《ASTM D6268-2015 9502 Standard Practice for Handling Transportation and Storage of HFC-125 Pentafluoroethane (C2HF5)《搬动 运输和存放HFC-125 五氟乙烷 (C2HF5) 的标准实践规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6268-2015 9502 Standard Practice for Handling Transportation and Storage of HFC-125 Pentafluoroethane (C2HF5)《搬动 运输和存放HFC-125 五氟乙烷 (C2HF5) 的标准实践规程》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D6268 15Standard Practice forHandling, Transportation, and Storage of HFC-125,Pentafluoroethane (C2HF5)1This standard is issued under the fixed designation D6268; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the yea
2、r of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers guidance and direction to suppliers,purchasers, and users in the handling, transportation, a
3、ndstorage of HFC-125, pentafluoroethane (C2HF5).1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to
4、 address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D6231 Spe
5、cification for HFC-125 (Pentafluoroethane,C2HF5)2.2 CGA Standards:3C-1 Methods for Hydrostatic Testing of Compressed GasCylindersC-6 Standards for Visual Inspection of Steel CompressedGas CylindersC-7 Guide to Preparation of Precautionary Labeling andMarking of Compressed Gas ContainersP-1 Safe Hand
6、ling of Compressed Gases in ContainersSB-1 Hazards of Refilling Compressed Refrigerant (Haloge-nated Hydrocarbon) Gas CylindersSB-5 Safety Bulletin: Hazards of Reusing Disposable Re-frigerant (Halogenated Hydrocarbon) Gas CylindersSB-18 Safety Bulletin: Use of Refrigerant (HalogenatedHydrocarbons) R
7、ecovery Cylinders2.3 U.S. Government Standards:4Code of Federal Regulations (CFR) Title 40, Part82.106, Environmental Protection Agency, Warning State-ment RequirementsCFR Title 49, Part 172, U.S. DOT Hazardous MaterialsTable, Special Provisions, Hazardous MaterialsCommunications, Emergency Response
8、 Information, andTraining RequirementsCFR Title 49, Part 172.101, U.S. DOT Tables of HazardousMaterials and Special ProvisionsCFR Title 49, Part 173, U.S. DOT Shippers-General Re-quirements for Shipping and PackagingCFR Title 49, Part 178, U.S. DOT Specification for Pack-agingsCFR Title 49, Part 180
9、, U.S. DOT Continuing Qualificationand Maintenance of Packagings3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 containersstorage vessels for HFC-125.3.1.2 cylinderscontainers of HFC-125.3.1.3 HFC-125pentafluoroethane, a compound used toinert, extinguish or suppress a fire or
10、explosion hazard.3.1.4 insulatedplaced in an isolated situation to protectand prevent the transfer of damage.4. Significance and Use4.1 This practice provides requirements for the handling,transportation, and storage of HFC-125 encountered in distri-bution through both commercial and military channe
11、ls. It isintended to insure that HFC-125 is handled, transported, andstored in such a way its physical properties are not degraded.Transport may be by various means, such as, but not limited to,highway, rail, water, and air.1This practice is under the jurisdiction of ASTM Committee D26 on Haloge-nat
12、ed Organic Solvents and Fire Extinguishing Agents and is the direct responsi-bility of Subcommittee D26.09 on Fire Extinguishing Agents.Current edition approved Jan. 1, 2015. Published April 2015. Originallyapproved in 1998. Last previous edition approved in 2009 as D626809. DOI:10.1520/D6268-15.2Fo
13、r referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from the Compressed Gas Association (CGA), 14501 Geor
14、ge CarterWay, Suite 103, Chantilly, VA 20151, http:/.4Available from U.S. Government Publishing Office, 732 N. Capitol St., NW,Washington, DC 204010001, http:/www.gpo.gov.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States15. Practice5.1
15、To ensure safe handling, loading, unloading, storing,and transporting of material, personnel shall be trained in theCGA publications and Title 49 CFR regulations as listed in 2.2and 2.3, respectively.5.2 Handling:5.2.1 Handling shall be in accordance with CGA P-1, SafeHandling of Compressed Gases in
16、 Containers, and as specifiedby the manufacturer.5.2.1.1 Personnel who handle or store, or both, cylinders ofHFC-125 shall be trained properly to recognize and identify thecharacteristics of the product and the proper methods of safelyhandling full, partly full, and empty cylinders.5.2.2 All HFC-125
17、 transfers between storage containers andrecycling processes shall be performed by personnel trained inhandling procedures.5.2.2.1 HFC-125 recycling and transfer processes shall be inconjunction with the equipment specified by the manufacturer.5.2.3 HFC-125 handling shall be in nonsmoking, heater-fr
18、ee, ventilated areas to preclude product accumulation. Provi-sions shall be made to ensure that service areas limit HFC-125concentrations to not exceed 10 % for 1 min and 0.1 % for 8 h.5.2.4 Cylinders shall not be overfilled. The maximum per-mitted filling density shall be 59 lb/ft3(945 kg/m3). The
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD626820159502STANDARDPRACTICEFORHANDLINGTRANSPORTATIONANDSTORAGEOFHFC125PENTAFLUOROETHANEC2HF5 搬动

链接地址:http://www.mydoc123.com/p-522016.html