ASTM F1134-2012 Standard Specification for Insulation Resistance Monitor for Shipboard Electrical Motors and Generators《船用电动机和发电机绝缘电阻监测器的标准规范》.pdf
《ASTM F1134-2012 Standard Specification for Insulation Resistance Monitor for Shipboard Electrical Motors and Generators《船用电动机和发电机绝缘电阻监测器的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1134-2012 Standard Specification for Insulation Resistance Monitor for Shipboard Electrical Motors and Generators《船用电动机和发电机绝缘电阻监测器的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1134 12 An American National StandardStandard Specification forInsulation Resistance Monitor for Shipboard ElectricalMotors and Generators1This standard is issued under the fixed designation F1134; the number immediately following the designation indicates the year oforiginal adoption
2、or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers monitoring devices (monitors)for the automatic dete
3、ction and signaling of low insulationresistance values in idle electrical motors or generators, orboth.1.2 Monitors are intended for permanent installation in bothexisting or new panels and controller enclosures designed formarine application.1.3 The values stated in SI units are to be regarded as t
4、hestandard. The values given in parentheses are for informationonly.1.4 The following safety hazards caveat pertains only to thetest method described in this specification: This standard doesnot purport to address all of the safety concerns, if any,associated with its use. It is the responsibility o
5、f the user of thisstandard to establish appropriate safety and health practicesand determine the applicability of regulatory limitations priorto use.2. Referenced Documents2.1 UL Standard:2UL 94 Test for Flammability of Plastic Materials for Parts inDevices and Appliances2.2 IEEE Standards:3IEEE 45
6、Recommended Practice for Electrical Installationson ShipboardIEEE 100 Standard Dictionary of Electrical and ElectronicsTerms2.3 Government Standard:Title 46 Code of Federal Regulations Shipping43. Terminology3.1 DefinitionsIn general, definitions shall be in accor-dance with IEEE 100 (see Section 2)
7、.3.2 Definitions of Terms Specific to This Standard:3.2.1 idle machinerotary machine, when not rotating,owing to the absence of energy.3.2.2 monitordevice, generally located in a motor starter,control panel, or main switchboard, that senses the leakageresistance of electrical machine windings to gro
8、und, while themonitored machine stands idle.4. Monitor Classification4.1 TypeThe insulation resistance monitors covered bythis specification shall be of the following types:4.1.1 Type IAlternating current motor monitors.4.1.2 Type IIAlternating current generator monitors.4.1.3 Type IIIDirect current
9、 motor monitors.4.1.4 Type IVDirect current generator monitors.4.2 Duty RatingAll monitors shall be capable of continu-ous duty operations as defined in accordance with IEEE 100.5. Ordering Information5.1 Monitoring devices shall be ordered by including thefollowing information:5.1.1 Purpose or Use
10、of Monitor(s)Application as motoror generator monitor.5.1.2 Line voltage and frequency.5.1.3 Control voltage and frequency.5.1.4 Type of starter (if motor monitor).5.1.5 Winding configuration (if motor monitor).5.1.6 Location of monitor.5.1.7 SensitivitySet for 1 megohm (optional setting, ifrequeste
11、d, from 0.1 to 5 M).5.1.8 Remote monitoring devices.5.1.9 Special options requested (that is, test buttons, el-evated ambient temperature usage, and so forth.).6. Materials and Manufacture6.1 GeneralMaterials used in the construction of insula-tion resistance monitors are to be manufactured and test
12、ed inaccordance with IEEE 45. Materials conforming to other1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Technology and is the direct responsibility of Subcommittee F25.10 onElectrical.Current edition approved Oct. 1, 2012. Published November 2012. Originally
13、approved in 1988. Last previous edition approved in 2007 as F1134 - 94(2007).DOI: 10.1520/F1134-12.2Available from Underwriters Laboratories (UL), 333 Pfingsten Rd.,Northbrook, IL 60062-2096, http:/.3Available from Institute of Electrical and Electronics Engineers, Inc. (IEEE),445 Hoes Ln., P.O. Box
14、 1331, Piscataway, NJ 08854-1331, http:/www.ieee.org.4Available from Superintendent of Documents, U.S. Government PrintingOffice, Washington, DC 20402.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1recognized standards will be subjec
15、t to approval by theprocuring agency, provided they are not less effective.6.2 Flame-Retardant MaterialsEnclosure materials usedin the construction of the monitors are to be flame-retardant inaccordance with UL 94, and have a minimum flame rating of94V-1 for monitors being installed within a motor c
16、ontrollerenclosure, or switchgear-type enclosure, or a minimum ratingof 94-5V for monitors not installed within such an enclosure.6.3 Electrical InsulationElectrical insulation materialsused and application thereof shall be in accordance with therequirements of IEEE 45.6.4 Current Carrying Terminals
17、All monitor current car-rying terminals shall be made of corrosion resistant material inaccordance with CFR 46, Subchapter J.6.5 Electrical IsolationMonitors shall isolate their mea-suring circuit from the line voltage, while the motor isoperating, by the use of an integral isolating relay.7. Genera
18、l Design Requirements7.1 Environment:7.1.1 TemperatureThe rating of the monitor shall be basedon an ambient temperature of 50C (122F).7.1.1.1 Operating Temperature RangeMonitors shall op-erate over the range from 0 to 50C (32 to 122F). (See 10.1.2for operation range.)7.1.2 SealingUpon final assembly
19、, the monitor housingshall protect the internal components against foreign matterand shall be constructed so as to prevent tampering.7.1.3 InclinationMonitors shall operate at inclinationangles up to 60 in any direction from the normal operatingposition.7.1.4 HumidityMonitors shall operate at a cons
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF11342012STANDARDSPECIFICATIONFORINSULATIONRESISTANCEMONITORFORSHIPBOARDELECTRICALMOTORSANDGENERATORS

链接地址:http://www.mydoc123.com/p-534250.html