《ASTM C1041-2010 Standard Practice for In-Situ Measurements of Heat Flux in Industrial Thermal Insulation Using Heat Flux Transducers《使用热通量转换器现场测定工业隔热材料的热通量用标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1041-2010 Standard Practice for In-Situ Measurements of Heat Flux in Industrial Thermal Insulation Using Heat Flux Transducers《使用热通量转换器现场测定工业隔热材料的热通量用标准实施规程》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1041 10Standard Practice forIn-Situ Measurements of Heat Flux in Industrial ThermalInsulation Using Heat Flux Transducers1This standard is issued under the fixed designation C1041; the number immediately following the designation indicates the year oforiginal adoption or, in the case o
2、f revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the in-situ measurement of heat fluxthrough industrial thermal insulation
3、 using a heat flux trans-ducer (HFT).1.2 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.3 This practice estimates the thermal transport propertiesof thermal insulation materials in-situ in field applicationsunder pseudo stea
4、dy-state conditions. It is not intended that thispractice should be used as a substitute for more preciselaboratory procedures such as Test Methods C177, C335,orC518.1.4 This practice is limited by the relatively small area thatcan be covered by an HFT and by the transient effects ofenvironmental co
5、nditions.1.5 Temperature limitations shall be as specified by themanufacturer of the HFT.1.6 While accurate values of heat flux are highly dependentupon proper calibrations under the conditions of use, it isacceptable to use the calibrations provided by the manufacturerof the HFT for comparative wor
6、k between similar materials,aging, or other conditions of use.NOTE 1Further information may be found in the literature (1-6).21.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish ap
7、pro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:3C177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC335 Test
8、Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC518 Test Method for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusE220 Test Method for Calibration of Thermocouples ByComparison TechniquesE230 Specification and Temperature-Electromotive Forc
9、e(EMF) Tables for Standardized Thermocouples3. Terminology3.1 Definitions:3.1.1 heat flux transducer (HFT)a rigid or flexible trans-ducer in a durable housing comprised of a thermopile orequivalent for sensing the temperature drop across a thinthermal resistance layer which gives a voltage output pr
10、opor-tional to the heat flux through the transducer.3.1.1.1 belt HFTa heat flux transducer having a belt-likeconfiguration such that the unit can be wrapped helicallyaround a section of pipe insulation (see Fig. 1).3.1.1.2 spot HFTa small heat flux transducer having around, square, rectangular or ot
11、her configuration for thesensitive area (see Fig. 1).3.1.2 pseudo steady state of HFTthe criterion for pseudosteady-state condition is that the average HFT reading over twoconsecutive 5-min periods does not differ by more than 2 %.Since the time constant of an HFT is typically less than or ofthe ord
12、er of 1 min, using a time interval of 5 min ensures thatthe transient effects in the HFT are averaged.3.2 Symbols:3.2.1 Qheat flow, W (Btu/h).3.2.2 qheat flux, W/m2(Btu/hft2).1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subco
13、mmittee C16.30 on ThermalMeasurement.Current edition approved June 1, 2010. Published September 2010. Originallyapproved in 1985. Last previous edition approved in 2007 as C1041 85 (2007).DOI: 10.1520/C1041-10.2The boldface numbers in parentheses refer to the list of references at the end ofthis sta
14、ndard.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, P
15、O Box C700, West Conshohocken, PA 19428-2959, United States.3.2.3 Coverall conductance of the insulated section,W/m2K (Btu/hft2 F).3.2.4 t0process surface temperature,C (F).3.2.5 t1insulation inside surface temperature. For pur-poses of this standard, t0and t1shall be considered to beidentical.3.2.6
16、 t2insulation outside surface temperature,C (F).3.2.7 Rareal resistance of the insulating section,m2 KWShft2FBtuD (1)3.2.8 l (k)apparent thermal conductivity, W/mK(Btuinhft2F).3.2.9 Dthickness of test section, m (in.).3.2.10 r2outer radius of pipe insulation, m (in.).3.2.11 r1inner radius of pipe in
17、sulation, m (in.).3.2.12 r0outer radius of pipe, m (in.).3.2.13 VHFT output in millivolts or other chosen unit.4. Summary of Practice4.1 This practice is a guide to the proper use of heat fluxtransducers for estimating the thermal transport properties ofthermal insulation in-situ in field applicatio
18、ns under pseudosteady-state conditions.5. Significance and Use5.1 The major contribution of this practice is that it enablesa measurement of the real-time energy loss or gain through achosen surface of an existing process insulation with minimaldisturbance to the heat flux through the insulating bod
19、y.5.2 The primary use of this practice will be for the in-situestimation of thermal transport properties of industrial insula-tion such as used on pipes, tanks, ovens, and boilers, operatingunder normal process conditions.5.3 Errors attributable to heat flow measurements over asmall area or short te
20、rm testing can be misleading and thispractice is intended to minimize such errors.5.4 Insulation processes with large temperature differencesacross the insulation are best suited to HFT measurementsbecause modest changes in ambient conditions have butminimal effects on HFT output.5.5 While it would
21、be ideal for the HFT and attachmentsystem to have zero thermal resistance, this factor is insignifi-cant to the measured result if kept to 5 % or less of theresistance of the insulating section being tested.6. Apparatus6.1 Heat Flux Transducer, as described in 3.1.1.6.2 Voltmeter/RecorderA voltage-m
22、easuring recordinginstrument accurate to within 0.5 % of the lowest HFT outputanticipated during the test. An integrating voltmeter is evenmore appropriate for reading the output of the HFT.6.3 Temperature SensorA thermocouple or other deviceof a type suitable for the temperatures being measured.6.3
23、.1 For measuring the temperature of an insulated surface,such as a pipe under insulation, a 1.5-mm diameter or smaller,flexible ungrounded thermocouple probe 500 mm long isrecommended.6.3.2 For measuring the temperature of surfaces that can beeasily accessed, 24 gauge or smaller, bare bead thermocou
24、plesor equivalent shall be used.6.4 Attachment MaterialsPressure-sensitive adhesivetape, elastic bands, straps, mastic, grease, or other means maybe used to hold the HFT in place on the test surface.6.5 Thermal Contact MaterialsPatching cement, siliconegrease, heat sink grease, silicone sealant, roo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC10412010STANDARDPRACTICEFORINSITUMEASUREMENTSOFHEATFLUXININDUSTRIALTHERMALINSULATIONUSINGHEATFLUXTRANSDUCERS

链接地址:http://www.mydoc123.com/p-463135.html