ASTM E2359 E2359M-2013(2018) Standard Test Method for Field Pull Testing of an In-Place Exterior Insulation and Finish System Clad Wall Assembly.pdf
《ASTM E2359 E2359M-2013(2018) Standard Test Method for Field Pull Testing of an In-Place Exterior Insulation and Finish System Clad Wall Assembly.pdf》由会员分享,可在线阅读,更多相关《ASTM E2359 E2359M-2013(2018) Standard Test Method for Field Pull Testing of an In-Place Exterior Insulation and Finish System Clad Wall Assembly.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2359/E2359M 13 (Reapproved 2018)Standard Test Method forField Pull Testing of an In-Place Exterior Insulation andFinish System Clad Wall Assembly1This standard is issued under the fixed designation E2359/E2359M; the number immediately following the designation indicates the yearof orig
2、inal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers a procedure to determine theresistance
3、of a section of the exterior insulation and finishsystem (EIFS) to outward loads imposed on an existingexterior wall assembly that has been in place on the buildingfor an unspecified period of time. It is destructive in naturewithin the localized areas tested and requires appropriate repairof the EI
4、FS cladding and sheathing once the test procedure hasbeen completed. This test procedure utilizes mechanical meth-ods to obtain information, which may be helpful in evaluatingthe natural application of negative wind loads on the EIFSassembly. Some variability of results should be anticipatedwithin t
5、he wall assembly tested due to differences in installa-tion procedures, exposure, or abuse subsequent to application.1.2 This test method is suitable for use on cladding assem-blies that have been in place a short time (new construction), aswell as for longer periods in order to evaluate detrimental
6、effects on the EIFS lamina, insulation attachment, substrateintegrity, and attachments after exposure to weather and otherenvironmental conditions. It is not intended to evaluate theperformance of structural framing. Test results on any particu-lar building may be highly variable depending on specim
7、enlocation and condition, and are subject to interpretation by thetest specifier.1.3 The values stated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be exact equivalents; therefore, eachsystem shall be used independently of t
8、he other. Combiningvalues from the two systems may result in non-conformancewith the standard.1.4 This standard may involve hazardous materials,operations, or equipment. This standard does not purport toaddress all of the safety concerns associated with its use. It isthe responsibility of the user o
9、f this standard to establishappropriate safety, health, and environmental practices and todetermine the applicability of regulatory limitations prior touse.NOTE 1Due to variations in exposure and construction assemblies,field specimens selected for testing utilizing this test method mayexperience su
10、dden failure and release of the imposed loads. See Note 7 forfurther information.1.5 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides
11、 and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2D3665 Practice for Random Sampling of Construction Ma-terialsE631 Terminology of Building ConstructionsE2110 Terminology for Exterior Insulation and Fini
12、sh Sys-tems (EIFS)E2128 Guide for Evaluating Water Leakage of BuildingWalls2.2 American Society of Civil Engineers (ASCE):3SEI/ASCE 7-05, Minimum Design Loads for Buildings andOther Structures3. Terminology3.1 For general terminology regarding EIFS and building ingeneral, see Terminology E2110 (for
13、EIFS terms) and Termi-nology E631 (for buildings in general).3.2 Definitions of Terms Specific to This Standard:3.2.1 face delamination, nfailure mode by which the faceof the sheathing loses bond or delaminates from the sheathingcore, either partially or fully.1This test method is under the jurisdic
14、tion of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.58on Exterior Insulation and Finish Systems (EIFS).Current edition approved Sept. 1, 2018. Published September 2018. Originallyapproved in 2006. Last previous edition approved in 2013 as E2359/
15、E2359M13.DOI: 10.1520/E2359_E2359M13R18.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Ameri
16、can Society of Civil Engineers (ASCE), 1801 AlexanderBell Dr., Reston, VA 20191, http:/www.asce.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized
17、 principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.13.2.2 fastener pull-out from stud, nfailure mode by whichfastener rel
18、eases from the substrate.3.2.3 fastener pull-through, nfailure mode by which thehead of the fastener pulls through the sheathing, insulation, orsubstrate.3.2.4 lamina release, nfailure mode by which the EIFSbase coat and finish coat release their bond to the underlyingthermal insulation board layer.
19、3.2.5 thermal insulation board failure, ncohesive failurewithin the thermal insulation board.4. Significance and Use4.1 The purpose of this test method is to assess the instal-lation adequacy and the overall effects of service-relateddeterioration (moisture, etc.) on the EIFS wall assembly asopposed
20、 to small localized areas of degradation. Resistance topull testing as determined by this test is used as one of thefactors in evaluating the EIFS assembly on a specific project.The values obtained by this test method are not purported to berepresentative of the actual wind load capacity or otherstr
21、uctural properties of a specific EIFS clad wall installation,but may be helpful in assessing such load capacities.4.2 Since this test is used for field evaluation of existingfacilities, load results obtained from this test must be inter-preted based on sound engineering practice, applicable build-in
22、g regulations, and codes having jurisdiction. It is the discre-tion of the test specifier to directly utilize the results derived bythis test method, or else to utilize the test results with anappropriate factor of safety to obtain acceptable working loadsfor each project.4.3 This method is intended
23、 for use on test specimensoccurring or installed on existing buildings. The loss ofoutward wind load resistance of an EIFS wall assembly afterexposure to moisture and other weather conditions may com-promise the ability of the cladding or other wall components toperform adequately in place. This tes
24、t method does not provideany means by which the test results may be generalized to thelarger wall area. Such efforts should be based on experienceand engineering judgement.4.4 The manner in which the test load is applied may affectthe load capacity obtained from using this test method. Adiscussion o
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME2359E2359M20132018STANDARDTESTMETHODFORFIELDPULLTESTINGOFANINPLACEEXTERIORINSULATIONANDFINISHSYSTEMCLADWALLASSEMBLYPDF

链接地址:http://www.mydoc123.com/p-530968.html