ASTM E2750-2017 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM 《按照ASTM实施阻火渗透系统试验的数据扩展用标准指南》.pdf
《ASTM E2750-2017 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM 《按照ASTM实施阻火渗透系统试验的数据扩展用标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2750-2017 Standard Guide for Extension of Data from Penetration Firestop System Tests Conducted in Accordance with ASTM 《按照ASTM实施阻火渗透系统试验的数据扩展用标准指南》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2750 131E2750 17 An American National StandardStandard Guide forExtension of Data from Penetration Firestop System TestsConducted in Accordance with ASTM E8141This standard is issued under the fixed designation E2750; the number immediately following the designation indicates the year
2、oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1 NOTEThe title of this guide was corrected editorially in February 2
3、013.1. Scope1.1 This guide covers the extension of results obtained from fire tests performed in accordance with Test Method E814 toapplications that have not been tested. Test Method E814 evaluates the duration for which test specimens will contain a fire, retaintheir integrity, or both during a pr
4、edetermined fire test exposure. Firestops are intended for use in fire-resistive walls and floors thatare evaluated in conformance with Test Method E119.NOTE 1Data obtained from firestops tested in accordance with Test Methods E119 with positive pressure can also be used.1.2 This guide is based on p
5、rinciples involving the extension of test data using simple considerations. The acceptance of theseprinciples and their application is based substantially on an analogous worst-case proposition.1.3 These principles are only applicable to temperature conditions represented by the standard time-temper
6、ature curve describedin Test Method E814, for systems falling within the scope of Test Method E814. This test method is a fire-test-response standard.1.4 The types of building constructions which are part of this guide are as follows: floors, walls, partitions, floor/ceiling androof/ceiling assembli
7、es.1.5 This guide applies to:1.5.1 a single penetrating item, or1.5.2 multiple penetrating items.1.6 This guide does not apply to joints systems tested to E119, E1966 and E2307.1.7 Penetrating items can be one of the following: metallic pipe, non-metallic pipe, metallic tubing, non-metallic tubing,m
8、etallic conduit, non-metallic conduit, flexible metal conduit, cables, cable trays, bus ducts, insulated pipes, insulated tubing,insulated conduit, insulated and non-insulated ducts, and structural members.Metallic pipe, tubing or conduit 6.7Insulated pipe, tubing or conduit 6.8Non-metallic pipe, tu
9、bing or conduit 6.9 and 6.10Flexible metal conduit 6.11.1.4 and 6.11.1.5Cables 6.11Cable tray 6.12Bus duct 6.13Non-insulated duct 6.14Insulated duct 6.14.2Non-structural or service support member 6.15Mixed penetrations 6.161.8 Assemblies can be one of the following; concrete floors or walls, masonry
10、 walls, gypsum walls, wood floor/ceilingassemblies, concrete floor/ceiling assemblies, chase wall in floor/ceiling assemblies and fire-rated insulated walls.Concrete floors or walls 6.1Masonry walls 6.1Gypsum board wall assemblies 6.2Wood floor/ceiling assemblies 6.3Floor/ceiling assembly with concr
11、ete floor 6.4Chase wall intersecting a floor/ceiling assembly 6.5Fire-resistance insulated walls 6.61 This standard guide is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved Jan. 1, 2013
12、Nov. 1, 2017. Published February 2013December 2017. Originally approved in 2011. Last previous edition approved in 20112013as E2750-11.-131. DOI: 10.1520/E2750-13E01.10.1520/E2750-17.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of w
13、hat changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered t
14、he official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.9 The extension of data using numerical calculations based on empirical data or theoretical models is not covered in this guide.1.10 This guide does not cover the
15、substitution of one proprietary material for another proprietary material, or materials forwhich fire-test data are not presently available.1.11 This guide is used to predict or provide a quantitative measure of the fire hazard from a specified set of fire conditionsinvolving specific materials, pro
16、ducts, or assemblies. This assessment does not necessarily predict the hazard of actual fires whichinvolve conditions other than those assumed in the analysis.1.12 This guide is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditio
17、ns, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,products or assemblies under actual fire conditions.1.13 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.1.14
18、 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety safety, health, and healthenvironmental practices and determine theapplicability of regulatory limitations prio
19、r to use.1.15 This international standard was developed in accordance with internationally recognized principles on standardizationestablished in the Decision on Principles for the Development of International Standards, Guides and Recommendations issuedby the World Trade Organization Technical Barr
20、iers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationE119 Test Methods for Fire Tests of Building Construction and MaterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE814 Test Method for Fire Tests o
21、f Penetration Firestop SystemsE1966 Test Method for Fire-Resistive Joint SystemsE2032 Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E 119E2307 Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale, Multi-story TestA
22、pparatus2.2 Other Standards:ACI 216 Fire Resistance of Concrete33. Terminology3.1 Definitions:3.1.1 For definitions used in this guide, refer to Terminologies in E176, C168 and E631.3.1.2 For definitions of terms specific to this standard, refer to E814 and E2032.4. Significance and Use4.1 The metho
23、ds and procedures set forth in this guide relate to the extension of the fire test results to firestop systems that havenot been tested.4.2 Users of this guide must have knowledge and understanding of the provisions of Test Method E119 and Test Method E814including those pertaining to conditions of
24、acceptance.4.3 In order to apply some of the principles described in this guide, reference to the original fire test report will be necessary.4.4 In Test Method E814, the specimens are subjected to specific laboratory fire test exposure conditions. Differences betweenthe tested assembly and the as-b
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME27502017STANDARDGUIDEFOREXTENSIONOFDATAFROMPENETRATIONFIRESTOPSYSTEMTESTSCONDUCTEDINACCORDANCEWITHASTM

链接地址:http://www.mydoc123.com/p-531822.html