1、- A-A-59194 9018054 O000225 BOT IMETRIC I I I A-A- 59194 5 May 1998 COMMERCIAL ITEM DESCRIPTION . BUS TRANSFER SWITCHES, ELECTRIC POWER, AUTOMATIC, SHIPBOARD (NON-NUCLEAR APPLICATIONS) The General Services Administration has authorized the use of this commercial item description, for all Federal age
2、ncies. 1. SCOPE - This Commercial Item Description (CID) covers alternating current (ac; 50, 60 or 400 Hz ) and direct current (dc) electric power bus transfer switches, automatic, for shipboard use. Semiconductor (solid state) devices used for transfer switch control circuits and solid state (stati
3、c) bus transfer switches are included. 2. CLASSIFICATION - Bus transfer devices shall be classified by type (see 2.1) and nominal fll load ampere rating (see 3.1.3.1) as defined herein. 2.1 m. The standard types of automatic bus transfer (ABT) switch are designated as follows: ABT - 1 : denotes an a
4、utomatic bus transfer switch encompassing a built-in sensig and control circuit time delay of 1.0 to 2.0 milliseconds on power source failure ( an undervoltage event of 60% of nominal ) and less than 8.33 milliseconds during a transient undervoltage, with a switching or time-to-transfer delay of 500
5、 microseconds, or less. This type is considered as being instantaneous and is applicable for use in distribution systems that supply electronic and combat system loads. The control circuit shall contain the minimum time delay period between sensing the out-of-tolerance condition to initiation of a c
6、ommand-to-transfer to preclude inadvertent transfers occurring due to short time period line voltage fluctuations. Beneficial comments, recommendations, additions, deletions, classifications, etc. and any other data which may improve this document should be sent to: Naval Sea Systems Command, Attn:
7、SEA 03R42,253 1 Jefferson Davis Highway, Arlington, VA 22242-5 106. AMSC NIA FSC 5930 DISTRIBUTION STATEMENT A. Approved for public release; distribution is uniimited. Licensed by Information Handling ServicesProvided by IHSNot for ResaleNo reproduction or networking permitted without license from I
8、HS-,-,- A-A-59194 m 9038054 0000226 746 m A-A-59194 ABT- 2: ABT- 3: denotes an automatic bus transfer switch encompassing a built-in sensing and control circuit time delay of 0.3 to 0.5 seconds and a short duration switching or time-to- transfer delay of 30.0 to 100.0 milliseconds. This type of auto
9、matic bus transfer switch is applicable for use in distribution systems that supply interior communication, general lighting and receptacle loads. The control circuit shall contain the minimum time delay period between sensig the out-of-tolerance condition to initiating a command to transfer to prec
10、lude inadvertent transfers occurring due to short time period line voltage fluctuations. The switch shall also contain the switching or time-to-transfer delay period measured as the actual time of interruption between power sources. This time period shall be factory set but field adjustable. denotes
11、 an automatic bus transfer switch encompassing a built-in sensing and control circuit time delay of 0.3 to 0.5 seconds and a long duration switching or time-to- transfer delay of 2.5 to 3.5 seconds. This type of automatic bus transfer switch is applicable for use in power distribution systems that s
12、upply transformer andlor motor loads. The control circuit shall contain the minimum time delay period between sensing the out-of-tolerance condition to initiating a command to transfer to preclude inadvertent transfers occurring due to short time period line voltage fluctuations. The switch shali al
13、so contain the switching or time-to-transfer delay period measured as the actual time of interruption between power sources. This time period shall be factory set but field adjustable. Note: Time-to-transfer is the finite period of time required by the unit to disconnect from one input source and co
14、nnect to another input source after receipt of a control circuit command. Optional additional features for each type of transfer switch shall be available when specified, and are described in Table I, Bus Transfer Switch Operating FeaturedOptions. 2.2 Part Identification. Pari identification shall b
15、e assigned to automatic bus transfer based on the designators and the operating features selected Com Table I, and shall be identified on the unit nameplate as follows: TvPe Desimator Voltage Frequency Current Rating 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without lice
16、nse from IHS-,-,-A-A-59194 = 9018054 O000227 b82 m have the device operate such that a transfer of power occurs upon loss of the pre-selected normal line source to the alternate source, and, after a purposeful time delay period, an automatic retransfer of power upon the re-establishment of correct e
17、lectrical parameters in the normal or pre- selected power source. NON-SELECTIVE - No automatic retransfer to the normal source shall occur. This switch shall hold position to the alternate source until a manual transfer is initiated or until a loss of Dower occurs on the alternate source. NS Non- 1
18、Selective A-A-59194 DESIGNATOR S I Selective 3. SALIENT CHARACTERISTICS DESCRIPTION SELECTIVE -A built-in function of the switch that allows an operator to 3.1 Automatic bus transfer (ABT) switch. PP 3.1.1 General. An automatic bus transfer switch as described in these requirements is a device that
19、automatically transfers a common load from a normal supply to an alternate supply in the event of failure of the normal supply. The automatic transfer switch shall be provided with a selectivcdnon-selective selector switch and logic control circuit that inhibits automatic operation of the device fko
20、m returning to a normal supply when the selector switch is in the non-selective position except that the ABT shall revert to automatic operation upon loss of alternate power to the load. This switch shall be integral to the design of the ABT and shall be accessible only from the interior of the encl
21、osure. A status indicator shall be provided on the exterior of the fiont panel to indicate switch position. Phase Protection The switch shall prevent transfer of input sources for all conditions of input power phase differentials greater than plus or minus 15 degrees at the time of connection to the
22、 second source. Both voltage and frequency sensing are reauired. 3.1.2 Performance. The ABT shall continuously monitor the voltage and, when specified, Erequency (for ac units only) of the input power sources and interrupt the existing power source upon sensing an out of tolerance condition by autom
23、atically connecting the output load to an available alternate power source within a predetermined period of time. ABTS shall be of the continuous duty type. The requirements of UL1008 and EEE Std 45 shall be adhered to in the design, manufacture and testing. VS SS FS TABLE I. Bus transfer switch ope
24、rating features/outions. Voltage Sensing Solid State Frequency Sensing The switch shall possess the ability to continuously monitor the input power sources for all-phase voltage magnitudes. The switch shall be constructed such that power transfers are accomplished with solid state power switching de
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYAA591941998BUSTRANSFERSWITCHESELECTRICPOWERAUTOMATICSHIPBOARDNONNUCLEARAPPLICATIONS 非核 应用 船只 电力 自动

链接地址:http://www.mydoc123.com/p-976369.html