ANSI American Society of Sanitary Engineering 1022-2017 Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment.pdf
《ANSI American Society of Sanitary Engineering 1022-2017 Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment.pdf》由会员分享,可在线阅读,更多相关《ANSI American Society of Sanitary Engineering 1022-2017 Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment.pdf(24页珍藏版)》请在麦多课文档分享上搜索。
1、ASSE Standard #1022-2017 ASSE Board Approved: June 2017ANSI Approved: June 2017ICS Codes: 13 060 2055 230An American National StandardPerformance Requirements for Backflow Preventer for Beverage Dispensing EquipmentASSE InternationalBackflow Preventer for Beverage Dispensing Equipment iASSE 1022-201
2、7General InformationNeither this standard, nor any portion thereof, may be reproduced without the written consent of ASSE International.No product may be said to be ASSE listed unless the manufacturer has applied to ASSE International, has had its product tested according to the applicable standards
3、, and when the product has passed the test, displays the ASSE Seal on the product.Instructions for receiving the authorization to display the seal are available from the ASSE International office. Organizations wishing to adopt or list any ASSE International standard should print the ASSE Internatio
4、nal standard number on the cover page first and in equal or larger type to that of the adopting or listing organization.ASSE InternationalMokena, IllinoisCopyright 2017, 2003, 1996All rights reserved.ii Backflow Preventer for Beverage Dispensing EquipmentASSE 1022-2017Backflow Preventer for Beverage
5、 Dispensing Equipment iiiASSE 1022-2017ForewordThis foreword shall not be considered a part of the standard; however, it is offered to provide background information.The need for this standard arose from numerous requests by regulatory authorities, manufacturers of backflow prevention devices, consu
6、mers, and users of beverage dispensing equipment.Concerns have been raised that a dual check valve alone will not show any visible indication of failure. ASSE Standard #1022, Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment, includes two check valves and an atmospher
7、ic vent. If there is failure of the downstream check and the backpressure exceeds the supply pressure, the vent will discharge, giving a visual indication of the check valves failure.Although many of the material specifications are detailed within Section IV of this standard, it is the responsibilit
8、y of the manufacturer and the installer to comply with the relevant jurisdictional requirements.This standard was promulgated in accordance with procedures developed by the American National Standards Institute (ANSI).Compliance with this standard does not imply acceptance by any code group unless t
9、he standard has been adopted by the code.iv Backflow Preventer for Beverage Dispensing EquipmentASSE 1022-2017Edward J. Lyczko, ChairpersonCleveland Clinic Retiree Cleveland, OHWilliam Briggs, Jr.MGJ AssociatesNew York, NYTerry BurgerNSF InternationalYpsilanti, MIWilliam ChapinProfessional Code Cons
10、ulting, LLCCullman, ALMark FishZurn Industries, LLCCary, NCRon GeorgePlumb-Tech Design & Consulting Services, LLCNewport, MIDaniel GleibermanSloan Los Angeles, CAJohn F. Higdon, P.E.Apollo Valves / Conbraco Industries, Inc.Matthews, NCGary HowardIllinois Plumbing Inspector RetireeLaGrange, ILConrad
11、L. Jahrling (non-voting)ASSE InternationalChicago, IL2016 Product Standards Committee Chuck LottPrecision Plumbing ProductsPortland, ORPeter MarzecUnited Association of Plumbers and PipefittersPearl River, NYThomas PitcherelloState of New JerseyBordentown, NJDaniel RademacherPlumbing Code and Design
12、 ConsultingButte, MTShabbir RawalpindiwalaKohler CompanyKohler, WIBilly SmithAmerican Society of Plumbing Engineers (ASPE)Montgomery, ALTsan-Liang Su, PhDStevens Institute of TechnologyHoboken, NJBackflow Preventer for Beverage Dispensing Equipment vASSE 1022-2017Dale Tripp, Chairperson Anderson Bra
