ASHRAE HVAC APPLICATIONS IP CH 52-2015 EVAPORATIVE COOLING.pdf
《ASHRAE HVAC APPLICATIONS IP CH 52-2015 EVAPORATIVE COOLING.pdf》由会员分享,可在线阅读,更多相关《ASHRAE HVAC APPLICATIONS IP CH 52-2015 EVAPORATIVE COOLING.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、52.1CHAPTER 52EVAPORATIVE COOLINGGeneral Applications . 52.1Indirect Evaporative Cooling Systems for Comfort Cooling. 52.2Booster Refrigeration. 52.8Residential or Commercial Cooling 52.10Exhaust Required . 52.10Two-Stage Cooling. 52.11Industrial Applications. 52.11Other Applications . 52.14Control
2、Strategy to Optimize Energy Recovery 52.15Air Cleaning and Sound Attenuation . 52.15Economic Factors. 52.17Psychrometrics . 52.17Entering Air Considerations 52.18VAPORATIVE cooling is energy-efficient, environmentallyE friendly, and cost-effective in many applications and all cli-mates. Applications
3、 range from comfort cooling in residential,agricultural, commercial, and institutional buildings, to industrialapplications for spot cooling in mills, foundries, power plants, andother hot environments. Several types of apparatus cool by evaporat-ing water directly in the airstream, including (1) di
4、rect evaporativecoolers, (2) spray-filled and wetted-surface air washers, (3) sprayed-coil units, and (4) humidifiers. Indirect evaporative coolingequipment combines the evaporative cooling effect in a secondaryairstream with a heat exchanger to produce cooling without addingmoisture to the primary
5、airstream.Direct evaporative cooling reduces the dry-bulb temperatureand increases the relative humidity of the air. It is most commonlyapplied to dry climates or to applications requiring high air ex-change rates. Innovative schemes combining evaporative coolingwith other equipment have resulted in
6、 energy-efficient designs.When temperature and/or humidity must be controlled withinnarrow limits, heat and mechanical refrigeration can be combinedwith evaporative cooling in stages. Evaporative cooling equip-ment, including unitary equipment and air washers, is covered inChapter 41 of the 2012 ASH
7、RAE HandbookHVAC Systems andEquipment.1. GENERAL APPLICATIONSCoolingEvaporative cooling is used in almost all climates. The wet-bulbtemperature of the entering airstream limits direct evaporative cool-ing. The wet-bulb temperature of the secondary airstream limitsindirect evaporative cooling.Design
8、wet-bulb temperatures are rarely higher than 78F, mak-ing direct evaporative cooling economical for spot cooling, kitchens,laundries, agricultural, and industrial applications. In regions withlower wet-bulb temperatures, evaporative cooling can be effectivelyused for comfort cooling, although some c
9、limates may requiremechanical refrigeration for part of the year.Indirect applications lower the air wet-bulb temperature and canproduce leaving dry-bulb temperatures that approach the wet-bulbtemperature of the secondary airstream. Using room exhaust as sec-ondary air or incorporating precooled air
10、 in the secondary airstreamcould lower the wet-bulb temperature of the secondary air and furtherenhances the cooling capability of the indirect evaporative cooler.Direct evaporative cooling is an adiabatic exchange of energy. Heatmust be added to evaporate water. The air into which water is evapo-ra
11、ted supplies the heat; thus, the dry-bulb temperature is lowered andthe moisture content increases. The amount of heat removed from theair equals the amount of heat absorbed by the water evaporated as heatof vaporization. If water is recirculated in the direct evaporative cool-ing apparatus, the wat
12、er temperature in the reservoir approaches thewet-bulb temperature of the air entering the process. By definition, noheat is added to, or extracted from, an adiabatic process; the initial andfinal conditions fall on a line of constant wet-bulb temperature, whichnearly coincides with a line of consta
13、nt enthalpy.The maximum reduction in dry-bulb temperature is the differencebetween the entering air dry- and wet-bulb temperatures. If air iscooled to the wet-bulb temperature, it becomes saturated and theprocess would be 100% effective. Effectiveness is the depression ofthe dry-bulb temperature of
14、the air leaving the apparatus divided bythe difference between the dry- and wet-bulb temperatures of theentering air. Theoretically, adiabatic direct evaporative cooling isless than 100% effective, although evaporative coolers are 85 to 95%(or more) effective.When a direct evaporative cooling unit a
15、lone cannot provide de-sired conditions, several alternatives can satisfy application require-ments and still be energy-effective and economical to operate. Therecirculating water supplying the direct evaporative cooling unit canbe increased in volume and chilled by mechanical refrigeration toprovid
16、e lower leaving wet- and dry-bulb temperatures and lower hu-midity. Compared to the cost of using mechanical refrigeration only,this arrangement reduces operating costs by as much as 25 to 40%.Indirect evaporative cooling applied as a first stage, upstream from asecond, direct evaporative stage, red
17、uces both the entering dry- andwet-bulb temperatures before the air enters the direct evaporativecooler. Indirect evaporative cooling may save as much as 60 to 75%or more of the total cost of operating mechanical refrigeration to pro-duce the same cooling effect. Systems may combine indirect evapo-r
18、ative cooling, direct evaporative cooling, heaters, and mechanicalrefrigeration, in any combination.The psychrometric chart in Figure 1 illustrates what happenswhen air is passed through a direct evaporative cooler. In the exam-ple shown, assume an entering condition of 95F db and 75F wb. Theinitial
19、 difference is 95 75 = 20F. If the effectiveness is 80%, thedepression is 0.80 20 = 16F db. The dry-bulb temperature leaving thedirect evaporative cooler is 95 16 = 79F. In the adiabatic evaporativecooler, only part of the water recirculated is assumed to evaporateand the water supply is recirculate
20、d. The recirculated water reachesan equilibrium temperature approximately the same as the wet-bulbtemperature of the entering air.The performance of an indirect evaporative cooler can also beshown on a psychrometric chart (Figure 1). Many manufacturersdefine effectiveness similarly for both direct a
21、nd indirect evapora-tive cooling equipment. With indirect evaporative cooling, the cool-ing process in the primary airstream follows a line of constantmoisture content (constant dew point). Indirect evaporative coolingeffectiveness is the dry-bulb depression in the primary airstreamdivided by the di
22、fference between the entering dry-bulb temperatureof the primary airstream and the entering wet-bulb temperature ofthe secondary air. Depending on heat exchanger design and relativeThe preparation of this chapter is assigned to TC 5.7, Evaporative Cooling.52.2 2015 ASHRAE HandbookHVAC Applicationsqu
23、antities of primary and secondary air, effectiveness ratings maybe as high as 85%.Assuming 60% effectiveness, and assuming both primary andsecondary air enter the apparatus at the outdoor condition of 95F dband 75F wb, the dry-bulb depression is 0.60(95 75) = 12F. Thedry-bulb temperature leaving the
24、 indirect evaporative cooling processis 95 12 = 83F. Because the process cools without adding mois-ture, the wet-bulb temperature is also reduced. Plotting on the psy-chrometric chart shows that the final wet-bulb temperature is 71.5F.Because both wet- and dry-bulb temperatures in the indirect evapo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASHRAEHVACAPPLICATIONSIPCH522015EVAPORATIVECOOLINGPDF

链接地址:http://www.mydoc123.com/p-454948.html