《ASTM F1869-2004 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride《用无水氯化钙测量混凝土底层地板湿气发散率的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1869-2004 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride《用无水氯化钙测量混凝土底层地板湿气发散率的标准试验方法》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 1869 04Standard Test Method forMeasuring Moisture Vapor Emission Rate of ConcreteSubfloor Using Anhydrous Calcium Chloride1This standard is issued under the fixed designation F 1869; the number immediately following the designation indicates the year oforiginal adoption or, in the cas
2、e of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the quantitative determinationof the rate of moisture vapor emitte
3、d from below-grade,on-grade, and above-grade (suspended) concrete floors.1.2 This quantity of moisture shall be expressed as the rateof moisture vapor emission, measured in pounds of moistureover a 1000 ft2area during a 24-h period.1.3 The values stated in inch-pound units are to be regardedas the s
4、tandard. The values given in parentheses are forinformation only.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices, and determine the app
5、lica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 670 Practice for Preparing Precision and Bias Statementsfor Test Methods for Constsruction MaterialsF 141 Terminology Relating to Resilient Floor Coverings2.2 Resilient Floor Covering Institute Standard:R
6、ecommended Work Practices32.3 Military Standard:Mil Spec B-131H Type 1, Class III43. Terminology3.1 Definitions: See Terminology F 141 for definitions ofthe terms, above-grade (suspended), below-grade, concrete,on-grade, and resilient flooring.3.2 Definitions of Terms Specific to This Standard:3.2.1
7、 moisture vapor emission rate (MVER)amount ofwater vapor in pounds emitted from a 1000 ft2area of concreteflooring during a 24-h period (multiply by 56.51 to convert tog/s m2).4. Significance and Use4.1 Use this test method to obtain a quantitative valueindicating the rate of moisture vapor emission
8、 from a concretefloor and whether or not that floor is acceptable to receiveresilient floor covering. The moisture vapor emission rate onlyreflects the condition of the concrete floor at the time of thetest. All concrete subfloors emit some amount of moisture invapor form. Concrete moisture emission
9、 is a natural processdriven by environmental conditions. All floor coverings aresusceptible to failure from excessive moisture vapor emissions.The moisture vapor emitted from a concrete slab is measuredin pounds. This measurement is the equivalent weight of waterevaporating from 1000 ft2of concrete
10、surface in a 24h period.The calcium chloride moisture test has been the industrystandard for making this determination and is a practical,well-established and accepted test of dynamic moisture. It willproduce quantified results directly applicable to flooring manu-facturers specifications. The resul
11、ts obtained reflect only thecondition of the concrete floor at that time.5. Apparatus5.1 Test Unit Contents:5.1.1 Cylindrical Plastic Dish Containing Anhydrous Cal-cium Chloride, heat sealed in a heat sealable bag meeting MilSpec B-131H Type 1, Class III, to protect from moistureintrusion.5.1.1.1 An
12、hydrous calcium chloride shall be in the form ofprilled beads and shall have a minimum purity of 94 %. Netweight of the anydrous calcium chloride shall be 16 6 1g.5.1.1.2 Dish shall be made of a material that does not absorbmoisture. Dimensions of the dish shall be 69 6 1 mm outsidediameter, 16 6 1
13、mm height, wall thickness less than 1 mm.Dish shall be supplied with a tight-fitting cover. The cover shallbe secured to the dish with pressure-sensitive-adhesive backedvinyl tape.1This test method is under the jurisdiction of ASTM Committee F06 on ResilientFloor Coverings and is the direct responsi
14、bility of Subcommittee F06.40 onPractices.Current edition approved June 1, 2004. Published July 2004. Originally approvedin 1998. Last previous edition approved in 2003 as F 186903.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.or
15、g. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Resilient Floor Covering Institute, 966 Hungerford Drive, Suite12-B, Rockville, MD 20850.4Available from Standardization Documents Order Desk, Bldg. 4 Section D, 70
16、0Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5.1.2 Pressure Sensitive Label, to be used to identify thecontainer of calcium chloride and to record the date, time, andcontaine
17、r weight when the test is started and completed.5.1.3 Transparent Cover, with 0.5 in. (12 mm) flangesaround the perimeter, approximately 0.5 ft2(460 6 46 cm2), asmeasured between the inside of the flanges, is required to sealthe test area of the floor. The plastic cover shall have a depthgreater tha
18、n the height of the container of anhydrous calciumchloride. The height of the container shall be 112 in. 6 0.125(38 6 3.2 mm).5.1.4 Strip of Sealant, to secure the plastic cover to the floorin an airtight fashion.5.1.5 Brightly Colored Warning Label, to be placed on theplastic cover as a protective
19、warning while the test is beingconducted.5.1.6 Mailing Bag, for the return of the sample to the partyresponsible for calculating the test results.5.2 Gram Scale, capable of measuring 0.1 g. This scale willbe used to weigh the calcium chloride container at the start andend of the test. On-site measur
20、ement is preferred to mailing thecontainer back to the supplier for results.5.3 Thermometer, capable of measuring room temperature.5.4 Hygrometer, capable of measuring the relative humidityof the test site.6. Conditioning6.1 The test site should be at the same temperature andhumidity expected during
21、 normal use. If this is not possible,then the test conditions should be 75 6 10F (23.9 6 5.5C)and 50 6 10 % relative humidity. Maintain these conditions 48h prior to, and during testing.6.2 Prior to placement of the anhydrous calcium chloridetests, the actual test area shall be clean and free of all
22、 foreignsubstances. All residual adhesives, curing compounds, sealers,paints, floor coverings, etc. shall be removed. Removal shall beaccomplished using approved OSHA work practices. Forremoval of existing resilient floorings or residual adhesive,strictly observe the Warning that follows and Notes 1
23、 and 2.(WarningDo not sand, dry sweep, dry scrape, drill, saw,beadblast, or mechanically chip or pulverize existing resilientflooring, backing, lining felt, or asphaltic cut-back adhesives.These products may contain either asbestos fibers or crystallinesilica. Avoid creating dust. Inhalation of such
24、 dust is a cancerand respiratory tract hazard. Smoking by individuals exposedto asbestos fibers greatly increases the risk of serious bodilyharm. Unless positively certain that the product containsnon-asbestos material, presume it contains asbestos. Regula-tions may require that the material be test
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF18692004STANDARDTESTMETHODFORMEASURINGMOISTUREVAPOREMISSIONRATEOFCONCRETESUBFLOORUSINGANHYDROUSCALCIUMCHLORIDE

链接地址:http://www.mydoc123.com/p-535900.html