ANSI ASTM D2655-2012 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 0 to 2000 V《额定电压达到2000伏的电线和电缆交联聚乙烯绝缘材料规范》.pdf
《ANSI ASTM D2655-2012 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 0 to 2000 V《额定电压达到2000伏的电线和电缆交联聚乙烯绝缘材料规范》.pdf》由会员分享,可在线阅读,更多相关《ANSI ASTM D2655-2012 Standard Specification for Crosslinked Polyethylene Insulation for Wire and Cable Rated 0 to 2000 V《额定电压达到2000伏的电线和电缆交联聚乙烯绝缘材料规范》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D2655 12Standard Specification forCrosslinked Polyethylene Insulation for Wire and CableRated 0 to 2000 V1This standard is issued under the fixed designation D2655; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers a crosslinked polyethyleneinsulation for electrical wires and cables in conductor siz
3、es 14AWG 2.08 mm2 and larger. The base polymer of thisinsulation consists substantially of polyethylene or a polyeth-ylene copolymer.1.2 This type of insulation is suitable for continuous use onpower cables in wet and dry locations, for voltage ratings notexceeding 2000 V and at conductor temperatur
4、es not exceeding90C for normal operation. For copper conductors, the insula-tion can be applied over the uncoated metal.1.3 Materials covered by this specification are not sunlightand weather resistant unless they are carbon black pigmentedor contain an additive system designed for this protection.1
5、.4 In many instances the insulation cannot be tested unlessit has been formed around a conductor. Therefore, tests aredone on insulated wire in this standard solely to determine therelevant property of the insulation and not to test the conductoror completed cable.1.5 Whenever two sets of values are
6、 presented, in differentunits, the values in the first set are the standard, while those inparentheses are for information only.2. Referenced Documents2.1 ASTM Standards:2D470 Test Methods for Crosslinked Insulations and Jacketsfor Wire and CableD1248 Specification for Polyethylene Plastics Extrusio
7、nMaterials for Wire and CableD1711 Terminology Relating to Electrical InsulationD2765 Test Methods for Determination of Gel Content andSwell Ratio of Crosslinked Ethylene Plastics2.2 ICEA Standard:ICEA T-28-562 Test Method for Measurement of Hot Creepof Polymeric Insulations33. Terminology3.1 Defini
8、tions:3.1.1 For definitions of terms used in this specification referto Terminology D1711.3.2 Definitions of Terms Specific to This Standard:3.2.1 aging (act of), nexposure of materials to air at121C for 168 h.4. Physical Properties4.1 The requirements for the insulation are listed in Table 1.5. Ele
9、ctrical Requirements5.1 Order of TestingPerform the ac voltage, insulationresistance, and dc voltage tests in that order when any of thesetests are required. The sequence for other testing is notspecified.5.2 AC Voltage TestSubject wires and cables to an ac testvoltage for a period of 5 min. Unless
10、otherwise specified, omitthis test if the dc voltage test described in 5.4 is to beperformed. Test at a voltage of 100 V/mil 4 kV/mm based onthe specified nominal thickness of insulation for the ratedcircuit voltage, phase to phase. Conduct the tests in accordancewith Test Methods D470.5.3 Insulatio
11、n ResistanceThe insulated conductor shallhave an insulation resistance equal to or greater than thatcorresponding to a constant of 10 000 at 60F 15.6C. Whenthe temperature of the water in which the insulation is testeddiffers from 60F, apply a correction factor. Table 2 of TestMethods D470 contains
12、the correction factors. Each insulationmanufacturer can furnish the 1F coefficient for the insulationmaterial by using the procedure given in Test Methods D470.1This specification is under the jurisdiction of ASTM Committee D09 onElectrical and Electronic Insulating Materials and is the direct respo
13、nsibility ofSubcommittee D09.07 on Electrical Insulating Materials.Current edition approved Jan. 1, 2012. Published February 2012. Originallyapproved in 1967. Last previous edition approved in 2006 as D2655 00 (2006).DOI: 10.1520/D2655-12.2For referenced ASTM standards, visit the ASTM website, www.a
14、stm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Insulated Cable Engineers Association, P. O. Box 440, SouthYarmouth, MA 02664 or Global Engineering Docume
15、nts, 15 Inverness Way East,Englewood, CO 80112.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1Multiply the measured value by the correction factor to obtainthe insulation-resistance value corrected to 60F.5.3.1 Where a nonconducting
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
2000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIASTMD26552012STANDARDSPECIFICATIONFORCROSSLINKEDPOLYETHYLENEINSULATIONFORWIREANDCABLERATED0TO2000V

链接地址:http://www.mydoc123.com/p-432291.html