1、*USACE / NAVFAC / AFCESA / NASA UFGS-28 31 02.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 02.00 20 (November 2009)UFGS-28 31 02.00 20 (April 2006)UFGS-13854N (August 2000)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION
2、TABLE OF CONTENTSDIVISION 28 - ELECTRONIC SAFETY AND SECURITYSECTION 28 31 02.00 20FIRE ALARM REPORTING SYSTEMS - DIGITAL COMMUNICATORS02/10PART 1 GENERAL1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 DESCRIPTION OF WORK1.4 SYSTEM DESCRIPTION1.4.1 SYSTEM DESIGN1.4.2 Power Calculations1.5 SUBMITTALS1.6 QU
3、ALITY ASSURANCE1.6.1 Qualifications of Installer1.6.2 Manufacturers Representative1.6.3 Qualifications of System Technician1.6.4 Regulatory Requirements1.6.5 Drawing Requirements1.6.5.1 System Floor Plans1.6.5.2 System Wiring Diagrams1.6.5.3 System As-built Drawings1.6.6 System UL Listing or FM Appr
4、oval1.7 MAINTENANCE1.7.1 Spare Parts1.7.2 ManualsPART 2 PRODUCTS2.1 DIGITAL ALARM COMMUNICATOR TRANSMITTER (DACT)2.1.1 Transmitter Identity Code2.1.2 Transmission Confirmation2.1.3 Automatic DACT Test2.1.4 Battery Supervision2.1.5 Trouble Supervision2.1.6 DACT Power Supplies2.1.6.1 Battery Power Sup
5、ply2.2 OVERVOLTAGE AND SURGE PROTECTIONSECTION 28 31 02.00 20 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.2.1 Power Line Surge Protection2.2.2 Communications Link Surge Protection2.2.3 Sensor Wiring Surge Protection2.3 DIGITAL ALARM COMMU
6、NICATOR RECEIVER (DACR)2.3.1 Display2.3.2 Memory2.3.3 Digital Clock2.3.4 Printers2.3.5 Audible Trouble and Alarm Devices2.3.6 Power Supplies2.3.7 Emergency Power Source2.3.7.1 Emergency Power Switchover2.3.8 Console Battery Charger2.3.9 Console Supervision2.3.10 Power Supervision2.3.11 Electrical Co
7、nnections2.4 CONDUIT2.4.1 Rigid Steel Conduit (Zinc-Coated)2.4.2 Intermediate Metal Conduit (IMC)2.4.3 Electrical Metallic Tubing (EMT)2.5 OUTLET BOXES2.6 WIRING2.7 GROUND RODSPART 3 EXECUTION3.1 INSTALLATION3.1.1 Continuity of Protection3.2 FIELD QUALITY CONTROL3.2.1 Preliminary Testing3.3 FINAL AC
8、CEPTANCE TEST3.4 ADDITIONAL TESTS3.5 MAINTENANCE INSTRUCTIONS3.6 INSTRUCTION OF GOVERNMENT PERSONNEL- End of Section Table of Contents -SECTION 28 31 02.00 20 Page 2Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-
9、28 31 02.00 20 (February 2010)-Preparing Activity: NAVFAC SupersedingUFGS-28 31 02.00 20 (November 2009)UFGS-28 31 02.00 20 (April 2006)UFGS-13854N (August 2000)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated April 2010*SECTION 28 31 02.00 20FIRE ALARM REPORTING SY
10、STEMS - DIGITAL COMMUNICATORS02/10*NOTE: This guide specification covers the requirements for a complete base-wide municipal-type fire alarm system which provides reporting of fire alarms to a central location through the use of digital alarm communicator transmitters connected to various building i
11、nterior fire alarm systems.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and requirements not required in respective project, whether or not b
12、rackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of Technical Proponents, including their organization designation and telephone number, is on the Internet.Recommended changes to a U
13、FGS should be submitted as a Criteria Change Request (CCR).*NOTE: Interior building fire alarm systems are covered by Section 28 31 74.00 20 INTERIOR FIRE DETECTION AND ALARM SYSTEM.*NOTE: The following information shall be shown on the drawings:1. A complete layout of the fire alarm watch office sh
14、owing locations of new equipment and existing SECTION 28 31 02.00 20 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-equipment that is to remain. Show points of connection to power supplies.2. Locations of digital alarm communicator transmitter
15、s to be installed.3. Locations of local alarm systems and initiating devices to be connected to digital alarm communicator transmitters, and points of connection to AC power (Note: AC power shall be obtained ahead of the main disconnects).4. A table showing each transmitter location, phone number, a
16、nd the number of auxiliary zones to be connected and their descriptions (e.g., Bldg. 591, phone numbers: 555-1212, 555-1213; Zone 1 - FACP Zone 1; Zone 2 - FACP Zone 2; Zone 3 - Sprinkler Riser, etc.).*PART 1 GENERAL1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the te
17、xt of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatic
18、ally place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish prin
19、t process.*The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.FM GLOBAL (FM)FM APP GUIDE (updated on-line) Approval Guide http:/ OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)IEEE C6
20、2.41.1 (2002; R 2008) Guide on the Surges Environment in Low-Voltage (1000 V and Less) AC Power CircuitsIEEE C62.41.2 (2002) Recommended Practice on Characterization of Surges in Low-Voltage SECTION 28 31 02.00 20 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without lic
21、ense from IHS-,-,-(1000 V and Less) AC Power CircuitsNATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)NATIONAL FIRE PROTECTION ASS
22、OCIATION (NFPA)NFPA 70 (2008; AMD 1 2008) National Electrical CodeNFPA 72 (2010; Am 10-2; Am 10-3; Proposed Am 971) National Fire Alarm and Signaling CodeUNDERWRITERS LABORATORIES (UL)UL 1242 (2006; R 2001 thru 2007) Standard for Electrical Intermediate Metal Conduit - SteelUL 467 (2007) Grounding a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYUFGS28310200202010FIREALARMREPORTINGSYSTEMSDIGITALCOMMUNICATORS 火警 报告 系统 数字通讯 PDF

链接地址:http://www.mydoc123.com/p-984831.html