ASTM C1760-2012 Standard Test Method for Bulk Electrical Conductivity of Hardened Concrete《硬化混凝土整体导电率的标准试验方法》.pdf
《ASTM C1760-2012 Standard Test Method for Bulk Electrical Conductivity of Hardened Concrete《硬化混凝土整体导电率的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1760-2012 Standard Test Method for Bulk Electrical Conductivity of Hardened Concrete《硬化混凝土整体导电率的标准试验方法》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1760 12Standard Test Method forBulk Electrical Conductivity of Hardened Concrete1This standard is issued under the fixed designation C1760; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A
2、number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of the bulkelectrical conductivity of saturated specimens of hardenedconcrete to provide a ra
3、pid indication of the concretesresistance to the penetration of chloride ions by diffusion (SeeNote 1). The results of this test method can be related to theapparent chloride diffusion coefficient that is determined usingTest Method C1556.NOTE 1The term “bulk” is used because the electrical conducti
4、vity isdetermined by measuring the current passing through all the phases of atest specimen (e.g., cement paste, sand, aggregate). This is accomplishedusing electrodes that cover the ends of the specimen. Other test methodsthat measure conductivity may use probes placed on the side surface of thespe
5、cimen.1.2 UnitsThe values stated in SI units are to be regardedas standard. No other units of measurement are included in thisstandard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to est
6、ablish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. (WarningFreshhydraulic cementitious mixtures are caustic and may causechemical burns to exposed skin and tissue upon prolongedexposure.2)2. Referenced Documents2.1 ASTM Standards:
7、3C31/C31M Practice for Making and Curing Concrete TestSpecimens in the FieldC42/C42M Test Method for Obtaining and Testing DrilledCores and Sawed Beams of ConcreteC125 Terminology Relating to Concrete and Concrete Ag-gregatesC192/C192M Practice for Making and Curing ConcreteTest Specimens in the Lab
8、oratoryC511 Specification for Mixing Rooms, Moist Cabinets,Moist Rooms, and Water Storage Tanks Used in theTesting of Hydraulic Cements and ConcretesC1202 Test Method for Electrical Indication of ConcretesAbility to Resist Chloride Ion PenetrationC1543 Test Method for Determining the Penetration ofC
9、hloride Ion into Concrete by PondingC1556 Test Method for Determining the Apparent ChlorideDiffusion Coefficient of Cementitious Mixtures by BulkDiffusion3. Terminology3.1 Definitions:3.1.1 For definitions of terms used in this test method, referto Terminology C125.4. Summary of Test Method4.1 This
10、test method measures the electrical current througha saturated concrete specimen with a potential difference of 60V dc maintained across the ends of the specimen. Testspecimens can be 100 mm diameter by 200 mm long moldedcylinders or nominal 100 diameter cores with length rangingfrom 100 to 200 mm.
11、The apparatus and specimen conditioningprocedures are the same as described in Test Method C1202,except that the side of the specimen does not have to be sealed.The current is measured 1 min after the voltage is first applied.The measured current, the applied voltage, and the specimendimensions are
12、used to calculate the bulk electrical conductiv-ity of the concrete.5. Significance and Use5.1 This test method measures the bulk electrical conduc-tivity of concrete, which has a theoretical relationship to thediffusion coefficient of chloride ion, or other ions, in theconcrete (1, 2).4Experimental
13、 data confirm that there is acorrelation between the apparent chloride diffusion coefficientmeasured by Test Method C1556, or similar method, and thebulk electrical conductivity (3, 4).5.2 A number of factors are known to affect electricalconductivity of concrete: water cementitious materials ratio,
14、1This test method is under the jurisdiction of ASTM Committee C09 onConcrete and Concrete Aggregates and is the direct responsibility of SubcommitteeC09.66 on Concretes Resistance to Fluid Penetration.Current edition approved Jan. 1, 2012. Published February 2012. DOI: 10.1520/C1760-12.2See section
15、on Safety Precautions, Manual of Aggregate and Concrete Testing,Annual Book of ASTM Standards, Vol. 04.02.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standa
16、rds Document Summary page onthe ASTM website.4The boldface numbers in parentheses refer to a list of references at the end ofthis standard.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.the type and amount of supplementary cementiti
17、ous materials,presence of polymeric admixtures, admixtures that containsoluble salts, specimen age, air-void system, aggregate type,degree of consolidation, degree of saturation, and type ofcuring. Different curing methods are used in this test methoddepending on whether the concrete contains supple
18、mentarycementitious materials. Use the same method and duration ofcuring when comparing mixtures.5.3 This test method is suitable for evaluation of concretemixtures for proportioning purposes and for research anddevelopment. Specimens must be sufficiently saturated formeasured electrical conductivit
19、y to provide an indication of theresistance of the concrete to chloride ion penetration. Becausethe electrical conductivity depends upon the degree of satura-tion, specimens are vacuum saturated before testing to ensurea common reference state for comparison purposes. If thespecimen is tested in a p
20、artially saturated, or “as delivered”state, it shall be noted in the test report.5.4 This test can be used to evaluate the electrical conduc-tivity of concretes in structures for applications that mayrequire such information, such as the design of cathodicprotection systems.5.5 The type of specimen
21、and conditioning procedure de-pends on the purpose of the test. For evaluation of concretemixtures, specimens are 100 mm diameter molded cylindersthat are moist cured up to the time of testing. For evaluation ofconcrete samples taken from structures, specimens are 100 mmdiameter cores that are vacuu
22、m saturated before performing thetest.5.6 Age of the test specimen may have significant effects onthe test results, depending on the type of concrete and thecuring procedure. Most concretes, if properly cured, becomeprogressively and significantly less conductive with time.5.7 Measured electrical co
23、nductivity can be used as a basisfor determining the acceptability of a concrete mixture.NOTE 2Because the method and duration of curing of test specimensaffect the test results, the acceptance criteria will need to specify the curingprocedure and test age.6. Interferences6.1 This test method can pr
24、oduce misleading results if one iscomparing concrete mixtures with and without soluble chemi-cal admixtures such calcium nitrite (See Note 3). Calciumnitrite increases greatly the conductivity of the pore solution.For two concrete samples with the same microstructure, theelectrical conductivity of c
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC17602012STANDARDTESTMETHODFORBULKELECTRICALCONDUCTIVITYOFHARDENEDCONCRETE 硬化 混凝土 整体 导电 标准 试验 方法

链接地址:http://www.mydoc123.com/p-465755.html