ASTM E2768-2011(2018) Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test).pdf
《ASTM E2768-2011(2018) Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test).pdf》由会员分享,可在线阅读,更多相关《ASTM E2768-2011(2018) Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test).pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2768 11 (Reapproved 2018) An American National StandardStandard Test Method forExtended Duration Surface Burning Characteristics ofBuilding Materials (30 min Tunnel Test)1This standard is issued under the fixed designation E2768; the number immediately following the designation indicat
2、es the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 The purpose of this fire-test-response standa
3、rd is toevaluate the ability of a product to limit the surface spread offlame when evaluated for 30 min. This fire-test-responsestandard uses the apparatus and procedure of Test Method E84with the total test period extended to 30 min.1.2 Building applications affecting fire and life safety oftenrequ
4、ire products with specific criteria for surface spread offlame and flame spread index. The resulting performancecharacteristics included in the conditions of classification forthis fire-test-response standard are intended to be used forregulatory purposes to determine the suitability of materials or
5、products for use in buildings under specified conditions wheresignificantly reduced surface burning characteristics are re-quired.1.3 Materials and products that are beyond the scope of TestMethod E84 are beyond the scope of this standard.1.4 Materials or products which melt, drip or delaminate toth
6、e extent that the continuity of the flame front is destroyed arebeyond the scope of this standard.NOTE 1Testing of materials that melt, drip, or delaminate to such adegree that the continuity of the flame-front is destroyed, results in lowflame spread indices that do not relate directly to indices o
7、btained bytesting materials that remain in place. Materials or products that melt, drip,or delaminate, or that cannot support their own weight, have the potentialfor demonstrating reduced flame spread results as compared to the flamespread results where the materials or products remain in place duri
8、ngtesting.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 The text of this standard references notes and footnotesthat provide ex
9、planatory information. These notes andfootnotes, excluding tables and figures, shall not be consideredas requirements of the standard.1.7 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itse
10、lfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions1.8 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standar
11、d to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limitations prior to use.1.9 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.1.10 This international
12、 standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee
13、.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE176 Terminology of Fire Standards2.2 ICC Codes3IBC International Building CodeIWUIC International Wildland Urban Interface CodeIRC International Residential Code2.3 NFPA Code4NFPA 101
14、 Life Safety Code1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.22 on SurfaceBurning.Current edition approved Aug. 1, 2018. Published August 2018. Originallyapproved in 2011. Last previous edition approved in 20
15、11 as E2768-11. DOI:10.1520/E2768-11R18.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3ICC codes are availa
16、ble from International Code Council, 4051 W. FlossmoorRd., Country Club Hills, IL 60478.4NFPA Codes are available from National Fire Protection Association, 1Batterymarch Park, Quincy, MA, 02269.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. Unite
17、d StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers
18、to Trade (TBT) Committee.12.4 California Building Code5CBC California Building Code3. Terminology3.1 DefinitionsFor definitions of terms used in this testmethod, refer to Terminology E176 and Test Method E84. Theterms surface flame spread, flame spread index, and smokedeveloped index are of particul
19、ar interest to this standard.4. Summary of Test Method4.1 This test method is conducted using the sameequipment, apparatus, calibration, and calculation of flamespread index and smoke developed index as Test Method E84.4.2 Test Method E84 exposes a nominal 24-ft long by 20-inwide (7.32 m by 508 mm)
20、specimen to a controlled air flow andflaming fire exposure adjusted to spread the flame along theentire length of the select grade red oak specimen in 5.5 min(615 s). Test Method E84 measures the flame spread distancefrom a point beginning 4.5 ft (1.4 m) beyond the centerline ofthe burners.4.3 The f
21、lame spread index is determined during the initial10 min of the test period and calculated as described in TestMethod E84.4.4 In this test method, the Test Method E84 test is extendedby 20 min to a 30 min test period. Determination is made of thedistance traveled by the flame front (surface spread o
22、f flame) asmeasured from the centerline of the burners during the 30 mintest period.4.5 The test method has conditions for classification inSection 13.5. Significance and Use5.1 This standard is useful to establish the relative surfaceburning characteristics of materials or products under labora-tor
23、y conditions for a 30 min test period.5.2 The performance characteristics in the conditions ofclassification are intended to be used in specific applications asrequired by building codes or other regulatory requirements orspecifications.5.3 This test method does not provide the measurement ofheat tr
24、ansmission through the tested surface.5.4 This test method does not provide the classification ordefinition of a material or product as noncombustible, bymeans of the results from this standard test or flame spreadindex by itself.6. Apparatus/Test Equipment6.1 The apparatus, equipment, recording dev
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME276820112018STANDARDTESTMETHODFOREXTENDEDDURATIONSURFACEBURNINGCHARACTERISTICSOFBUILDINGMATERIALS30MINTUNNELTESTPDF

链接地址:http://www.mydoc123.com/p-531856.html