BS EN 50133-2-1-2000 Alarm systems - Access control systems for use in security applications - General requirements for components《报警系统 安全用通路控制系统 元件一般要求》.pdf
《BS EN 50133-2-1-2000 Alarm systems - Access control systems for use in security applications - General requirements for components《报警系统 安全用通路控制系统 元件一般要求》.pdf》由会员分享,可在线阅读,更多相关《BS EN 50133-2-1-2000 Alarm systems - Access control systems for use in security applications - General requirements for components《报警系统 安全用通路控制系统 元件一般要求》.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、BRITISH STANDARD BS EN 50 133-2- 1:2000 Alarm systems - Access control systems for use in security applications - Part 2-1: General requirements for components The European Standard EN 50133-2-1:2OOO has the status of a British Standard ICs 13.320 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMED B
2、Y COPYRIGHT LAW COPYRIGHT European Committee for Electrotechnical StandardizationLicensed by Information Handling ServicesBS EN 60133-2-1:2000 AmdNo. This British Standard, having been prepared under the direction of the Consumer Products and Services Sector Committee, was pubikhed under the authori
3、ty of the Standards Committee and comes into effect on 15 November ZOO0 Date Comments Q MI 11-2000 National foreword This British standard is the official English language version of EN 50133-2-12000. The UK participation in its preparation was entrusted by Technical Committee GW/l, Electronic secur
4、ity systems, to Subcommittee GW/1/8, Access control, which has the responsibility to: - aid enquirers to understand the tea - present to the responsible European committee any enquiries on the - monitor related internatiomi and European developments and promulgate interpretation, or proposals for ch
5、ange, and keep the UK interests informed; them in the UK. A list of organizations represented on this subcommittee can be obtained on request to its secretary. Cross-references The British Stan - to collect in one document all the general requirements for component(s) of an access control system as
6、defined in the diagram shown in 4.2 of EN 50133-1. This standard may be complemented by other standards dealing with more specific requirements for individual components. In this standard, the expressions “environmental class“ and “equipment class“ are used respectively, instead of group and equipme
7、nt category, which are used in EN 50133-1, in order to be in accordance with EN 50130-5. The word component has the similar meaning to the word equipment used in EN 501 33-1 I Scope This standard provides general requirements for the components for an automated access control system as shown in 4.2
8、of EN 501 33-1. This standard does not define component functionality as this is detailed in EN 501 33-1. 2 Normative references This standard incorporates, by dated or undated reference, provision from other publications. These normative references are cited at the appropriate place in the text and
9、 the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European standard only when incorporated in it by amendment or revision. For undated references, the latest edition of the publication referred to applies. E
10、N 50102 1995 Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code). EN 501 30-5 1998 Alarm systems - Part 5: Environmental test methods. EN 50133-1 1996 Alarm systems - Access control systems for use in security applications - Part 1 : Sy
11、stem requirements. EN 60529 1991 Degrees of protection provided by enclosures (IP code) (IEC 60529: 1989). 3 Definitions For the purposes of this standard, the definitions listed in EN 501 33-1 apply together with the following. component device forming part of the access control system and carrying
12、 at least one function described in EN 501 33-1 O BSI 11-2000 COPYRIGHT European Committee for Electrotechnical StandardizationLicensed by Information Handling ServicesPage 5 EN 50133-2-1 2000 4 Requirements 4.1 General The manufacturer shall describe the functions embodied within the component(s) s
13、ubmitted for certification and shall fulfil the appropriate functional requirements as detailed in EN 501 33-1. 4.2 Electrical safety The component shall comply with requirements included in 5.4.3 of EN 50133-1, 4.3 Electromagnetic compatibility The component shall comply with requirements included
14、in 5.4.2 of EN 501 33-1. 4.4 Environmental 4.4.1 Environmental test requirements The components used in an access control system shall conform to the environmental tests listed below from EN 50130-5 and from EN 501 33-1. Details of equipment class (fixed, movable, portable) and environmental class (
15、I, II, III, IV) shall be included in the manufacturers documentation. 4.4.1.1 Dry heat, operational test The test is described in EN 501 30-5, clause 8. 4.4.1.2 Cold, operational test The test is described in EN 50130-5, clause 10. 4.4.1.3 Water, operational test The test is described in EN 50130-5,
16、 clause 16. 4.4.1.4 Impact, operational test (applicable only to recognition equipment and access point interface) The test is described in EN 501 30-5, clause 20. 4.4.1.5 Vibration, sinusoidal endurance test The test is described in EN 501 30-5, clause 23. 4.4.1.6 Supply voltage variations, operati
17、onal test The test is described in EN 501 33-1, 5.4.1.6. The word voltage in this clause means the supply voltage which is provided to the component. 4.4.1 .I Supply voltage dips and interruptions, operational test The test is described in EN 501 33-1, 5.4.1.7. Q BSI 11-2000 COPYRIGHT European Commi
18、ttee for Electrotechnical StandardizationLicensed by Information Handling ServicesPage 6 4.5 Power supply For each component of an access control system, the outputs and inputs of the power supply shall be protected against short circuit. Requirements pertaining to 5.2.1 d of EN 50133-1 concerning p
19、ower disconnection only apply when power is provided by the main distribution network. EN 501 33-2-1 :2000 NOTE: If a power supply is provided with a secondary source of power, failure of the mains should be annunciated. 4.6 Housings 4.6.1 .I Opening It shall not be possible to open components or to
20、 remove components from their mounting without the use of tools (e.g. screwdriver, keys). 4.6.2 Adjustments Adjustment points (switches, potentiometers) shall be located inside the housing of the component. The adjustment settings, which require the use of equipment (portable programmer) shall fulfi
21、l the requirements of 5.2.4 of EN 50133-1 in respect of programmability protection. 4.6.3 Cable outlets Where the construction of the housing does not provide for concealed cable entry (rear entry) this shall be clearly stated in the product documentation. 4.7 Documentation The manufacturer shall pr
22、ovide the following information: the function of the components according to the diagram of an access control system (Figure 1 and list of 4.1of EN 50133-1); security classification (recognition and access class) if applicable (see EN 50133-1, 5.1); environmental class and equipment class: electrica
23、l specifications (power supply, inputs, outputs); installation, commissioning, maintenance and operating instructions; operating temperature and humidity range; IP and IK Codes; document listing all the information needed for document checking as specified in EN 50133-1, 6.2.1. 4.8 Markinglldentific
24、ation Each access control system component shall be labelled. Q BSI 11-2000 COPYRIGHT European Committee for Electrotechnical StandardizationLicensed by Information Handling ServicesSTD-BSI BS EN 50133-2-1-ENGL 2000 1b2qbbS 0885907 Ob3 = Page 7 EN 50133-2-1:2000 As a minimum, the label shall give th
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BSEN50133212000ALARMSYSTEMSACCESSCONTROLSYSTEMSFORUSEINSECURITYAPPLICATIONSGENERALREQUIREMENTSFORCOMPONENTS
链接地址:http://www.mydoc123.com/p-574598.html