1、MIL-R-24563 = 9999706 3074234 373 9 MIL-R-24563 (SHI 15 November 1977 MILITARY SPECIFICATION RELAY, ALTERNATING CURRENT. POWER-SENSING ThZa specification is approved for use by the Naval Sea Systems C-d and is available for use by all Departments and Agencies of the Department of Defense. 1. SCOPE 1
2、.1 This specification covers alternating current (a.c.), power-sensing relays (see 6.4.1) using electraaagnetic devices or solid state circuitry, or a combination of both, for we on Naval ships (sea 6.1). 2. APPLICABLE DocmENTs 2.1 Issues of documents. The following documents, of the issue in effect
3、 on date of invitationforidia or request for proposal, form a part of the specification to the extent specified herein. SPECIFICATIONS MILITARY KXL-1-631 - Insulation, Electrical, Synthetic-Resin Composition, Nonrigid. MIL-S-901 - Shock Tests H.I. (High Impact) Shipboard Machinery, Equipment and MIL
4、-E-917 - Electrical Power Equipment, Basic Requirements for (Naval Ship- MIL-E-2036 - Enclosures for Electric and Electronic Equipment, Naval Shipboard. BUL-C-2212 - Controllers, Electric Motor, A.C. or D.C. and Associated Switching MIL-E-17555 - Electronic and Electrical Equipment, Accessories, and
5、 Repair Parts: Packaging and Packing of. MIL-R-19523 - Relays, Control, Naval Shipboard. Systems, Requirements for. board Use) . Devices, Naval Shipboard. STANDARDS WILITARX ML-STO-167-1 - Mechanical Vibrations of Shipboard Equipment (Type I - hvimn- MIL-STD-454 - Standard General Requirements for E
6、lectronic Equipment. MIL-STD-740 - Airborne and Structureborne Noise Measurements and Acceptance MIL-STD-1399, Section 103 - Interface Standard for Shipboard Systems-Electric mental and Type II - Internally Excited). Criteria of Shipboard Equipment. Power, Alternating Current. PWLICATXONS MILITARY N
7、AVSEA 0969-U-019-7000 - Electronic Test Equipment Application Guide. (Copies of specifications, standards, drawings, and publications required by contractors in connection with specific procurament functions should be obtained from the procuring activity or a8 directed by the contracting officer.) t
8、he extent-i- Unless otherwise indicated, the issue in effect on date of invitation for bids or request for proposal shall apply. 2.2 Other ublications. The following document fornu a part of this specification to Beneficial coiiimants (reccmmiendations, additions, deletions) and any pertinent data v
9、hich may be of une in improving this document should be addressed to: Commander, Naval Ship Engineering Center, SEC 6124, Department of the Navy, Washington, Dc 20362 by using the self-addressed Standardization Document Improvement Proposal (DD Form 1426) appearing at the end of this document or by
10、letter. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-R-24563 m 9999906 LO94235 ZUT m MIL-R-24563 (SHI NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) ICs - Industrial Controls and Systems. (Application for copies should be addressed to th
11、e National Electrical Manufacturers (Technical society and technical association specifications and standards are generally Association, 155 East 44th Street, New York, NY 10017.) available for reference from libraries. They are also distributed among technical groups and using Federal agencies. 3.
12、REQUIREMENTS 3.1 Sample for first article ins ection. Prior to beginning production a sample power- sensing relay (hereinafter Zdkay) shall be examined and tested as specified in 4.3 (see 6.3). E-917, except the bragraphs, in addition to the requirements specified herein. (Whenever a requirement of
13、MIL-E-917 conflicts with a requirement of this specification, the requirement of this specification shall govern.) The following requirements of MIL-E-917 are not applicable unless required by the procurement docurttent: 3.2 General re uirements. Relay shall be in accordance with the requirements of
14、 MIL- (a) Piping systems. (b) Equipment cooled by forced air. (c) Equipment cooled by water. 3.2.1 Characteristics. Relay shall have the following characteristics, as specified (see 6.2.1) : (a) Relay shall sense real power from a 3-phaser 3-wire, 60 hertz (Hz) circuit (b) and change contact positio
15、n when preset actuation conditions are met. Power input to the relay shall consist of the voltage output of potential transformers providing 115 volt, 3-phase signal for the relay voltage coils and current signals from two current transformers, one in phase AB and one in phase CA for the current coi
16、ls of the relay or as otherwise specified (see 6.2.1). 6.4.2) with a contact rating of 10 amperes at 450 volts, 60 Kz. The contacts shall be electrically insulated from each other and from the relay input (see 3.2.8). Relay shall operate in an electric power system with characteristics of type I, 60
17、 Hz power as defined by MIL-STD-1399, section 103. Relay shall not be damaged nor shall have false operations caused by transients or other characteristics of a type I power system as defined in MIL-STD-1399, section 103. circuit if a fault occurs. Power level to actuate the relay shall be adjustabl
18、e in 5 percent increments (or lesa) or continuously adjustable between 80 and 150 percent of rated power. Adjustment markings shall be provided to approximate the adjustment setting. Relay shall reset to the normal condition when power to the relay is reduced to 75 + 5 percent of the set trip point.
19、 values shall not vary more than 5 percent of the set value (average of ten operating cycles). Calibration shall be at 40.C ambient temperature. Oper- ating point shall not change more than 3 percent of set value for each 1O.C change in ambient temperature between 10.C and 70.C. the actuating level.
20、 The time delay shall be adjustable from zero (no intentional delay) time delay to 20 second time delay in increments of 1 second or less. (c) Relay shall have two normally open and two normally closed contacts (see (d) Manentary short circuit power may be applied to the relay sensing (e) The trip a
21、nd reset (f) Relay shall be provided with adjustable time delay to occur after power reaches 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-R-24563 9999906 1094236 146 O a MIL-R-24563 (SE:) 3.2.2 Temperature rice (see 6.4.3). Temperature rice
22、shall not exceed the values shown in table I. TABLE I. Maximum permissible temperature based on an ambient temperature of 65OC. Name of part Bolted connections and terminal studs: Not silver plated Silver plated Class B insulation- Class F insulation- Class H insulation- Class N insuationl Solid Sol
23、id silver faced case Calculated peak junction temperature rise for discrete devices Integrated circuit devices YMeasured by resistance method. Shunt coils: Contacts : Capacitors - air within 1/2 inch of Semiconductors: Temperature rise OC 35 50 55 75 10 o 115 55 65 20 -90 Tm2/ -115 -Rated maximum op
24、erating junction temperature of the particular devices. 3.2.3 Ambient temperature (see 6.4.4). Unless otherwise specified (see 6.2.11, relay shall be designed for an ambient temperature of 65OC. 3.2.4 Endurance. The current interrupting portion of the relay (contacts) shall have a minimum life of 25
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILR245631977RELAYALTERNATINGCURRENTPOWERSENSING 功率 传感 电流继电器 PDF

链接地址:http://www.mydoc123.com/p-981215.html