ASHRAE REFRIGERATION SI CH 7-2010 CONTROL OF MOISTURE AND OTHER CONTAMINANTS IN REFRIGERANT SYSTEMS《制冷系统中水分控制和其它污染物》.pdf
《ASHRAE REFRIGERATION SI CH 7-2010 CONTROL OF MOISTURE AND OTHER CONTAMINANTS IN REFRIGERANT SYSTEMS《制冷系统中水分控制和其它污染物》.pdf》由会员分享,可在线阅读,更多相关《ASHRAE REFRIGERATION SI CH 7-2010 CONTROL OF MOISTURE AND OTHER CONTAMINANTS IN REFRIGERANT SYSTEMS《制冷系统中水分控制和其它污染物》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、7.1CHAPTER 7CONTROL OF MOISTURE AND OTHER CONTAMINANTS IN REFRIGERANT SYSTEMSMoisture 7.1Other Contaminants 7.6System Cleanup Procedure After Hermetic Motor Burnout . 7.8Contaminant Control During Retrofit. 7.9Chiller Decontamination. 7.10MOISTUREOISTURE (water) is an important and universal contami
2、nantM in refrigeration systems. The amount of moisture in a refrig-erant system must be kept below an allowable maximum for satis-factory operation, efficiency, and longevity. Moisture must beremoved from components during manufacture, assembly, and ser-vice to minimize the amount of moisture in the
3、 completed system.Any moisture that enters during installation or servicing should beremoved promptly.Sources of MoistureMoisture in a refrigerant system results from Inadequate equipment drying in factories and service operationsIntroduction during installation or service operations in the fieldLea
4、ks, resulting in entrance of moisture-laden airLeakage of water-cooled heat exchangersOxidation of some hydrocarbon lubricants that produce moistureWet lubricant, refrigerant, or desiccantMoisture entering a nonhermetic refrigerant system throughhoses and sealsDrying equipment in the factory is disc
5、ussed in Chapter 5. Properinstallation and service procedures as given in ASHRAE Standard147 minimize the second, third, and fourth sources. Lubricants arediscussed in Chapter 12. If purchased refrigerants and lubricantsmeet specifications and are properly handled, the moisture contentgenerally rema
6、ins satisfactory. See the section on Electrical Insula-tion under Compatibility of Materials in Chapter 6 and the sectionon Motor Burnouts in this chapter.Effects of MoistureExcess moisture in a refrigerating system can cause one or all ofthe following undesirable effects:Ice formation in expansion
7、valves, capillary tubes, or evaporatorsCorrosion of metalsCopper platingChemical damage to motor insulation in hermetic compressors orother system materialsHydrolysis of lubricants and other materialsSludge formationIce or solid hydrate separates from refrigerants if the water con-centration is high
8、 enough and the temperature low enough. Solidhydrate, a complex molecule of refrigerant and water, can form attemperatures higher than those required to separate ice. Liquid waterforms at temperatures above those required to separate ice or solidhydrate. Ice forms during refrigerant evaporation when
9、 the relativesaturation of vapor reaches 100% at temperatures of 0C or below.The separation of water as ice or liquid also is related to the sol-ubility of water in a refrigerant. This solubility varies for differentrefrigerants and with temperature (Table 1). Various investigatorshave obtained diff
10、erent results on water solubility in R-134a andR-123. The data presented here are the best available. The greaterthe solubility of water in a refrigerant, the less the possibility that iceor liquid water will separate in a refrigerating system. The solubilityof water in ammonia, carbon dioxide, and
11、sulfur dioxide is so highthat ice or liquid water separation does not occur.The concentration of water by mass at equilibrium is greater inthe gas phase than in the liquid phase of R-12 (Elsey and Flowers1949). The opposite is true for R-22 and R-502. The ratio of massconcentrations differs for each
12、 refrigerant; it also varies with tem-perature. Table 2 shows the distribution ratios of water in the vaporphase to water in the liquid phase for common refrigerants. It canbe used to calculate the equilibrium water concentration of the liq-uid-phase refrigerant if the gas phase concentration is kno