13、ss Co.Hartsville, SCJohn Higdon, PEApollo Valves / Conbraco Industries, Inc.Pageland, SCConrad L. Jahrling (non-voting)ASSE InternationalChicago, IL 1022 Working GroupDavid OrtonNSF InternationalAnn Arbor, MIS. Scott ParkhurstSGS North America Inc.Tulsa, OKGeorge ThompsonThe Coca-Cola Co.Atlanta, GA
14、vi Backflow Preventer for Beverage Dispensing EquipmentASSE 1022-2017Table of ContentsSection I . 11.0 General . 11.1 Application 11.2 Scope . 1Table 1 11.3 Reference Standards . 2Section II 32.0 Test Specimens 32.1 Samples Submitted for Test . 32.2 Samples Tested 32.3 Drawings 32.4 Rejection 3Secti
15、on III. 43.0 Performance Requirements and Compliance Testing 43.1 Hydrostatic Pressure 4Figure 1 43.2 Hydrostatic Test of Check Valves . 4Figure 2 53.3 Atmospheric Port Leakage . 53.4 Water Flow Test 6Figure 3 63.5 Deterioration at Extremes of Manufacturers Rated Temperature and Pressure Ranges 63.6
16、 Check Valve Sealing Pressure . 73.7 Endurance and Cycle Testing . 7Figure 4 83.8 Atmospheric Port-Opening Pressure 8Figure 5 93.9 Check Valve Leakage . 9Section IV 104.0 Detailed Requirements . 104.1 Materials and Toxicity . 104.2 Design and Construction 104.3 Markings 114.4 Installation Instructio
17、ns 11Section V . 125.0 Definitions. 12Backflow Preventer for Beverage Dispensing Equipment 1ASSE 1022-2017Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment Section I1.0 General1.1 ApplicationBackflow Preventer for Beverage Dispensing Equipment (herein referred to as “
18、device”) is engineered for installation in carbonated post-mix dispensing systems. This standard covers a backflow prevention device designed to protect the potable water supply serving beverage dispensing equipment. These devices are intended for use under continuous or intermittent pressure condit
19、ions.1.2 Scope1.2.1 DescriptionThese devices shall consist of two independently acting check valves biased to a normally closed position. An atmospheric port shall be located between the check valves and shall be biased to a normally open position. The port shall vent liquids, gases, or both, under
20、backflow conditions.1.2.2 Minimum FlowThe device shall meet the minimum flow capacity as described in Table 1.Table 1Device Type Minimum Flow Rate at a Maximum Pressure Drop of 15.0 psi (103.4 kPa)GPM L/sA 1.00 0.06B 2.00 0.13C 3.00 0.19Type indicates the flow capacity of the device and not the conn
21、ection size of the device.1.2.3 Inlet and Outlet ConnectionsInlet and outlet connections shall include 1/4” (8 DN), 3/8” (10 DN), and 1/2” (15 DN) nominal pipe size. 1.2.4 Pressure RangeThese devices shall function properly over the pressure range of 10.0 psi to 200.0 psi (68.9 kPa to 1379 kPa).1.2.
22、5 Temperature RangeThese devices shall function properly over the temperature range of 40.0 F to 130.0 F (4.4 C to 54.44 C).2 Backflow Preventer for Beverage Dispensing EquipmentASSE 1022-20171.3 Reference StandardsASME B1.20.1-2013, Pipe Threads, General Purpose (Inch) ASME B1.20.3-1976 (R2013), Dr
23、yseal Pipe Threads (Inch) ASTM D2240-15, Standard Test Method for Rubber Property Durometer HardnessCFR Title 21, Section 177, Food and Drugs: Indirect Food Additives: PolymersISA 75.02.01-2008 (IEC 60534-2-3 Mod), Control Valve Capacity Test Procedures NSF Standard 18-2012, Manual Food and Beverage
24、 Dispensing EquipmentNSF Standard 61-2015, Drinking Water System Components Health EffectsASME American Society of Mechanical Engineering, Three Park Avenue, New York, NY 10016, www.asme.orgASTM American Society for Testing Materials, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959, www.astm
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ANSIAMERICANSOCIETYOFSANITARYENGINEERING10222017PERFORMANCEREQUIREMENTSFORBACKFLOWPREVENTERFORBEVERAGEDISPENSINGEQUIPMENTPDF

链接地址:http://www.mydoc123.com/p-430851.html