ANSI IEEE C2 ERTA-2016 National Electrical Safety Code.pdf
《ANSI IEEE C2 ERTA-2016 National Electrical Safety Code.pdf》由会员分享,可在线阅读,更多相关《ANSI IEEE C2 ERTA-2016 National Electrical Safety Code.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、Accredited Standards Committee C2-2017 13 September 2016 1 Insert to STDPT20924 Errata to 2017 Edition National Electrical Safety CodeCorrection Sheet Issued 13 September 2016 The following corrections should be made: Foreword Page iii: In the 2017 Edition subsection of the Foreword, change the firs
2、t sentence of the seventh paragraph as follows: Guy insulator Rule 215C2 to Rule 215C8 of the 2012 edition were rewritten and reorganized to make them easier to understand and apply with the voltage transfer rules associated with guy insulators being removed. NESC Main Committee Membership Page viii
3、: In the second column of the NESC Main Committee list, change the header to “Principal.” NESC Subcommittee 1 Page ix: In the first column of the NESC Subcommittee 1 list, change the header to “Principal.” Page ix: At the bottom of the page, change the names of the following organizations: NCTANatio
4、nal Cable . . .”) of Table 234-1(m), change Footnote 14 to Footnote 16. Page 142: In the sixth column of the header row (“Unguarded rigid live parts, over 750 V to 22 kV; . . .”) of the continued Table 234-1(m), change Footnote 14 to Footnote 16. Page 143: In the sixth column of the header row (“Ung
5、uarded rigid live parts, over 750 V to 22 kV; . . .”) of the continued Table 234-1(m), change Footnote 14 to Footnote 16. Page 145: In the fourth column of the header row (“Unguarded rigid live parts, 0 to 750 V; . . .”) of Table 234-1(ft), change Footnote 14 to Footnote 16. Page 146: In the fourth
6、column of the header row (“Unguarded rigid live parts, 0 to 750 V; . . .”) of the continued Table 234-1(ft), change Footnote 14 to Footnote 16. Page 147: In the fourth column of the header row (“Unguarded rigid live parts, 0 to 750 V; . . .”) of the continued Table 234-1(ft), change Footnote 14 to F
7、ootnote 16. Page 156: Change the reference below the Table 234-6(m) caption as follows: Table 234-6Clearance over roof not readily accessible See Rule 234C3d(1). Page 157: Change the reference below the Table 234-6(ft) caption as follows: Table 234-6Clearance over roof not readily accessible See Rul
8、e 234C3d(1). 235. Clearance for wires, conductors, or cables carried on the same supporting structure Page 160: In Rule 235C1, delete “and” as follows: Basic clearance for line wires, conductors, cables, and service drops of same or different circuits Section 24. Grades of construction 242. Grades o
9、f construction for conductors Page 201: In Footnote 3 of the continued Table 242-1, delete “not” as follows: Grade C construction may be used if the supply circuits will be promptly de-energized, both initially and following subsequent breaker operations, in the event of a contact with lower supply
10、conductors or other grounded objects. Accredited Standards Committee C2-2017 13 September 2016 10 Insert to STDPT20924 243. Grades of construction for line supports Page 202: In Rule 243A3, change the reference from Rule 241C3b to Rule 241C4b. Page 202: In Rule 243B3, change the reference from Rule
11、241C3b to Rule 241C4b. Page 202: In Rule 243C3, change the reference from Rule 241C3b to Rule 241C4b. Section 26. Strength requirements 260. General (see also Section 20) Page 226: In Rule 260A2, change the reference from Rule 13A2 to Rule 013A2. Page 226: In Rule 260B1 NOTE 2, change the bibliograp
12、hic reference numbers as follows: PCI Design Handbook: Precast and Prestressed Concrete B51 IEEE Std 751-1991, IEEE Trial-Use Design Guide for Wood Transmission Structures B32 The Aluminum Association, Aluminum Design Manual B52 261. Grades B and C construction Page 234: In Rule 261N, change the bib