13、wn, andvice versa.Freezing at expansion valves or capillary tubes can occur whenexcessive moisture is present in a refrigerating system. Formationof ice or hydrate in evaporators can partially insulate the evaporatorand reduce efficiency or cause system failure. Excess moisture cancause corrosion an
14、d enhance copper plating (Walker et al. 1962).Other factors affecting copper plating are discussed in Chapter 6.The preparation of this chapter is assigned to TC 3.3, Refrigerant Contami-nant Control.Table 1 Solubility of Water in Liquid Phase ofCertain Refrigerants, ppm (by mass)Temp., CR-11 R-12 R
15、-13 R-22 R-113 R-114 R-123R-134aR-410A R-50270 470 620 3900 460 480 2500 4100 180060 350 430 3100 340 340 2000 3200 7200 140050 250 290 2500 250 230 1600 2500 4800 110040 180 190 1900 180 158 1300 1900 3100 84030 120 120 1500 120 104 1000 1400 2000 62020 83 72 1100 83 67 740 1010 1200 46010 55 43 35
16、 810 55 42 550 720 700 3300 35 24 20 581 35 25 400 500 400 23010 21 13 10 407 22 14 290 340 220 15020 13 7.0 5 277 13 8 200 230 110 10130 7 3.5 2 183 8 4 135 143 54 6440 4 1.6 1 116 2 88 87 25 3950 2 0.7 71 1 55 51 2360 1 0.3 42 0.4 33 28 1370 0.4 23 0.2 19 15 7Data on R-134a adapted from Thrasher e
17、t al. (1993) and Allied-Signal Corporation.Data on R-123 adapted from Thrasher et al. (1993) and E.I. DuPont de Nemours the color changesat a low enough level to be safe. Manufacturers instructions must befollowed because the color change point is also affected by liquid-line temperature and the ref
18、rigerant used.Moisture MeasurementTechniques for measuring the amount of moisture in a compres-sor, or in an entire system, are discussed in Chapter 8. The followingmethods are used to measure the moisture content of various halo-carbon refrigerants. The moisture content to be measured is gener-ally
19、 in the milligram-per-kilogram range, and the proceduresrequire special laboratory equipment and techniques.The Karl Fischer method is suitable for measuring the moisturecontent of a refrigerant, even if it contains mineral oil. Although dif-ferent firms have slightly different ways of performing th
20、is test andget somewhat varying results, the method remains the commonindustry practice for determining moisture content in refrigerants.The refrigerant sample is bubbled through predried methyl alcoholin a special sealed glass flask; any water present remains with thealcohol. In volumetric titratio
21、n, Karl Fischer reagent is added, andthe solution is immediately titrated to a “dead stop” electrometricend point. The reagent reacts with any moisture present so that theamount of water in the sample can be calculated from a previous cal-ibration of the Karl Fischer reagent. In coulometric titratio
22、n (AHRI Standard 700C), water is titratedwith iodine that is generated electrochemically. The instrument mea-sures the quantity of electric charge used to produce the iodine andtitrate the water and calculates the amount of water present.These titration methods, considered among the most accurate,ar
23、e also suitable for measuring the moisture content of unused lubri-cant or other liquids. Special instruments designed for this particu-lar analysis are available from laboratory supply companies.Haagen-Smit et al. (1970) describe improvements in the equipmentand technique that significantly reduce
24、analysis time.The gravimetric method for measuring moisture content ofrefrigerants is described in ASHRAE Standards 35 and 63.1. It isnot widely used in the industry. In this method, a measuredamount of refrigerant vapor is passed through two tubes in series,each containing phosphorous pentoxide (P2
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEREFRIGERATIONSICH72010CONTROLOFMOISTUREANDOTHERCONTAMINANTSINREFRIGERANTSYSTEMS 制冷系统 水分 控制 其它 污染物

链接地址:http://www.mydoc123.com/p-455979.html