《ASTM E2032-2009(2017) Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E&x2009 119《与ASTM E 119保持一致的耐火性试验中数据扩展用标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2032-2009(2017) Standard Guide for Extension of Data From Fire Resistance Tests Conducted in Accordance with ASTM E&x2009 119《与ASTM E 119保持一致的耐火性试验中数据扩展用标准指南》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2032 09 (Reapproved 2017) An American National StandardStandard Guide forExtension of Data From Fire Resistance Tests Conducted inAccordance with ASTM E 1191This standard is issued under the fixed designation E2032; the number immediately following the designation indicates the year of
2、original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers the extension of fire resistance ratingso
3、btained from fire tests performed in accordance with TestMethod E119 to constructions that have not been tested. TestMethod E119 evaluates the duration for which test specimenswill contain a fire, retain their standard integrity, or both duringa predetermined test exposure.1.2 This guide is based on
4、 principles involving the exten-sion of test data using simple considerations. The acceptance ofthese principles and their application is based substantially onan analogous worst case proposition.1.3 These principles are only applicable to temperatureconditions represented by the standard time-tempe
5、rature curvedescribed in Test Method E119. Test Method E119 is afire-test-response standard.1.4 The types of building constructions which are thesubject of this guide are categorized as follows: beams; floorand roof assemblies; columns; and walls and partitions. Floorand roof assemblies include such
6、 assemblies with ceilingprotective membranes.1.5 The extension of test data using numerical calculationsbased on empirical data or theoretical models is not covered inthis guide.1.6 This guide does not cover the substitution of oneproprietary material for another proprietary material, or mate-rials
7、for which fire test data are not presently available.1.7 This guide does not purport to be comprehensive in itstreatment of non-proprietary modifications of tested construc-tions. Engineering evaluation or tests are recommended forassessing modifications not specifically covered in this guide.1.8 Th
8、e values stated in SI units are to be regarded asstandard.1.9 This standard is used to determine certain fire-testresponses of materials, products, or assemblies to heat andflame under controlled conditions by using results obtainedfrom fire-test-response standards. The results obtained fromusing th
9、is standard do not by themselves constitute measures offire hazard or fire risk.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and de
10、termine the applica-bility of regulatory limitations prior to use.1.11 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-men
11、dations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC553 Specification for Mineral Fiber Blanket Thermal Insu-lation for Commercial and Industrial ApplicationsC612 Specific
12、ation for Mineral Fiber Block and BoardThermal InsulationE119 Test Methods for Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE1264 Classification for Acoustical Ceiling ProductsE1513 Practice for Application of Sprayed Fir
13、e-ResistiveMaterials (SFRMs)3. Terminology3.1 Definitions:3.1.1 For definitions used in this guide, refer to Terminolo-gies E176, C168, E631, and Test Method E119.1This standard guide is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E0
14、5.11 on FireResistance.Current edition approved April 1, 2017. Published April 2017. Originallyapproved in 1999. Last previous edition approved in 2013 as E203209(2013). DOI:10.1520/E2032-09R17.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at s
15、erviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordanc
16、e with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.13.1.2 mineral fiber insulation, nins
17、ulation composed prin-cipally of fibers manufactured from rock, slag, or glassprocessed from molten state into fibrous form to compriseflexible batts or blankets, rigid or semi-rigid blocks and boards,or loose fill insulations, with or without binder.3.1.2.1 DiscussionMineral fiber blanket thermal i
18、nsula-tions and mineral fiber block and board thermal insulations areclassified into various types based upon the maximum usetemperature, which can range from 204C (400F) to 982C(1800F), and the apparent thermal conductivity (See Specifi-cations C553 and C612).3.1.3 unit weight, nas applied to concr
19、ete, weight per unitvolume.3.2 Definitions of Terms Specific to This Standard:3.2.1 acoustical ceiling panel, na form of a prefabricatedsound absorbing ceiling element used with exposed suspensionsystems (see Specification E1264).3.2.2 acoustical ceiling tile, na form of a prefabricatedsound absorbi
20、ng ceiling element used with concealed orsemi-exposed suspension systems, stapling, or adhesive bond-ing (see Specification E1264).3.2.3 beams, nall horizontally oriented structural mem-bers employed in building construction and known variously asbeams, joists, or girders.3.2.4 ceiling protective me
21、mbrane, na ceiling membraneattached to or suspended from the structural members of thefloor or ceiling assembly, usually by hanger wire or threadedrods, consisting of a grid suspension system with lay-in ceilingpanels or a grid of steel furring channels to which the ceilingmembrane is directly attac
22、hed, intended to provide fireprotection, acoustical and or aesthetic enhancements, or both.3.2.5 composite, nas applied to loadbearing elements, aninteraction between structural components which is to be takeninto account in the evaluation of load capacity.3.2.6 design load, nthe intended maximum de
23、sign loadcondition allowed by design under appropriate nationallyrecognized structural design criteria.3.2.7 directly applied fire resistive coating, nmaterials thatare normally sprayed onto substrates to provide fire-resistiveprotection of the substrates.3.2.7.1 DiscussionThese coatings are called
24、sprayed fire-resistive materials in Standard Practice E1513 and relatedstandards.3.2.8 equivalent thickness, nthe calculated solid thicknessof concrete or masonry for purposes of determining fireresistance ratings of barrier elements on the basis of heattransmission end-point criteria.3.2.9 insulati
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME203220092017STANDARDGUIDEFOREXTENSIONOFDATAFROMFIRERESISTANCETESTSCONDUCTEDINACCORDANCEWITHASTMEX2009119

链接地址:http://www.mydoc123.com/p-530107.html