13、liographic reference number as follows: IEEE Std 1307-2004 B37 Section 27. Line insulation 279. Guy and span insulators Page 244: In the NOTE of Rule 279A2a, change the reference from Rule 215C7 to Rule 215C4. Accredited Standards Committee C2-2017 13 September 2016 11 Insert to STDPT20924 Part 3. S
14、afety Rules for the Installation and Maintenance of Underground Electric Supply and Communication Lines Section 35. Direct-buried cable and cable in duct not part of a conduit system 355. Additional rules for duct not part of a conduit system Page 270: In Rule 355D, delete “a” from the first sentenc
15、e as follows: The portion of duct installed through an exterior building wall, floor, or roof shall have seals inside the duct and external seals on the outside surface of the duct at the point of entry into the building intended to limit the likelihood of the entrance of gas into the building. Accr
16、edited Standards Committee C2-2017 13 September 2016 12 Insert to STDPT20924 Part 4. Work Rules for the Operation of Electric Supply and Communications Lines and Equipment Section 41. Supply and communications systemsRules for employers 410. General requirements Page 278: In Rule 410A3, third paragr
17、aph, change the bibliographic reference number as follows: Neal, Bingham, and Doughty B45 Page 278: In Rule 410A3 EXCEPTION 4, change the text as follows: Arc-rated equipment is not necessary for the employees head or face when the employee is wearing head protection meeting OSHA 29 CFR 1910.135 B48
18、 if the estimated incident energy is less than 9 cal/cm2for exposures involving single phase arcs in open air less than or 5 cal/cm2for other exposures. Arc-rated equipment is necessary for the protection of the employees head and face and may consist of head protection meeting OSHA 29 CFR 1910.135
19、and a face shield with a minimum arc rating of 8 cal/cm2if the estimated incident-energy exposure is greater than 9 cal/cm2and less than 13 cal/cm2for exposures involving single-phase arcs in open air or greater than 5 cal/cm2and less than 9 cal/cm2for other exposures. For exposures involving single
20、 phase arcs in open air, the arc rating for the employees head and face protection may be 4 cal/cm2less than the estimated incident energy. Page 279: In Rule 410A3 EXCEPTION 5, change the text as follows: For dc systems with voltages from 50 V to 250 V and 8000 A maximum fault current, in lieu of pe
21、rforming an arc hazard analysis, clothing with a minimum effective arc rating of 5 cal/cm2shall be used. Page 279: In Rule 410A3 NOTE 1, change the bibliographic reference number as follows: Doan, “Arc Flash Calculations for Exposures to DC Systems” B24 Page 279: In Rule 410A6 NOTE, change the bibli
22、ographic reference numbers as follows: OSHA 29 CFR 1910.97, Subpart G B47 OSHA 29 CFR 1910.268, Subpart R B49 FCC Bulletin No. 65 B26 IEEE Std C95.1-2005 B44 Pages 280 and 281: In the footnotes to Table 410-1, change the bibliographic reference numbers in Footnotes 6, 9, 11, 12, and 13 as follows: E
23、blen and Short B25 Accredited Standards Committee C2-2017 13 September 2016 13 Insert to STDPT20924 Section 42. General rules for employees 423. Underground line operating procedures Page 291: In Rule 423D2 NOTE and Rule 423D3 NOTE, change the bibliographic reference numbers as follows: IEEE Std 133
24、3-1994 B38 Section 44. Additional rules for supply employees 441. Energized conductors or parts Page 296: In Rule 441A1d NOTE 2, change the bibliographic reference number as follows: OSHA 29 CFR 1910.269 Appendix B B50 Page 296: In NOTE 3 of Rule 441A1d, add the bibliographic reference number after
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIIEEEC2ERTA2016NATIONALELECTRICALSAFETYCODEPDF

链接地址:http://www.mydoc123.com/p-435277.html