ASTM E1645-2001(2007) Standard Practice for Preparation of Dried Paint Samples by Hotplate or Microwave Digestion for Subsequent Lead Analysis《热板法或微波溶解法连续分析铅含量用干漆样品制备的标准实施规程》.pdf
《ASTM E1645-2001(2007) Standard Practice for Preparation of Dried Paint Samples by Hotplate or Microwave Digestion for Subsequent Lead Analysis《热板法或微波溶解法连续分析铅含量用干漆样品制备的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1645-2001(2007) Standard Practice for Preparation of Dried Paint Samples by Hotplate or Microwave Digestion for Subsequent Lead Analysis《热板法或微波溶解法连续分析铅含量用干漆样品制备的标准实施规程》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1645 01 (Reapproved 2007)Standard Practice forPreparation of Dried Paint Samples by Hotplate orMicrowave Digestion for Subsequent Lead Analysis1This standard is issued under the fixed designation E 1645; the number immediately following the designation indicates the year oforiginal ad
2、option or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the sample preparation proceduresfor paint sampl
3、es that are collected during the assessment,management or control of lead hazards.1.2 This practice describes the digestion procedures using ahot plate or microwave oven or apparatus for paint samples thatare to be analyzed for lead content.1.3 This practice covers the general considerations forquan
4、titative sample extraction for total recoverable lead indried paint samples (either bulk paint or paint powder) usinghot plate or microwave heating techniques, or both.1.4 The values stated in SI units are to be regarded as thestandard.1.5 This practice contains notes that are explanatory and notpar
5、t of the mandatory requirements of the standard.1.6 This practice is based on two NIOSH Methods, 7082and 7105, and on an EPA standard operating procedure for leadin paint.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility
6、 of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificprecautionary statements, see 6.2.4.4 and 7.2.1.2. Referenced Documents2.1 ASTM Standards:2D 1129 Terminology Relating to WaterD 11
7、93 Specification for Reagent WaterE 1605 Terminology Relating to Lead in BuildingsE 1729 Practice for Field Collection of Dried Paint Samplesfor Subsequent Lead Determination2.2 Other Documents:Environmental Protection Agency, Standard Operating Pro-cedures for Lead in Paint by Hotplate- or Microwav
8、e-based Acid Digestions and Atomic Absorption or Induc-tively Coupled Plasma Emission Spectrometry; U.S. EPA,Research Triangle Park, NC (1991). (NTIS No.PB92114172)3NIOSH Manual of Analytical Methods, P.M. Eller and M.E.Cassinelli, Eds., 4th ed., Methods 7082 and 7105; Na-tional Institute for Occupa
9、tional Safety (800)35NIOSH.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.except that it has no sample placed initially into the digestionvessel. (The same reagents and processing conditions that areapplied to field samples within a
10、 batch are also applied to thereagent blank.)3.1.7.1 DiscussionAnalysis results from this sample pro-vide information on the level of potential contaminationresulting from only laboratory sources that are experienced bysamples processed within the batch.3.1.8 reference material (certified reference
11、material)(CRM)a material of known composition where the lead levelis certified by the manufacturer.3.1.9 sample seta group of samples (one or more).3.1.10 spiked sample or spiked duplicate sample a blankmedium that contains no purposely added analyte to which aknown amount of analyte is added before
12、 preparation.3.1.10.1 DiscussionAnalysis results for these samples areused to provide information on the precision and accuracy ofthe overall process.4. Summary of Practice4.1 Lead in dried paint samples (chips, powder, etc.) issolubilized (extracted) by digestion with nitric acid and hydro-gen pero
13、xide facilitated by heat, or by a mixture of nitric acidand hydrochloric acid facilitated by microwave energy. (It isassumed that the paint samples were collected in accordancewith Practice E 1729; however, this practice can be used forany collected paint sample.) The lead content of the digestedsam
14、ple is then in a form ready for measurement.5. Significance and Use5.1 Paint in buildings and related structures needs to bemonitored for lead content in order to determine the potentiallead hazard. Hence, effective and efficient methods are requiredfor the preparation of paint samples that may cont
15、ain lead.5.2 This practice may be used for the digestion of paintsamples that are collected during various lead-hazard controland risk assessment activities associated with lead abatement inand around buildings and related structures. This practice isalso suitable for the digestion of paint samples
16、collected fromlocations such as commercial buildings.5.3 This practice may be used to prepare samples that havebeen obtained in order to ensure compliance with laws thatgovern lead content in paints.5.4 This practice may be used to prepare samples that havebeen collected for risk assessment purposes
17、.5.5 This practice is intended for use with paint samples thatare prepared for subsequent analysis by laboratory-basedquantitative analytical methods.6. Apparatus6.1 Heating Equipment:6.1.1 Electric Hot Platesuitable for operation at surfacetemperatures up to at least 140C. A temperature of at least
18、100C, as measured by a thermometer placed inside a boro-silicate glass container (on the hot plate) filled with digestionsolution, should be attainable. (See Note 1.)NOTE 1Provided that the hot plate is capable of handling the extraheating required, use of a 12 to 25-mm (approximately 0.5 to 1-in.)
19、thickaluminum plate placed on the burner head can help reduce the presence ofhot spots common to electric hot plates.6.1.2 Microwave Extraction ApparatusCaution: Ensure that manufacturers safety recommenda-tions are followed.NOTE 2The procedure described is for microwave digestion systemswith a temp
20、erature control system. Microwave digestion systems that areequipped only with a pressure control system or lower pressure vessels, orboth, may be used, provided that a prior assessment of the dissolutionefficiency is carried out.6.1.2.1 Microwave Digestion Systemdesigned for closedvessel digestion,
21、 with power output regulation, fitted with atemperature control system capable of sensing the temperatureto within 62C, and automatically adjusting the microwavepower output within 2 s. The microwave cavity shall beresistant to chemical attack, and equipped with exhaust venti-lation for acid vapor p
22、rotection of the unit and operator. Allelectronics shall be protected against corrosion to ensure safeoperation. Safety interlocks, to shut off magnetron poweroutput, shall be contained within the oven door openingmechanism.Caution: Domestic (kitchen) microwave ovens shall not beused, since there ar
23、e very significant hazards associated withtheir use for the procedure described in this standard. Forexample, acid vapors released into the cavity can corrodesafety devices that prevent the magnetron from shutting offwhen the door is opened, potentially exposing the operator tomicrowave energy.Also,
24、 the fumes generated can be extremelyhazardous.NOTE 3Apressure control system is also very useful, since it providesa safeguard against the possibility of sample loss due to excessive pressurebuildup and partial venting of the sample vessels.6.1.2.2 Lined Sample Vesselsclosed, designed for carry-ing
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME164520012007STANDARDPRACTICEFORPREPARATIONOFDRIEDPAINTSAMPLESBYHOTPLATEORMICROWAVEDIGESTIONFORSUBSEQUENTLEADANALYSIS

链接地址:http://www.mydoc123.com/p-529129.html