ASHRAE NY-08-006-2008 Evaporative Cooling Choices to Maximize Waterside Economizer Use in Datacom Installations《数字通讯装置中水侧节能器最大化的蒸发冷却选择》.pdf
《ASHRAE NY-08-006-2008 Evaporative Cooling Choices to Maximize Waterside Economizer Use in Datacom Installations《数字通讯装置中水侧节能器最大化的蒸发冷却选择》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE NY-08-006-2008 Evaporative Cooling Choices to Maximize Waterside Economizer Use in Datacom Installations《数字通讯装置中水侧节能器最大化的蒸发冷却选择》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、28 2008 ASHRAEABSTRACT Sustainability for datacom installations means providingthe necessary cooling while using a minimum of energy, a mini-mum of water, and with a minimum release of pollutants to theenvironment. Designing a system that maximizes the use ofwaterside economizers may be a way to ach
2、ieve significantenergy savings. This paper will examine three choices in evap-orative cooling (open cooling towers, closed-circuit coolers,and hybrid water/air systems) and the benefits and issues withtheir operations in waterside economizer mode. In addition,advancements in non-chemical water treat
3、ment of the openloop in evaporative cooling equipment will be discussed.INTRODUCTIONThe cooling load profile in datacom centers is signifi-cantly different from the load profile for a comfort-coolingbuilding system. The most significant differences are the highwintertime cooling load required and le
4、ss humidity generatedwith datacom installations. The high winter loading presentsan opportunity for energy reduction by maximizing the use ofwaterside economizers. In waterside economizer mode, theenergy required to remove heat is in the 0.1 kW/ton rangecompared to the 0.55 to 0.75 kW/ton energy req
5、uirementswhen running a chiller. Even when the condensing watertemperature runs as low as 60F (a practical minimum temper-ature for chiller operation), chillers will still consume about0.35 kW/ton. Most HVAC cooling towers are designed to produce aspecified amount of cool water under a specific desi
6、gn-maxi-mum ambient condition. A waterside economizer is oftenadded almost as an afterthought. For comfort-cooling HVACsystems, this is a reasonable approach since the wintertimecooling load is drastically lower than the summertime load andit is the summertime loading that drives the cooling towerde
7、sign requirements. For data centers, the load requirementsare more constant over the year, and there can be significantcooling requirements even when outside ambient tempera-tures are quite cold. In addition, the heat loading for a data-center has a much higher percentage of sensible heat than mostH
8、VAC installations. This means that there is less moisturegenerated by a datacenter load than an equivalently sizedHVAC installation. Moisture is removed by providing verycold water (45-55F) to the cooling system and having themoisture condense on the cold-water coils. With less moisturein the system
9、, warmer cold water (55-65F) might be accept-able, resulting in more efficient operation of both the chiller(less lift) and waterside economizer (more hours of operation).This paper will not consider the merits between airsideeconomizers and waterside economizers; also, this paper willnot discuss th
10、e use of multiple small chillers coupled with anevaporative condenser that operates efficiently at low headpressure; rather it will focus on how different evaporativecooling systems respond to operation during winter condi-tions. We hope that, for a specific environment, this informa-tion may lead t
11、o a design solution with overall lower energyuse and improved operational reliability. Three types of evap-orative cooling systems will be reviewed with the benefits andissues for each system. The different systems will be evaluatedfor their ability to operate in a waterside economizer modeboth reli
12、ably and over a broad range of ambient conditions.EVAPORATIVE COOLINGCooling systems transfer heat from water to air. Evapo-rative (latent) cooling systems are more efficient than dryEvaporative Cooling Choices to Maximize Waterside Economizer Use in Datacom Installations John Lane Daryn ClineAssoci
13、ate Member ASHRAE Associate Member ASHRAEJohn Lane is a Vice President of Water Treatment Systems and Daryn Cline is a Senior Manager of Environmental Technologies for Evapco,Inc., Taneytown, MD.NY-08-0062008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashra
14、e.org). Published in ASHRAE Transactions, Volume 114, Part 1. For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAEs prior written permission.ASHRAE Transactions 29(sensible) cooling systems for two reasons. Firs
15、tly, in evapo-rative cooling, a cooling tower can typically cool system waterto within 5F of the ambient wet bulb temperature, this isdefined in the industry as the “approach” to wet bulb temper-ature. Air cooled heat exchangers can only cool system waterto within approximately 15F of the ambient dr
16、y bulb temper-ature. This inherent advantage means that you can always coolto a lower leaving water temperature with respect to theoutside ambient dry bulb or in other words achieve closeapproach temperatures with evaporative cooling. The secondadvantage, which is a little less intuitive, is that th
17、e amount ofheat that can be dumped into a given volume of air is muchgreater with evaporation than with sensible (dry) cooling.A pound of air occupies the volume of about two 55-gallon drums. To raise the temperature of this pound of airfrom 77F to 78F dry bulb Fahrenheit requires about Btu.To raise
18、 this same pound of air from 77F wet bulb to 78F wetbulb requires about one Btu, four times as much heat. Thereason for this difference is that when raising the wet bulb,water evaporates into the air. The latent heat from the evapo-ration of water requires the input of additional Btus. Sincecooling
19、towers cool water by raising the wet bulb of ambientair, the volume of air is required for evaporative cooling(using wet bulb temperatures) than for dry cooling. Thisallows for much smaller equipment and fan energy to be usedwith evaporative cooling than dry cooling. An additionaladvantage is that t
20、here are few times and places in populatedareas where the wet bulb exceeds 78F, while dry bulb temper-atures in excess of 100F are not uncommon.All of these advantages of evaporative cooling diminish atlow temperatures. The amount of water that can be held in coldair is much less at low temperatures
21、 than at higher tempera-tures. While dry heating a pound of air still is about Btu atlower temperatures, to heat a pound of air from 44F wet bulbto 45F requires Btu, only about one-half of the amount at77F. In addition, while at summer conditions the differencebetween wet bulb and dry bulb temperatu
22、re can often be 10 to15F or greater, at cold temperatures the difference is oftenmuch less. These two factors, lower quantity of water that canbe held by cool air and the smaller amount of wet bulb depres-sion (difference between wet bulb and dry bulb temperature),make designing an evaporative syste
23、m to cool water to 45Fvery different from designing a system to cool water to 85F.THEORETICAL AIRFLOW REQUIREMENTSTo “dry-cool” (no water added) 100 gpm of water from95F to 85F using 78F dry bulb 75% RH (72F WB) willrequire heating an airflow of about 27,600 CFM.1To cool thesame amount of water with
24、 the same ambient conditions warm and muggy using evaporative cooling would requireonly 4,200 CFM 85% less airflow. Since the size of thesystem is related to the amount of air that must be moved, evenunder these high humidity conditions, an air-cooled systemwould need to be 7 times larger than a wat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAENY080062008EVAPORATIVECOOLINGCHOICESTOMAXIMIZEWATERSIDEECONOMIZERUSEINDATACOMINSTALLATIONS 数字通讯

链接地址:http://www.mydoc123.com/p-455532.html