ANSI ASTM E1725-2014 Standard Test Methods for Fire Tests of Fire-Resistive Barrier Systems for Electrical System Components.pdf
《ANSI ASTM E1725-2014 Standard Test Methods for Fire Tests of Fire-Resistive Barrier Systems for Electrical System Components.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM E1725-2014 Standard Test Methods for Fire Tests of Fire-Resistive Barrier Systems for Electrical System Components.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1725 141An American National StandardStandard Test Methods forFire Tests of Fire-Resistive Barrier Systems for ElectricalSystem Components1This standard is issued under the fixed designation E1725; the number immediately following the designation indicates the year oforiginal adoption
2、or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1NOTESections were rearranged editorially in December 2016.1. Scope*1.1 These test method
3、s cover fire-test-response.1.2 These fire-test-response test methods provide informa-tion on the temperatures recorded on the electrical systemcomponent within a fire-resistive barrier system during theperiod of exposure.1.3 This standard is used to measure and describe theresponse of materials, pro
4、ducts, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1.4 Potentially important factors and fire characteristics notaddress
5、ed by these test methods include, but are not limited to:1.4.1 The performance of the fire-resistive barrier systemconstructed with components other than those tested.1.4.2 An evaluation of the functionality of the electricalsystem within the fire-resistive barrier system.1.4.3 An evaluation of the
6、ampacity of the electrical systemwithin the fire-resistive barrier system.1.4.4 An evaluation of the smoke, toxic gases, corrosivity,or other products of heating.1.4.5 A measurement of the flame spread characteristicsover the surface of the fire-resistive barrier system.1.4.6 An evaluation of throug
7、h-penetration sealing methods.1.4.7 Combustibility of materials in the fire-resistive barriersystem or of the electrical system components.1.4.8 The need for supports beyond those normally re-quired.1.4.9 Environmental conditions in the area of service.1.5 The values stated in inch-pound units are t
8、o be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of
9、 the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.7 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.2. Referenced
10、Documents2.1 ASTM Standards:2E119 Test Methods for Fire Tests of Building Constructionand MaterialsE1529 Test Methods for Determining Effects of Large Hy-drocarbon Pool Fires on Structural Members and Assem-blies3. Terminology3.1 Definitions:3.1.1 air droplengths of open run conductors or cablessupp
11、orted only at each end.3.1.2 electrical system componentscable trays, conduitsand other raceways, open run cables and conductors, cables,conductors, cabinets, and other components, as defined or usedin the National Electrical Code, and air drops as defined in3.1.1.3.1.3 fire-resistive barrier system
12、a specific construction ofdevices, materials, or coatings installed around, or applied to,the electrical system components.3.1.4 specimena construction consisting of electrical sys-tem components and a fire-resistive barrier system.1These test methods are under the jurisdiction of ASTM Committee E05
13、 on FireStandards and are the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved July 1, 2014. Published August 2014. Originallyapproved in 1995. Last previous edition approved in 2008 as E172508. DOI:10.1520/E1725-14E01.2For referenced ASTM standards, visit the
14、ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr
15、 Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recomme
16、ndations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.13.1.5 test assemblyhorizontal or vertical construction onwhich test specimens are to be mounted together with associ-ated instrumentation.4. Significance and Use4.1 These fire-test-response test methods eval
17、uate, under thespecified test conditions, the ability of a fire-resistive barriersystem to inhibit thermal transmission to the electrical systemcomponent within.4.2 In these procedures, the specimens are subjected to oneor more specific sets of laboratory test conditions. If differenttest conditions
18、 are substituted or the end-use conditions arechanged, it is not always possible by or from these test methodsto predict changes in the fire test response characteristicsmeasured. Therefore, the results are valid only for the fire testexposure conditions described in these procedures.4.3 These test
19、methods provide a measurement of thetransmission of heat to the electrical system components withinthe barrier system.4.4 These test methods provide qualification of a fireresis-tive barrier system as one element of an electrical systemdesigned to maintain continuous operation of critical functionsa
20、nd processes for a specific fire resistance rating.4.4.1 In addition to the temperature data provided by thesetest methods, numerous other factors, such as referenced in 1.4shall be considered in specifying such a system.5. Control of Fire Test5.1 Fire Test Exposure Conditions:5.1.1 Time-Temperature
21、 CurveMaintain the fire environ-ment within the furnace in accordance with the standardtime-temperature curve shown in Test Method E119 or therapid temperature rise curve shown in Test Method E1529.5.2 Furnace Temperatures:5.2.1 The temperature fixed by the curve shall be theaverage temperature obta
22、ined from readings of thermocouplesdistributed within the test furnace. Disperse the thermocouplesas symmetrically as possible within the furnace to measure thetemperature near all exterior surfaces of the specimen. Do notplace the thermocouples at locations where temperature read-ings would be effe
23、cted by drafts within the furnace.5.2.2 Measure and report the temperatures at intervals notexceeding 1 min.5.3 Furnace Thermocouples:5.3.1 Test Method E119:5.3.1.1 Enclose the thermocouples in sealed protectiontubes of such materials and dimensions that the time constantof the protected thermocoupl
24、e assembly lies within the rangefrom 300 to 400 s3. The exposed length of the pyrometer tubeand thermocouple in the furnace chamber shall be not less than12 in. (305 mm).5.3.2 Test Methods E1529:5.3.2.1 Measure the temperature of the gases adjacent to andimpinging on the test specimens using factory
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTME17252014STANDARDTESTMETHODSFORFIRETESTSOFFIRERESISTIVEBARRIERSYSTEMSFORELECTRICALSYSTEMCOMPONENTSPDF

链接地址:http://www.mydoc123.com/p-432561.html