《ASTM F1669M-1996(2007) Standard Specification for Insulation Monitors for Shipboard Electrical Systems [Metric]《船用电气设备用绝缘监控器的标准规范(米制)》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1669M-1996(2007) Standard Specification for Insulation Monitors for Shipboard Electrical Systems [Metric]《船用电气设备用绝缘监控器的标准规范(米制)》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 1669M 96 (Reapproved 2007)METRICAn American National StandardStandard Specification forInsulation Monitors for Shipboard Electrical SystemsMetric1This standard is issued under the fixed designation F 1669M; the number immediately following the designation indicates the year oforiginal
2、 adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers two (2) types of electricalsystem insula
3、tion monitoring devices.1.1.1 Type I is an ac device intended as a permanentlyinstalled unit for use in the detection of ohmic insulation faultsto ground in active ac ungrounded electrical systems up to1000 VAC, having dc components up to 1500 VDC.1.1.2 Type II is a dc device intended as a permanent
4、lyinstalled unit for use in the detection of ohmic insulation faultsto ground in dc ungrounded electrical systems up to 1500VDC.1.2 LimitationsThis specification does not cover devicesthat are intended for operation in ac ungrounded systemswithout dc components.1.3 The values stated in SI units are
5、to be regarded as thestandard. The values given in parentheses are for informationonly.1.4 The following precautionary caveat pertains only to thetest methods portion, Section 7 of this specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use
6、. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limita-tions prior to use.2. Referenced Documents2.1 UL Standard:UL STD 840 Insulation Coordination Including Clearancesand Creepage Distances for
7、Electrical Equipment22.2 IEC Standards:3IEC 255-5 Insulation Tests for Electrical RelaysIEC 364-4-41 Electrical Installations of Buildings/Protection for Safety/Protection Against Electrical Shock2.3 Military Standard:MIL-STD-1399 (NAVY) Section 300A Interface Standardsfor Shipboard Systems; Electri
8、cal Power, AlternatingCurrent43. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 ac or dc ungrounded electrical system, na systemthat has no intentional connection to ground and can continueto perform normally if one conductor becomes connected toground.3.1.2 measuring signal, nt
9、he output signal from the insu-lation monitor that is superimposed between the ac or dcungrounded system to be monitored and ground.3.1.3 response value, nthe adjustable or preset set-pointvalue of the system insulation resistance at which an insulationmonitor will provide an alarm indication.3.1.4
10、system leakage capacitance, nthe total capacitanceto ground of the system including all connected consumers.3.1.5 touch voltage, nthe voltage appearing during aninsulation fault, between simultaneously accessible parts. Thisterm is used only in connection with protection against indirecthuman contac
11、ts, that is, no direct human contact with a liveconductor. The International Electrotechnical Commission(IEC) limits the maximum prospective touch voltage which canbe maintained indefinitely to 50 VAC rms or 120 V ripple-freedc.4. Ordering Information4.1 Orders for monitoring devices under this spec
12、ificationshall state the following information:4.1.1 Type and quantity.4.1.2 Nominal system voltage and frequency (for ac sys-tem).4.1.3 Input supply voltage.4.1.4 Response value/set-point range expressed in K-Ohms.1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marin
13、e Technology and is the direct responsibility of Subcommittee F25.10 inElectrical.Current edition approved May 1, 2007. Published June 2007. Originallyapproved in 1996. Last previous edition approved in 2002 as F 1669M - 96(2002).2Available from Underwriters Laboratories (UL), 333 Pfingsten Rd., Nor
14、th-brook, IL 60062-2096, http:/.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.4Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700Robbins Ave., Philadelphia, PA 19111-5098, Attn: NPODS.1Copyright
15、 ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.1.5 ASTM designation and year of issue.4.1.6 System leakage capacitance or data from which anestimate of its magnitude can be determined.4.1.7 Special requirements such as Test/Reset buttons, o
16、hm-meters, visual indicators, memory fault retention, and so forth.5. Materials and Manufacturing Methods5.1 The materials and manufacturing methods used shall besuch that the resulting products will conform to the propertiesand characteristics prescribed in this specification.6. Performance Require
17、ments6.1 Response of Insulation Monitor to a Step InputTheinsulation monitor measures the combined parallel resistanceto ground from all power or circuit conductors. The time torespond to a step change in the actual resistance to a value lessthan or equal to 50 % of the desired response value shall
18、begoverned by the expression:t s! #100 1 40 RI3 Cs! (1)whereRI= internal resistance of monitor, ohm, andCs= total system capacitance, farad.For example,t 5 124 sifRI5 120 000 ohm and Cs5 5 3 1026farad.6.2 Measuring Signal Voltage LimitsThe peak value ofthe measuring signal shall under all operating
19、conditions belimited to a magnitude deemed acceptable by applicable safetystandards for the intended use.The peak value of the measuringsignal shall be less than the touch voltage limits: 120 VDCripple-free and 50 VAC rms.6.3 Internal Impedance and Internal ResistanceThe acinternal impedance and dc
20、internal resistance shall be at least30 ohms per volt nominal system voltage but in either caseshall not be less than 12 K-Ohms.6.4 Response ToleranceThe response tolerance of themonitor shall not exceed 0 to +50 % of the upper value of theset point range when measured at a room temperature of 25 65
21、C (72 6 9F), with an input supply voltage 80115 % of itsnominal value and with a system leakage capacitance equal tothe value at which the monitor is calibrated (1 fd minimum).6.5 Working Range of System Voltage and FrequencyTheinsulation monitor shall perform as specified when operatingwith a syste
22、m voltage of 0115 % nominal over the frequencyrange 50400 hz.6.6 Self-TestThe insulation monitor shall include abuilt-in test device or be equipped with connection provisionsfor a separate device that shall be furnished with the equipmentwhich can verify the proper functioning for the monitor.6.7 Ou
23、tput RelayThe insulation monitor shall have pro-visions for an external (remote) audible or visual alarm tooperate when the insulation resistance value falls below theset-point value or a remote indication of the insulation resis-tance value of the ungrounded system, or both. Built-in relayscontacts
24、 for connection to an external alarm shall have acontinuous rating of at least 4 amperes at 250 VAC. The breakcapacity shall be at least 2 amps at 250 VAC (0.7 power factor)and 0.3 amps at 120 VDC.6.8 Built-In Display of Insulation ResistanceIf provisionsare made to indicate (display) the current in
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF1669M19962007STANDARDSPECIFICATIONFORINSULATIONMONITORSFORSHIPBOARDELECTRICALSYSTEMSMETRIC 用电 备用

链接地址:http://www.mydoc123.com/p-535367.html