITY CONTROL3.8.1 Tests During Installation3.8.1.1 Ground Resistance Tests3.8.1.2 Dielectric Strength and Insulation Resistance TestsSECTION 28 31 73.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-3.8.1.3 Power Suppl
11、y Tests3.8.1.4 Supervisory Features and Trouble Alarm Circuit Test3.8.1.5 Box and Transmitter Tests3.8.1.6 Signal Transmission and Recording Tests3.8.1.7 Trouble Line Operation Tests3.8.2 Complete Printout Documentation3.8.3 Final Performance and Acceptance Tests3.8.3.1 Acceptance Testing3.8.4 Addit
12、ional Tests3.8.5 Manufacturers Field Service3.8.5.1 Manufacturers Representative3.8.5.2 Instruction for Government Personnel3.9 CONTINUITY OF PROTECTION- End of Section Table of Contents -SECTION 28 31 73.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without licens
13、e from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 73.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 73.00 20 (February 2003)UFGS-13851N (February 2003)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION 28 31 73.00 20E
14、XTERIOR FIRE ALARM SYSTEM, CLOSED CIRCUIT TELEGRAPHIC TYPE02/10*NOTE: This guide specification covers the requirements for exterior fire alarm reporting and receiving system of the closed circuit telegraphic type.Edit this guide specification for project specific requirements by adding, deleting, or
15、 revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the
16、 technical proponent of the specification. A listing of Technical Proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*NOTE: System requirements must conform to UFC 3-600-01
17、, “Fire Protection Engineering for Facilities“.*NOTE: The following information shall be shown on the project drawings:1. Location of Decoding/receiving console.2. Locations where recording equipment should be installed.3. Dimensions of cabinets and whether flush or SECTION 28 31 73.00 20 Page 4Prov
18、ided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-surface mounted.4. Location of the panel, bells, and other equipment.5. Location of the alarm gongs and bells.6. Location of all boxes.7. All portions of the system that will be underground and any portion
19、that will be installed in an outside overhead system.8. Cables that are to be installed in the duct-and-manhole system, the design of the system, the location of the cables, and the number of conductors in each cable.9. Cables that are to be installed in outside overhead systems, the design of the s
20、ystem, the location of the cables, and the number of conductors in each cable.10. Cables that are to be buried directly in earth, their location, where cables pass under roadways or paved areas, and the ducts or conduits used, and the number and AWG size of conductors in each cable.11. Locations of
21、the branch or “Y“ connections and the necessary related details.12. Ground connections that should be welded or brazed, if any.13. Lightning arrester locations and detail arrangement.14. System timing.15. Code Numbers of Fire Alarm Boxes: Coding shall be an integrated four-digit code. Code numbers s
22、hould not contain any digit larger than 6, shall not have succeeding digits of the number “1“ or “0.“ (Example: 1-1-3-4.) A table should indicate location of all boxes with respective code numbers.*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text o
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS28317300202010EXTERIORFIREALARMSYSTEMCLOSEDCIRCUITTELEGRAPHICTYPE 闭合 电信 外部 火警 系统 PDF

链接地址:http://www.mydoc123.com/p-984833.html