ARI 460-2005 PERFORMANCE RATING OF REMOTE MECHANICAL- DRAFT AIR-COOLED REFRIGERANT CONDENSERS《远程机械通风空气冷却冷凝器作业评定》.pdf
《ARI 460-2005 PERFORMANCE RATING OF REMOTE MECHANICAL- DRAFT AIR-COOLED REFRIGERANT CONDENSERS《远程机械通风空气冷却冷凝器作业评定》.pdf》由会员分享,可在线阅读,更多相关《ARI 460-2005 PERFORMANCE RATING OF REMOTE MECHANICAL- DRAFT AIR-COOLED REFRIGERANT CONDENSERS《远程机械通风空气冷却冷凝器作业评定》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、 4100 N. FAIRFAX DRIVE, SUITE 200 ARLINGTON, VIRGINIA 22203 2005 STANDARD for PERFORMANCE RATING OF REMOTE MECHANICAL- DRAFT AIR-COOLED REFRIGERANT CONDENSERS Standard 460 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or n
2、etworking permitted without license from IHS-,-,-IMPORTANT SAFETY DISCLAIMER ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly
3、 recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing stat
4、e-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard 460-2000. Price $10.00 (M) $20.00 (NM) Copyright 2005, by Air-Conditioning and
5、Refrigeration Institute Printed in U.S.A. Registered United States Patent and Trademark Office Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-TABLE OF CONTENTS SECTION PA
6、GE Section 1. Purpose1 Section 2. Scope.1 Section 3. Definitions 1 Section 4. Test Requirements 2 Section 5. Rating Requirements.3 Section 6. Minimum Data Requirements for Published Ratings .4 Section 7. Marking and Nameplate Data .4 Section 8. Conformance Conditions 5 TABLES Table 1. Standard Ratin
7、g Conditions 3 APPENDICES Appendix A. References - Normative 6 Appendix B. References - Informative.6 Copyright Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-Copyright Air-Conditi
8、oning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 460-2005 1PERFORMANCE RATING OF REMOTE MECHANICAL-DRAFT AIR-COOLED REFRIGERANT CONDENSERS Section 1. Purpose 1.1 Purpose. The purpo
9、se of this standard is to establish for Remote Mechanical-Draft Air-Cooled Condensers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; marking and nameplate data; and conformance conditions. 1.1.1 Intent. This standard is intended for the guidanc
10、e of the industry, including: manufacturers, designers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to Remote Mechanical-Draft Air-Cooled Refrigerant Condense
11、rs as defined in Section 3 for use with or without external air resistance. 2.2 Exclusions. 2.2.1 This standard does not apply to Air-Cooled Condensers designed primarily for installation within the machinery compartment of a self-contained product or in a factory-assembled condensing unit. 2.2.2 Th
12、is standard does not apply to remote mechanical-draft evaporatively-cooled refrigerant condensers as covered by ARI Standard 490. Section 3. Definitions 3.1 Definitions. All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Venti
13、lation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.2 Bubble Point. Refrigerant liquid saturation temperature at a specified pressure. 3.3 Dew Point. Refrigerant vapor saturation temperature at a specified pressure. 3.4 Entering Air Dry-Bulb Temperature. The averag
14、e dry-bulb temperature of the ambient air entering the condenser assembly, F C. 3.5 Entering Air Wet-Bulb Temperature. The average wet-bulb temperature of the air entering the condenser assembly, F C. 3.6 Net Refrigeration Effect. The rate of total heat absorption by the refrigerant, at stated evapo
15、rator conditions, of the complete refrigeration system. This effect is equal to the product of the refrigerant mass flow rate through the system and the enthalpy difference between the refrigerant vapor leaving the evaporator and the refrigerant liquid entering the liquid control device of the evapo
16、rator, Btu/h W. 3.7 Published Rating. A statement of the assigned values of those performance characteristics, under stated Rating Conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same man
17、ufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature, including computer software and computer-generated reports, controlled by the manufacturer, at stated Rating Conditions. Copy
18、right Air-Conditioning and Refrigeration Institute Provided by IHS under license with ARI Not for ResaleNo reproduction or networking permitted without license from IHS-,-,-ARI STANDARD 460-2005 _ _ 2 3.7.1 Application Rating. A rating based on tests performed at application rating conditions (other
19、 than Standard Rating Conditions). 3.7.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.8 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.8.1 Standard
20、 Rating Conditions. Rating Conditions used as the basis of comparison for performance characteristics. 3.9 Remote Mechanical-Draft Air-Cooled Refrigerant Condenser (Air-Cooled Condenser). A factory-made encased unit which is intended for connection in the field by means of refrigerant piping, and wh
21、ich includes a means for forced-air circulation and elements by which heat is transferred from refrigerant to air. The purpose of this unit is to condense refrigerant vapor by rejecting heat to the air. 3.10 Saturated Condensing Temperature (Condensing Temperature). For single component and azeotrop
22、e refrigerants, the saturation temperature corresponding to the refrigerant pressure at the condenser entrance. For zeotropic refrigerants, the arithmetic average of the Dew Point and Bubble Point temperatures corresponding to the refrigerant pressure at the condenser entrance.3.11 “Shall“ or “Shoul
23、d“. “Shall“ or “Should“ shall be interpreted as follows: 3.11.1 Shall. Where “shall“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.11.2 Should. “Should“ is used to indicate provisions which are not mandatory but which are
24、desirable as good practice. 3.12 Standard Air. Air weighing 0.075 lb/ft31.2 kg/m3, which approximates dry air at 70F 21C and at a barometric pressure of 29.92 in Hg 101.3 kPa. 3.13 Subcooling. The difference between the saturation temperature corresponding to the liquid pressure at the coil outlet a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI4602005PERFORMANCERATINGOFREMOTEMECHANICALDRAFTAIRCOOLEDREFRIGERANTCONDENSERS 远程 机械 通风 空气冷却 冷凝器 作业

链接地址:http://www.mydoc123.com/p-429444.html