ASTM D6301-2013 0625 Standard Practice for Collection of On-Line Composite Samples of Suspended Solids and Ionic Solids in Process Water《选择生产用水中悬浮固体和离子固体即时综合样品的标准实施规程》.pdf
《ASTM D6301-2013 0625 Standard Practice for Collection of On-Line Composite Samples of Suspended Solids and Ionic Solids in Process Water《选择生产用水中悬浮固体和离子固体即时综合样品的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6301-2013 0625 Standard Practice for Collection of On-Line Composite Samples of Suspended Solids and Ionic Solids in Process Water《选择生产用水中悬浮固体和离子固体即时综合样品的标准实施规程》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D6301 13Standard Practice forCollection of On-Line Composite Samples of SuspendedSolids and Ionic Solids in Process Water1This standard is issued under the fixed designation D6301; the number immediately following the designation indicates the year oforiginal adoption or, in the case of
2、 revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice is applicable for sampling condensedsteam or water, such as boiler feedwater, for
3、 the collection ofsuspended solids and (optional) ionic solids using a 0.45-mmembrane filter (suspended solids) and ion exchange media(ionic solids). As the major suspended component found inmost boiler feedwaters is some form of corrosion product fromthe preboiler system, the device used for this p
4、ractice iscommonly called a corrosion product sampler.1.2 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is therespons
5、ibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D1066 Practice for Sampling SteamD1129 Terminology Relating to WaterD1193 Specification for Re
6、agent WaterD1971 Practices for Digestion of Water Samples for Deter-mination of Metals by FlameAtomicAbsorption, GraphiteFurnace Atomic Absorption, Plasma EmissionSpectroscopy, or Plasma Mass SpectrometryD2332 Practice for Analysis of Water-Formed Deposits byWavelength-Dispersive X-Ray FluorescenceD
7、2777 Practice for Determination of Precision and Bias ofApplicable Test Methods of Committee D19 on WaterD3370 Practices for Sampling Water from Closed ConduitsD3864 Guide for On-Line Monitoring Systems for WaterAnalysis3. Terminology3.1 DefinitionsFor definitions of terms used in thispractice, refe
8、r to Terminology D1129.3.2 Definitions of Terms Specific to This Standard:3.2.1 corrosion product sampler, na device used to collectintegrated samples of suspended solids and (as an option) ionicsolids.3.2.1.1 DiscussionIt consists of a flow totalizer that accu-rately measures the amount of sample p
9、assing through thedevice and a 0.45-m pore size membrane filter. Adding asecond filter for ion exchange resin impregnated membranesallows for collecting ionic solids.3.2.2 ionic solids, nincludes all matter that will passthrough a 0.45-m pore size filter and may be captured onanion, or cation ion ex
10、change membranes, or both.3.2.3 suspended solids, nincludes all matter that is re-moved by a 0.45-m pore size filter.4. Summary of Practice4.1 A typical sampling apparatus, or corrosion productsampler, is used to obtain integrated, representative samples ofsuspended solids and ionic solids using a 0
11、.45-m membranefilter and ion exchange membranes. The sampling is accom-plished at system operating pressure or after pressurereduction, and sample temperature of 50C. The practiceutilizes a modified stainless steel high pressure filter housing toaccommodate a 47-mm diameter filter (for suspended sol
12、ids)and if desired, ion exchange membranes (for ionic solids). Thesample collection system (corrosion product sampler) is de-signed and operated specifically for quantitative collection ofsuspended solids and ionic solids. An important feature of thesampler is the flow totalizer, which accurately de
13、termines thetotal volume of sample that has passed through the sampler,regardless of changes in flowrate or pressure during thecollection period. Control and pressure reducing valves andmetering devices are downstream of the filter housing toeliminate the possible contribution of suspended solids an
14、dionic solids from these components to the sample stream.1This practice is under the jurisdiction of ASTM Committee D19 on Water andis the direct responsibility of Subcommittee D19.03 on Sampling Water andWater-Formed Deposits, Analysis of Water for Power Generation and Process Use,On-Line Water Ana
15、lysis, and Surveillance of Water.Current edition approved July 15, 2013. Published August 2013. Originallyapproved in 1998. Last previous edition approved in 2008 as D6301 08. DOI:10.1520/D6301-13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service a
16、t serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1FIG. 1 Simplified Flow Diagram for Corrosion Produ
17、ct SamplerD6301 132Additional flow may bypass the filter housing, so that flowswithin the sample lines are maintained within required range(see Guide D3864). If a single sampling point is not represen-tative due to lack of homogeneity in the process fluid (the waterbeing sampled), multiple point sam
18、pling may be required.5. Significance and Use5.1 The transport of any suspended solids or corrosionproducts from the preboiler cycle has been shown to bedetrimental to all types of steam generating equipment. Cor-rosion product transport as low as 10 ppb can have significantimpact on steam generator
19、s performance.5.2 Deposited corrosion products on PWR steam generatortubes can reduce heat transfer, and, if the deposit is sufficientlythick, can provide a local area for impurities in the bulk waterto concentrate, resulting in a corrosive environment. In BWRplants, the transport of corrosion produ
20、cts can cause fuelfailure, out of core radiation problems from activationreactions, and other material related problems.5.3 In fossil plants, the transport of corrosion products canreduce heat transfer in the boilers leading to tube failures fromoverheating. The removal of these corrosion products b
21、ychemical cleaning is expensive and potentially harmful to theboiler tubes.5.4 Normally, grab samples are not sensitive enough todetect changes in the level of corrosion product transport.Also,system transients may be missed by only taking grab samples.An integrated sample over time will increase th
22、e sensitivity fordetecting the corrosion products and provide a better under-standing of the total corrosion product transport to steamgenerators.6. Interferences6.1 The ion exchange capacity may be exceeded if anexcessive volume of sample is passed through the ion exchangemedia.6.2 The removal effi
23、ciency of the ion exchange media isflowrate and matrix dependent and could show variations fromlot to lot.6.3 Sample temperature greater than 50C may have delete-rious effects on the ion exchange media.6.4 The corrosion products collected on the 0.45-m filtermay be loose so care should be taken to p
24、revent loss of sample.6.5 Due to settling, or deposition, or both, in sampling lineswith low velocity, flow in sampling lines must be turbulent andmaintained at a velocity of 1.8 m/s (6 ft/s) (see also PracticesD3370).7. Apparatus7.1 Sample heat exchanger, made of such material that fullsystem press
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD630120130625STANDARDPRACTICEFORCOLLECTIONOFONLINECOMPOSITESAMPLESOFSUSPENDEDSOLIDSANDIONICSOLIDSINPROCESSWATER

链接地址:http://www.mydoc123.com/p-522122.html