《ASTM F150-2006(2013) Standard Test Method for Electrical Resistance of Conductive and Static Dissipative Resilient Flooring《导电的和静态消散弹性地板材料电阻的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM F150-2006(2013) Standard Test Method for Electrical Resistance of Conductive and Static Dissipative Resilient Flooring《导电的和静态消散弹性地板材料电阻的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F150 06 (Reapproved 2013)Standard Test Method forElectrical Resistance of Conductive and Static DissipativeResilient Flooring1This standard is issued under the fixed designation F150; the number immediately following the designation indicates the year of originaladoption or, in the case
2、 of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.Asuperscriptepsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This test metho
3、d covers the determination of electricalconductance or resistance of resilient flooring either in tile orsheet form, for applications such as hospitals, computer rooms,clean rooms, access flooring, munition plants, or any otherenvironment concerning personnel-generated static electricity.1.2 This st
4、andard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1
5、 ASTM Standards:2D2240 Test Method for Rubber PropertyDurometer Hard-ness3. Terminology3.1 Definitions:3.1.1 conductive flooringa floor material that has a resis-tance to between 2.5 104and 1.0 106.3.1.2 dissipative floor materialfloor material that has aresistance between 1.0 106to 1.0 109.4. Signi
6、ficance and Use4.1 Conductive and static dissipative floors (static controlflooring) serve as a convenient means of electrically connect-ing persons and objects together to prevent the accumulation ofelectrostatic charges. A static control floor is specified on thebasis of controlled resistance valu
7、es. The surface of the floorprovides a path of moderate electrical conductivity between allpersons and equipment making contact with the floor toprevent the accumulation of dangerous electrostatic charges.Static control footwear will need to be used in conjunction withthe floor for the floor to perf
8、orm effectively with personnel.4.2 The resistance of some flooring materials change withage. Floors of such materials should have an initial resistancelow enough or high enough to permit increase or decrease inresistance with age without exceeding the limits prescribed inthe product specifications.5
9、. Apparatus5.1 Self-Contained Resistance Meter (such as a megohmmeter) or power supplies and current meters in the appropriateconfiguration for resistance measurement with 610 % accu-racy. For safety, all power supplies used herein should becurrent limited, usually below 5.0 mA. This apparatus shall
10、 becapable of open circuit voltages of 100 VDC 6 10 %, and 10VDC 6 10 %. Test leads should be isolated from ground.5.2 ElectrodesTwo cylindrical 5 lb 6 1 oz (2.27 kg 6 28g) metal electrodes shall have a diameter of 2.5 6 0.062 in.(63.5 6 1.58 mm) each having contacts of electrically conduc-tive mate
11、rial with a Shore-A (IRHD) durometer hardness of5070 (Test Method D2240). The electrically conductivematerial may be permanently attached to the electrode. Theresistance between the electrodes shall be less than 1 Kohmswhen measured at 10 V or less on a metallic surface.6. Test Specimen6.1 Qualifica
12、tion TestingWhen mounting specimen, useinsulative support material (14 in. (6.35 mm) tempered hard-board is recommended). Use manufacturers recommendedprocedures, adhesives, and grounding method to install thesample floor. The specimen shall consist of a portion of floorcovering 48 by 48 in. (1.22 b
13、y 1.22 m) in area. If a qualificationtest is required, one specimen shall be tested unless otherwisespecified. Unless otherwise specified, make five measurementson the specimen with electrodes at different locations for eachmeasurement and record the value to two significant figures.6.2 When the fol
14、lowing is to be tested after jobsiteinstallation, the specimen shall be a portion of the floor notexceeding 20 by 20 ft (6 by 6 m) in dimensions.1This test method is under the jurisdiction ofASTM Committee F06 on ResilientFloor Coverings and is the direct responsibility of Subcommittee F06.20 on Tes
15、tMethods - Products Construction/Materials.Current edition approved May 15, 2013. Published July 2013. Originallyapproved in 1972. Last previous edition approved in 2006 as F150 - 06. DOI:10.1520/F0150-06R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Custome
16、r Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States17. Conditioning7.1 Whenever possible, c
17、ondition the test specimen at least24 h at 73.4 6 1.8F (23 6 1C) and 50 6 5 % relativehumidity, and test in the same environment.8. Procedure8.1 Qualification TestingPlace the installed specimen asdescribed in 6.1 on a nonconductive surface, and lightly wipewith a lint-free cloth to remove any forei
18、gn material prior toplacing of the electrodes. The surfaces of the electrodes, priorto placing, should be cleaned with a minimum 70 %isopropanol-water solution using a clean low linting cloth.Allow to dry. Follow the manufacturers recommendation as tothe time after installation prior to testing.8.1.
19、1 Surface to Surface Test:8.1.1.1 For conductive floorsPlace the electrodes at least1 in. (25.4 mm) in from an edge of the specimen and 36 in.(914.4 mm) apart. Set meter to 10 VDC, and apply the voltageand take the reading 15 s after the application of voltage oronce the reading has reached equilibr
20、ium. If the reading isbelow 1.0 106, record the reading. If the reading is higherthan 1.0 106, change the voltage to 100 VDC and take thereading 15 s after the application of voltage or once the readinghas reached equilibrium and record the reading.8.1.1.2 For static dissipative floorsPlace the elec
21、trodes atleast 1 in. (25.4 mm) in from an edge of the specimen and 36in. (914.4 mm) apart. Apply the prescribed voltage (either 100VDC or 10 VDC) and take a reading 15 s after the applicationof voltage or once the reading has reached equilibrium. If thefloor is known to be greater than 1.0 106 use 1
22、00 VDC.8.1.2 Surface to Ground TestAttach the positive electrodeor the positive wire from the megohm meter to the groundconnection and place the negative electrode on the surface ofthe flooring material. The negative electrode should be over 6in. (152.4 mm) from the ground connection and over 6 in.(
23、152.4 mm) from any metal ground strip embedded in theadhesive.8.1.2.1 For conductive floorsSet meter to 10 VDC, applythe voltage and take the reading 15 s after the application ofvoltage or once the reading has reached equilibrium. If thereading is below 1.0 106, record the reading. If the readingis
24、 higher than 1.0 106, change the voltage to 100 VDC andtake the reading 15 s after the application of voltage or once thereading has reached equilibrium and record the reading.8.1.2.2 For static dissipative floorsApply the prescribedvoltage (either 100 VDC or 10 VDC) and take a reading 15 safter the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF15020062013STANDARDTESTMETHODFORELECTRICALRESISTANCEOFCONDUCTIVEANDSTATICDISSIPATIVERESILIENTFLOORING

链接地址:http://www.mydoc123.com/p-532472.html