ASTM D5424-2005 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Configurati.pdf
《ASTM D5424-2005 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Configurati.pdf》由会员分享,可在线阅读,更多相关《ASTM D5424-2005 Standard Test Method for Smoke Obscuration of Insulating Materials Contained in Electrical or Optical Fiber Cables When Burning in a Vertical Cable Tray Configurati.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 5424 05An American National StandardStandard Test Method forSmoke Obscuration of Insulating Materials Contained inElectrical or Optical Fiber Cables When Burning in a VerticalCable Tray Configuration1This standard is issued under the fixed designation D 5424; the number immediately fo
2、llowing the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This is a fir
3、e-test-response standard.1.2 This test method provides a means to measure thesmoke obscuration resulting from burning electrical insulatingmaterials contained in electrical or optical fiber cables whenthe cable specimens, excluding accessories, are subjected to aspecified flaming ignition source and
4、 burn freely under wellventilated conditions.1.3 This test method provides two different protocols forexposing the materials, when made into cable specimens, to anignition source (approximately 20 kW), for a 20 min testduration. Use it to determine the flame propagation and smokerelease characterist
5、ics of the materials contained in single andmulticonductor electrical or optical fiber cables designed foruse in cable trays.1.4 This test method does not provide information on thefire performance of electrical or optical fiber cables in fireconditions other than the ones specifically used in this
6、testmethod nor does it measure the contribution of the cables to adeveloping fire condition.1.5 Data describing the burning behavior from ignition tothe end of the test are obtained.1.6 The production of light obscuring smoke is measured.1.7 The burning behavior is documented visually, by pho-tograp
7、hic or video recordings, or both.1.8 The test equipment is suitable for making other, op-tional, measurements, including the rate of heat release of theburning specimen, by an oxygen consumption technique andweight loss.1.9 Another set of optional measurements are the concen-trations of certain toxi
8、c gas species in the combustion gases.1.10 The values stated in SI units are to be regarded as thestandard (see IEEE/ASTM SI 10).1.11 This standard measures and describes the response ofmaterials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporat
9、e allfactors required for fire hazard or fire risk assessment of thematerials, products or assemblies under actual fire conditions.1.12 Fire testing of products and materials is inherentlyhazardous. Employ adequate safeguards for personnel andproperty in conducting these tests.1.13 This standard doe
10、s not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Stan
11、dards:2D 1711 Terminology Relating to Electrical InsulationE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 176 Terminology of Fire StandardsE 800 Guide for Measurement of Gases Present or Gener-ated During FiresE 1354 Test Method for Heat and Visible Smoke ReleaseRates for
12、Materials and Products Using an Oxygen Con-sumption CalorimeterIEEE/ASTM SI 10 Standard for Use of the InternationalSystem of Units (SI): The Modern Metric System2.2 NFPA Standard:3ANSI/NFPA 70-1990 National Electrical Code1990, Na-tional Fire Protection Association32.3 Underwriters Laboratories Sta
13、ndards:4UL 1056 Fire Test of Upholstered Furniture, UnderwritersLaboratories, 1989UL 1581 Reference Standard for Electrical Wires, Cables,and Flexible Cords, March 6, 1987, Underwriters Labo-ratories, Inc., ANSI/UL 1581-1985UL 1685 Standard Vertical Tray Fire Propagation and1This test method is unde
14、r the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct responsibility ofSubcommittee D09.21 on Fire Performance Standards.Current edition approved September 1, 2005. Published October 2005. Originallyapproved in 1993. Last previous edition approve
15、d in 1999 as D 5424 99.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from National Fire Protecti
16、on Association, Batterymarch Park,Quincy, MA 02269.4Available from Underwriters Laboratories, Inc., 333 Pfingsten Rd., Northbrook,IL 60062.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.Smoke Release Test for Electrical and Optical
17、FiberCables, Underwriters Laboratories, Inc., January 27, 19922.4 Canadian Standards Association Standards:5CSA Standard FT-4 Vertical Flame Tests: Cables in CableTrays, Section 4.11.4 in C22.2 No. 0.3-M1985, TestMethods for Electrical Wires and Cables2.5 IEEE Standards:6IEEE 1202-1991 Standard for
18、Flame Testing of Cables forUse in Cable Tray in Industrial and Commercial Occu-pancies, May 29, 1991.2.6 Other Standards:CATechnical Bulletin 133 Flammability Test Procedure forSeating Furniture for Use in Public Occupancies, January,19917Nordtest Method NT Fire 032 Upholstered Furniture: Burn-ing B
19、ehaviorFull Scale Test8ISO 13943 Fire SafetyVocabulary93. Terminology3.1 For definitions of terms used in this test method andassociated with fire issues, refer to Terminology E 176 andISO 13943. In case of conflict, the definitions given in Termi-nology E 176 shall prevail. For definitions of terms
20、 used in thistest method and associated with electrical insulation issues,refer to Terminology D 1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 sample, nan amount of the cable type and construc-tion to be tested, which is representative of the product for test.3.2.2 specimen, nthe ind
21、ividual length of cable, or cablebundle, to be placed in the cable tray, which is representativeof the product to be tested.4. Summary of Test Method4.1 This fire-test-response standard determines a number offire-test-response characteristics associated with smoke obscu-ration resulting from burning
22、 the materials insulating full-scalespecimens of electrical or optical fiber cables located in avertical cable tray and ignited with a propane gas burner. Thistest method is also suitable for making other, optional mea-surements, including rates of heat release, total amounts of heatreleased, rates
23、and concentrations of carbon oxides releasedand rates and amounts of mass of the specimen lost (seeAppendix X2). Further optional measurements are also pos-sible.4.2 The vertical cable tray that holds the specimen is locatedin an enclosure of specified dimensions.4.3 A hood, connected to a duct, is
24、located above the fireenclosure. Smoke release instrumentation is placed in the duct.Heat and gas analysis release instrumentation (optional) is alsoplaced in the duct.4.4 Two different test procedures are specified, which differin the burner used and in the electrical or optical fiber cableloading.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD54242005STANDARDTESTMETHODFORSMOKEOBSCURATIONOFINSULATINGMATERIALSCONTAINEDINELECTRICALOROPTICALFIBERCABLESWHENBURNINGINAVERTICALCABLETRAYCONFIGURATIPDF

链接地址:http://www.mydoc123.com/p-519743.html