1、BRITISHSTANDARD BS6174:1982 Incorporating Amendment No.1 Specification for Differential pressure transmitters with electrical outputs UDC 621.317.39:531.787.91BS6174:1982 This BritishStandard, having been prepared under the directionof the Industrial-process Measurementand ControlStandards Committee
2、 waspublished under the authorityof the Board of BSI andcomes into effect on 26February1982 BSI 12-1999 The following BSI references relate to the work on this standard: Committee reference PCL/1 Draft for comment 74/27963 DC ISBN 0 580 12411 8 Cooperating organizations The Industrial-process Measur
3、ement and Control Standards Committee, under whose direction this BritishStandard was prepared, consists of representatives from the following: British Gas Corporation* British Industrial Measuring and Control Apparatus Manufacturers Association* British Steel Corporation Control and Automation Manu
4、facturers Association (BEAMA) Department of Industry Department of Industry (Computers Systems and Electronics) Department of Industry (National Engineering Laboratory) Department of the Environment (Water Engineering Division including Water Data Unit) Electrical, Electronic, Telecommunications and
5、 Plumbing Union Electricity Supply Industry in England and Wales* Energy Industries Council* Engineering Equipment Users Association* Institute of Measurement and Control* Institution of Gas Engineers* Oil Companies Materials Association* Post Office Engineering Union Scientific Instrument Manufactu
6、rers Association* Sira Institute The organizations marked with an asterisk in the above list, together with the following, were directly represented on the Technical Committee entrusted with the preparation of this BritishStandard: British Pressure Gauge Manufacturers Association Chemical Industries
7、 Association Department of Energy Gas Standards National Coal Board Amendments issued since publication Amd. No. Date of issue Comments 5222 September 1986 Indicated by a sideline in the marginBS6174:1982 BSI 12-1999 i Contents Page Cooperating organizations Inside front cover Foreword ii 1 Scope 1
8、2 References 1 3 Definitions 1 4 Classification 1 5 Performance 2 6 Materials and construction 4 7 Marking 5 Appendix A Test methods 6 Table 1 Limits of combined error 2 Table 2 Limits of zero shift and span change with temperature, andlimitsofresidual changes after temperature excursions 2 Table 3
9、Limits of zero shift and span change with pressure 3 Table 4 Limits of residual changes after pressure excursions 4 Table 5 Limits of average long-term drift 4 Table 6 Atmospheric conditions for reference measurements 6 Table 7 Frequency ranges for evaluation 9 Publications referred to Inside back c
10、overBS6174:1982 ii BSI 12-1999 Foreword This standard has been prepared under the direction of the Industrial-process Measurement and Control Standards Committee. The SI pressure unit “pascal” has been used throughout this standard. However, since a large sector of British industry is committed to t
11、he use of the pressure unit “bar” and intends to maintain this position, the equivalent in bars has been given in brackets after the value in pascals. A British Standard does not purport to include all the necessary provisions of a contract. Users of British Standards are responsible for their corre
12、ct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. Summary of pages This document comprises a front cover, an inside front cover, pagesi andii, pages1 to10, an inside back cover and a back cover. This standard has been updated (see copyright
13、 date) and may have had amendments incorporated. This will be indicated in the amendment table on the inside front cover.BS6174:1982 BSI 12-1999 1 1 Scope This BritishStandard specifies requirements ford.c. powered electrical transmitters with analogue direct current output used in differential pres
14、sure measurement. This standard applies only to transmitters with a linear relationship between differential pressure input and current output for general industrial use, and does not apply to aerospace, marine, laboratory and medical requirements. 2 References The titles of the publications referre
15、d to in this standard are listed on the inside back cover. 3 Definitions For the purposes of this standard the following definitions apply. 3.1 measured error the largest deviation of the output of the transmitter from its corresponding ideal value, obtained with both increasing and decreasing input
16、s NOTEMeasured error is expressed as a percentage of span and is determined in accordance with A.2.5. 3.2 hysteresis that property of an element evidenced by the dependence of the value of the output, for a given excursion of the input, upon the history of prior excursions and the direction of the c
17、urrent traverse NOTEThis is a common usage definition which includes hysteresis error and dead band. That portion of the difference which is dependent on the history of prior excursion is hysteresis error while that portion attributable to dead band may be determined by a conventional dead band test
18、. 3.3 hysteresis error that portion of hysteresis attributable to energy absorption in the elements of a measuring instrument NOTEHysteresis error should be determined by subtracting the value of dead band from the maximum measured separation between upscale-going and downscale-going indications of
19、the measured variable, during a full-range traverse unless otherwise specified. 3.4 dead band the largest change in input that can be effected without causing a detectable change of output 3.5 range the region between the limits within which a quantity is measured, received or transmitted expressed
20、by stating the lower and upper range values 3.6 lower range value the lowest value of the measured variable that a device is adjusted to measure 3.7 upper range value the highest value of the measured variable that a device is adjusted to measure 3.8 span the algebraic difference between the upper a
21、nd lower range values 3.9 over-range the condition in which the value of the input signal exceeds its upper range value or goes below its lower range value 3.10 repeatability the closeness of agreement among a number of consecutive measurements of the output for the same value of the input under the
22、 same operating conditions, approaching from the same direction, for full-range traverses 3.11 transmitter measuring transducer whose output is a standardized signal 4 Classification The performance characteristics of transmitters are classified under four headings as follows: a) accuracy class; b)
23、temperature coefficient class; c) static pressure class; d) over-range class. For fixed range transmitters the performance characteristics shall be identified by a four-element code in the above order (seeTable 1to Table 4), followed by the range of pressure within which the characteristics apply. F
24、or example:0.5A3B,0kPa to200kPa (0bar to2bar)BS6174:1982 2 BSI 12-1999 For adjustable range transmitters the performance characteristics shall be identified by four-element codes appropriate to ranges corresponding at least to the maximum and minimum spans. For example: 0.5A3B0kPa to200kPa(0bar to2b
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- BS61741982SPECIFICATIONFORDIFFERENTIALPRESSURETRANSMITTERSWITHELECTRICALOUTPUTS 电量 输出 传感器 规范 PDF

链接地址:http://www.mydoc123.com/p-545786.html