《ASTM C636 C636M-2006 Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels.pdf》由会员分享,可在线阅读,更多相关《ASTM C636 C636M-2006 Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-In Panels.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 636/C 636M 06Standard Practice forInstallation of Metal Ceiling Suspension Systems forAcoustical Tile and Lay-In Panels1This standard is issued under the fixed designation C 636/C 636M; the number immediately following the designation indicates the yearof original adoption or, in the
2、case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This p
3、ractice covers the installation of suspension sys-tems for acoustical tile and lay-in panels. It is applicable tocontractors whose services are utilized for installing acousticalceilings and to other trades if their activities are responsible forinterference with ceiling components or performance as
4、 de-fined in this recommended practice.1.2 While the practices described in this document haveequal application to rated fire-resistive suspension systems,additional requirements may have been imposed to obtain thefire endurance classification of particular floor-ceiling or roof-ceiling assemblies.
5、These details should be obtained from themanufacturers.1.3 Similarly, additional detailing may be necessary to meetsound attenuation requirements when ceiling plenums extendover contiguous rooms. These, too, should be obtained fromthe manufacturer of the acoustical material employed.1.4 The values s
6、tated in either inch-pound units or SI unitsare to be regarded as the standard. Within the text, the SI unitsare shown in brackets. The values stated in each system are notexact equivalents; therefore, each system must be used inde-pendently of the other. Combining values fro the two systemsmay resu
7、lt in nonconformance with the specification.1.5 While many of the practices described in this practicehave application to the installation of metal suspension systemsin exterior environments, the specific design of exterior ceilinginstallations requires the review and approval of the architector eng
8、ineer, or both, who are responsible for the constructionof the building or modifications to an existing building. Whilerecommendations from the manufacturer should be solicited, itremains the final responsibility of the architect/engineer toensure proper application of the materials in question.1.6
9、This standard does not purport to address of the safetyconcerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety andhealth practices and determine the applicability of regulatorylimitations prior to use.2. Installation of Componen
10、ts2.1 Hangers:2.1.1 Where acoustical ceilings are suspended from a struc-ture of wood construction, attach hangers with suitable me-chanical devices either to the bottom edge of the wood joists orto the vertical face of the wood joists near the bottom edge.Holding power tests certified by the manufa
11、cturer must beavailable on request for bottom edge attachment devices.2.1.2 Where acoustical ceilings are suspended from a struc-ture of concrete construction, mount hangers using cast-in-place hanger wires, hanger inserts, or other hanger attachmentdevices whose suitability has been demonstrated by
12、 standardconstruction practice or by certified test data.2.1.3 Space hangers for carrying channels or main runners 4ft 0 in. 1200 mm on centers. If local situations allow greatercenter distances between hangers, reduce the load-carryingcapacity of the ceiling suspension system commensurate withthe a
13、ctual center-to-center hanger distances used. If localsituations allow lesser center distances between hangers, in-crease the load-carrying capacity of the ceiling suspensionsystem commensurate with the actual center-to-center hangerdistances used.2.1.4 Each suspension wire shall not hang more than
14、one insix out of plumb unless a countersloping wire or horizontalbracing is provided. See Fig. 1 for allowable counterslopingmethods. Suspension wires should not press against ducts orpipes.2.1.5 Hangers formed from galvanized sheet metal stockshall be suitable for suspending carrying channels or ma
15、inrunners from an existing structure provided that the hangers donot yield, twist, or undergo other objectionable movement.2.1.6 Wire hangers for suspending carrying channels ormain runners from an existing structure shall be prepared froma minimum of No. 12-gage 2.70 mm galvanized, soft-annealed, m
16、ild steel wire.1This practice is under the jurisdiction of ASTM Committee E33 on Environ-mental Acoustics and is the direct responsibility of Subcommittee E33.04 onApplication of Acoustical Materials and Systems.Current edition approved July 15, 2006. Published July 2006. Originallyapproved in 1969.
17、 Last previous edition approved in 2004 as C 636 04.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.2.1.7 In some installations hanger wires are secured tospecial attachment devices that support the carrying channelsor main runners.
18、Such attachment devices shall have certifiedload test data from an independent test laboratory and shall becapable of carrying five times the design load.2.2 Carrying Channels:2.2.1 Install the carrying channels so that they are all levelto within18 in. in 12 ft 3.2 mm in 3600 mm.2.2.2 Perform level
19、ing with the supporting hangers taut toprevent any subsequent downward movement of the carryingchannels when the ceiling loads are imposed.2.2.3 Local kinks or bends shall not be made in hanger wiresas a means of leveling carrying channels.2.2.4 In installations where hanger wires are wrappedaround
20、carrying channels, the wire loops shall be tightlyformed to prevent any vertical movement or rotation of themember within the loop.2.3 Main Runners:2.3.1 Install main runners so that they are all level to within14 in. in 10 ft 6 mm in 3000 mm. Determine evaluation oflevelness from measurements taken
21、 below hanger points. MakeFIG. 1 Allowable Countersloping MethodsC 636/C 636M 062the measurements after completion of the ceiling installationsbut prior to building occupancy.2.3.2 Where main runners are supported directly by hang-ers, perform leveling with the supporting hanger taut to preventany s
22、ubsequent downward movement of the main runnerswhen the ceiling loads are imposed.2.3.3 Local kinks or bends shall not be made in hanger wiresas a means of leveling main runners.2.3.4 In installations where hanger wires are wrappedthrough or around main runners, the wire loops shall be tightlywrappe
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC636C636M2006STANDARDPRACTICEFORINSTALLATIONOFMETALCEILINGSUSPENSIONSYSTEMSFORACOUSTICALTILEANDLAYINPANELSPDF

链接地址:http://www.mydoc123.com/p-507848.html