ASHRAE LV-11-C023-2011 In-tube Boiling Heat Transfer of CO2 Lubricant Mixture at Low Temperatures Preliminary Results.pdf
《ASHRAE LV-11-C023-2011 In-tube Boiling Heat Transfer of CO2 Lubricant Mixture at Low Temperatures Preliminary Results.pdf》由会员分享,可在线阅读,更多相关《ASHRAE LV-11-C023-2011 In-tube Boiling Heat Transfer of CO2 Lubricant Mixture at Low Temperatures Preliminary Results.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Pradeep Bansal is a professor in the Department of Mechanical Engineering, The University of Auckland, New Zealand. ORNL In-tube Boiling Heat Transfer of CO2Lubricant Mixture at Low Temperatures: Preliminary Results Pradeep Bansal, PhD Fellow ASHRAE ABSTRACT The use of CO2in cascade refrigeration sy
2、stems is increasing to achieve low temperatures, particularly in food and refrigeration industries, where understanding of the flow boiling heat transfer mechanisms is essential for heat exchanger design. This paper presents preliminary experimental results of the flow boiling heat transfer of CO2 l
3、ubricant mixture at low saturation temperatures varying between -30oC to -40oC, oil concentration varying between 0 4%, along with the effects of refrigerant vapour quality. The addition of low oil quantities to the flow (80%). INTRODUCTION Recently there has been a resurgence of CO2as a useful refr
4、igerant in cascade refrigeration systems1-2in food and refrigeration industry down to -45oC due to the phase out of commonly used refrigerants containing chlorofluorocarbons (CFC) and hydro chlorofluorocarbons (HCFC). CO2 is a natural, environmentally friendly, non-GWP alternative refrigerant. The f
5、irst CO2system was built in the 1860s and its use in refrigeration systems continued until the 1930s. The introduction of CFC based refrigerants around this time led to the phase out of CO2due to its inherent disadvantages of high pressure containment, and capacity and efficiency loss at high temper
6、ature. The recent popularity of CO2in air-conditioning and industrial cascade refrigeration systems, has led to a reinvigorated development of technology3in areas such as CO2 lubricants, CO2 compressors and novel heat exchangers that require better understanding of the heat transfer and flow charact
7、eristics of CO2- lubricant mixtures. LV-11-C023186 ASHRAE Transactions2011. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions, Volume 117, Part 1. For personal use only. Additional reproduction, distribution, or transmi
8、ssion in either print or digital form is not permitted without ASHRAES prior written permission.There is a variety of commercially available CO2lubricants that are commonly used in industrial cascade refrigeration systems. These lubricants range in solubility with CO2from completely immiscible to mi
9、scible. Non-soluble lubricants such as Alklybenzenes (ABs) and Polyalphaolefins (PAOs) are still applicable due to their flow properties at low temperatures. Polyalkylene glycol (PAG) is partially miscible4with CO2. However, PAG is not miscible with CO2at high concentrations, while Polyol Ester (POE
10、) is found to be completely miscible with CO2 by Li and Rajewski5. With the addition of miscible lubricant, the refrigerant-lubricant mixture usually experiences increased density, surface tension, viscosity and heat conductivity. In CO2-oil mixtures, however, the rapid increase in surface tension a
11、nd viscosity at oil concentrations of more than 3% lead to a reduced heat transfer coefficient when compared to a pure CO2fluid as noted by Zhao and Bansal3. The mixture usually has a higher relative viscosity that results in preferential evaporation of pure refrigerant compared to the lubricant3in
12、the evaporators of vapour compression refrigeration systems. Flow boiling heat transfer of pure COhas been studied by several researchers, including Park and Hrnjak6and Zhao and Bansal7-9. Zhao and Bansal8-9noted that the boiling heat transfer coefficient at low temperatures (-300C) increases with v
13、apour quality until dryout when the maximum heat transfer coefficient occurs. Lower surface tension of CO2facilitates the bubble formation, thus resulting in higher nucleate boiling at low vapour quality. The nucleate boiling of COis more active than the conventional refrigerants, and dominates over
14、 most vapour quality during the flow boiling process. However, the heat transfer coefficient for CO2-lubricant mixture is found to reduce with the increase in the percentage of lubricant10. A review study by Zhao and Bansal3found that at small oil concentrations (75%). At low oil concentrations (2-3
15、%) this relation is well defined. At low vapour qualities (80%). This can be attributed to the increase in local oil concentration reducing the effect of saturation temperature through the creation of oil rich sub layer near the heating surface, in addition to difficulties in effective mixing within
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAELV11C0232011INTUBEBOILINGHEATTRANSFEROFCO2LUBRICANTMIXTUREATLOWTEMPERATURESPRELIMINARYRESULTSPDF

链接地址:http://www.mydoc123.com/p-455426.html