NAVY MIL-F-29000-1973 FREQUENCY CONVERTER SOLID STATE 5 KVA WITH TRANSIT CASE《有运输线5 KVA固态频率转炉》.pdf
《NAVY MIL-F-29000-1973 FREQUENCY CONVERTER SOLID STATE 5 KVA WITH TRANSIT CASE《有运输线5 KVA固态频率转炉》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-F-29000-1973 FREQUENCY CONVERTER SOLID STATE 5 KVA WITH TRANSIT CASE《有运输线5 KVA固态频率转炉》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、MIL-F-29008 bL m 9999906 009L3LlO O m - 3-15-0q MIL-F-29000(MC) 27 September 1373 SUPERSEDING See Section 6. MILITARY SPECIFICATION FREQUENCY CONVERTER: SOLID STATE, 5 KVA, WITH TRANSIT CASE This specification is approved for use by all Departments and Agencies of the Department of Defense. i. SCOPE
2、 1.1 This specification covers the requirements for one type portable, solid state, parallelable 5-kilovoltampere (kVA) frequency converter, housed in a transit case. 2. APPLICABLE DOCUIENTS 2.1 The following documents of the issue in effect on the date of invitation for bids or request for proposal
3、 form a part of the specification to the extent specified herein. SPECIFICATIONS MILITARY MIL-P- 15024 MIL-E-16400 MIL-E- 17555 MIL-T- 21200 MIL-H-46855 STANDARDS FEDERAL FED-STD-595 MILITARY - Plate, Tags And Bands For Identification Of Electronic Equipment, Naval Ship And Shore, Equipment. - Gener
4、al Specification (Navy). - Electronic And Electrical Equipment, Accessories, And Repair Parts, Packaging And Packing Of. - Electrical Equipment,General Specification For. - Systems, Equipment And Facilities. Test Equipment For Use With Electronic And Human Engineering Requirements For Military - Col
5、ors. MIL-STD- 108 - Definition Of, And Basic Requirement For Enclosure MIL-STD- 167 - Mechanical Vibrations Of Shipboard Equipment. MIL-STJI-454 - Standard General Requirement For Electronic For Electric And Electronic Equipment. v Equ i pmen t. 1 Provided by IHSNot for ResaleNo reproduction or netw
6、orking permitted without license from IHS-,-,-MIL-F-27000 61 = 7777706 007L34L 2 MIL-STD-461 - Electromagnetic Interference Characteristics, Requirements For Equipment. MIL- STD- 46 2 - Electromagnetic Interference Characteristics, Measurement Of. MIL-STD-463 - Definition And System Of Units, Electr
7、omagnetic Interference Technology. MIL-STD-705 - Generator Sets, Engine-Driven, Methods Of Tests And Instructions, MIL- STD- 8 10 - Environmental Test Methods. MIL-STDp 1332 - Definitions Of Tactical, Prime, Precise, And Utility Terminologies For Classification Of The DOD Mobile Electric Power Engin
8、e Generator Set Family. I (Copies of specifications and standards required by contractors in connection with specific procurement functions should be obtained from the procuring activity or as directed by the contracting officer.) 3. REQUIREMENTS 3.1 First article. Unless otherwise specified (see 6.
9、21, prior to submission of any complete production items for acceptance, the contractor shall furnish two first articles for testing under the direction and supervision of the cognizant Government inspector to determine conformance to this specification. First article is defined as a frequency conve
10、rter which will be identical to the production units which the contractor will subsequently produce in fulfillment of the contract. Approval of the first articles by the activity concerned shall not relieve the contractor of the responsibility to supply frequency converters conforming to this specif
11、ication. Examination and testing shall be as specified herein. Any changes or deviations of the production units from the first articles shall be subject to the approval of the contracting officer. articles may be included in the final shipment as part of the total quantity to be supplied under the
12、contract, provided they have been completely refurbished. The first 3.2 Parts and materials. In the selection of parts and materials, fulfillment of major design objectives shall be the prime consideration. In all cases, general material requirements as to nonflammability, fungus resistance, and non
13、toxicity as required by MIL-E-16400 must be met. doing so, the following factors shall govern. In 3.2.1 Electronic components. Parts and materials listed in MIL-E-16400 shall be given first consideration. accordance with MIL-E-16400 will not fulfill the design objective because of size, weight, perf
14、ormance, or other reasons, the use of other materials may take precedence, with the approval of the contracting officer. When use of parts or materials in c Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-_ MIL-F-27000 61 9 7977706 007L392 m 3.2.2 Me
15、chanical components, MIL-E-16400 shall be complied with, whenever possible, without sacrifice of the design objectives of size, weight, performance, reliability and ease of maintenance. mechanical parts whose function is to rotate, oscillate or cam against others are employed, and best choice of mat
16、erials comprises materials other than those listed in MIL-E-16400, use of those materials may take precedence, with the approval of the contracting officer, provided that maximum life is achieved by use of lubricating agents, protective paints or sprays or other methods. Where 3.2.3 Moisture and fun
17、gus treatment. The frequency converters shall be fungusproofed by selection of parts and materials which are nonnutrient for fungus or by treatment of the-parts and materials priot to their use in the frequency converter so that overall spraying of the frequency converter is not necessary. 3.2.4 Tra
18、nsistor and semiconductor complement. All transistors and semiconductors used in the construction of the frequency converter shall be reported to the contracting officer by completion and submission of Form DD-816, 3.3 Design and construction. The solid state frequency converter described herein sha
19、ll be capable of converting tactical utility class 2, 60 hertz (Hz), 120/208 alternating current volts 215 percent, 3-phase power as defined in MIL-STD-1332, to 400-Hz power as specified herein. 3.3.1 Case. The frequency converter shall be provided with a transit case which shall provide protection
20、for the equipment against shock, vibration, and deterioration from all environmental conditions that might be encountered during storage, shipment and unlimited use, The transit case shall be watertight in accordance with MIL-STD-108. The case design shall include the following: (a) A tight-fitting
21、protective enclosure when the cover has been placed in position and clamped. (b) The case and cover shall make positive contact, thereby relieving loading of the gasket, except that necessary to effect a seal, (cl Only one orientation of the equipment in the case. (d) Geometric configuration which w
22、ill permit stacking without harm to the case or its contents. (e) Pressure relief valves of the manual or automatic type shall be provided with each, or on each, transit case. 3 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-F-27000 61 m 7777706
23、 0073343 6 m (f) Capability of meeting the drop test specified herein. (8) Minimum volume and weight (loaded) compatible with the applicable requirements specified herein. (h) Construction of aluminum, plastic, or a three or more ply combination resin-bonded material which shall be strong enough to
24、meet the requirements specified herein. When approved by the procuring activity, other materials may be used where a reduction in weight, with no sacrifice in performance, can be obtained. (i) The corners shall be rounded with at least 1/4-inch radius. Cases, other than all-metal types, shall be pro
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILF290001973FREQUENCYCONVERTERSOLIDSTATE5KVAWITHTRANSITCASE 运输线 KVA 固态 频率 转炉 PDF

链接地址:http://www.mydoc123.com/p-979155.html