ASTM B228-2011 Standard Specification for Concentric-Lay-Stranded Copper-Clad Steel Conductors《芯线扭绞的包铜钢导线标准规格》.pdf
《ASTM B228-2011 Standard Specification for Concentric-Lay-Stranded Copper-Clad Steel Conductors《芯线扭绞的包铜钢导线标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM B228-2011 Standard Specification for Concentric-Lay-Stranded Copper-Clad Steel Conductors《芯线扭绞的包铜钢导线标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: B228 11Standard Specification forConcentric-Lay-Stranded Copper-Clad Steel Conductors1This standard is issued under the fixed designation B228; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision.
2、 A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers bare concentric-lay-stran
3、dedconductors made from bare round copper-clad steel wires forgeneral use for electrical purposes.1.2 For the purpose of this specification, conductors areclassified as follows: Grade 40 HS, Grade 30 HS, and Grade 30EHS.1.3 The values stated in inch-pound units are to be regardedas standard. The val
4、ues given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to est
5、ablish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 The following documents of the issue in effect on thedate of material purchase form a part of this specification to theextent referenced herein:2.2 ASTM
6、Standards:2B227 Specification for Hard-Drawn Copper-Clad SteelWireB354 Terminology Relating to Uninsulated Metallic Elec-trical Conductors2.3 ANSI Standards:C 42 Definitions of Electrical Terms32.4 National Institute of Standards and Technology:NBS Handbook 100Copper Wire Tables43. Ordering Informat
7、ion3.1 Orders for material under this specification shall includethe following information:3.1.1 Quantity of each size and grade;3.1.2 Conductor size: approximate diameter in fractions ofan inch, or number and AWG size of individual wires (Section7 and Table 1);3.1.3 Grade (see 1.2 and Table 1);3.1.
8、4 Direction of lay of outer layer, if other than left-hand(see 6.3);3.1.5 When physical tests shall be made (see 8.2);3.1.6 Package size (see 13.1);3.1.7 Special package marking, if required (Section 12);3.1.8 Lagging, if required (see 13.2); and3.1.9 Place of inspection (Section 14).3.2 In addition
9、, Supplementary Requirements shall applyonly when specified by the purchaser in the inquiry, contract, orpurchase order for direct procurement by agencies of the U. S.Government (S1, S2, and S3).4. Material for Wires4.1 The purchaser shall specify the grade of wire to be usedin the conductor.4.2 Bef
10、ore stranding, the copper-clad steel wire shall meetall the requirements of Specification B227.4.3 All wires in the conductor shall be of the same grade andquality.5. Joints5.1 Joints or splices may be made in the finished individualcopper-clad steel wires composing concentric-lay-strandedconductors
11、, using more than three wires provided that suchjoints or splices have a protection equivalent to that of the wireitself and that they do not decrease the strength of the finishedstranded conductor below the minimum breaking strength1This specification is under the jurisdiction of ASTM Committee B01
12、 onElectrical Conductors and is the direct responsibility of Subcommittee B01.06 onComposite Conductors.Current edition approved April 1, 2011. Published May 2011. Originallyapproved in 1948. Last previous edition approved in 2004 as B228 04. DOI:10.1520/B0228-11.2For referenced ASTM standards, visi
13、t the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York,
14、 NY 10036, http:/www.ansi.org.4Available from National Institute of Standards and Technology (NIST), 100Bureau Dr., Stop 1070, Gaithersburg, MD 20899-1070, http:/www.nist.gov.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.shown in T
15、able 1. Such joints or splices shall be not closer than50 ft (15 m) to any other joint in the same layer in theconductor (Note 1).NOTE 1Joints or splices in individual copper-clad steel wires in theirfinished size are made by electrical butt welding. Two types of joints areused and are described as
16、follows:(a) Weld-Annealed JointsAfter butt welding, the wire is annealed fora distance of approximately 5 in. (127 mm) on each side of the weld. Theweld is then protected from corrosion with a snug fitting seamless coppersleeve which extends at least38 in. (9.5 mm) on each side of the weld andwhich
17、is thoroughly sealed to the wire with solder. The wall thickness ofthe sleeve is at least 10 % of the radius of the wire.This joint has a tensile strength of approximately 60 000 psi (415 MPa).This is less than the strength of the individual wires, but an allowance ismade for this in the rated stren
18、gth of the conductor as a whole. Thecompleted conductor when containing such joints is required to have thefull rated strength.This type of joint is but slightly larger than the wire itself and isapplicable for 7, 12, and 19-wire stranded conductors.(b) Compression-Weld JointsCompression-weld joints
19、 differ fromweld-annealed joints in that the wire is not annealed after the butt-weldingoperation but is reinforced with a hard-drawn, seamless, silicon-tin bronzesleeve which is applied by means of a hydraulic compressor over the weld.This sleeve is covered with solder so as to completely seal the
20、ends. Thesesleeves have a wall thickness of 25 to 50 % of the radius of the wire,depending on the wire size. Their use is usually limited to 3-wireconductors where the relatively large diameter is not objectionable. Thisjoint develops the full strength of the wire.6. Lay6.1 For 3-wire conductors the
21、 preferred lay is 1612 times theoutside diameter, but the lay shall not be less than 14 times normore than 20 times this diameter.6.2 For 7- and 19-wire conductors the preferred lay is 1312times the diameter of that layer, but the lay shall not be lessthan 10 nor more than 16 times this diameter.6.3
22、 The direction of lay of the outer layer shall be left-handunless the direction of lay is specified otherwise by thepurchaser.6.4 The direction of lay shall be reversed in consecutivelayers.6.5 All wires in the conductor shall lie naturally in their truepositions in the completed conductor. They sha
23、ll tend to remainin position when the conductor is cut at any point and shallpermit restranding by hand after being forcibly unraveled at theend of the conductor.TABLE 1 Construction Requirements and Breaking Strength of Concentric-Lay-Stranded Copper-Clad Steel ConductorsNOTE 1Metric EquivalentsFor
24、 diameter, 1 in. = 25.40 mm (round to four significant figures); for breaking strength, 1 lb = 0.45359 kg (round tofour significant figures).Size DesignationConductor Diameter, in.ARated Breaking Strength, min, lbBInchCAWGDGrade 40 HS Grade 30 HS Grade 30 EHS78 19 No. 5 0.910 48 740 53 910 64 910131
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMB2282011STANDARDSPECIFICATIONFORCONCENTRICLAYSTRANDEDCOPPERCLADSTEELCONDUCTORS 扭绞 包铜钢 导线 标准 规格 PDF

链接地址:http://www.mydoc123.com/p-460677.html