ARI 325-1998 Ground Water-Source Heat Pumps《地下水资源蒸汽泵》.pdf
《ARI 325-1998 Ground Water-Source Heat Pumps《地下水资源蒸汽泵》.pdf》由会员分享,可在线阅读,更多相关《ARI 325-1998 Ground Water-Source Heat Pumps《地下水资源蒸汽泵》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、 STD-AR1 325-ENGL 3798 0352320 UOLLL7b 452 1998 STANDARD for AIR-CONDITIONING requirements for testing and rating performance requirements; marking and nameplate data; and conformance conditions. 1.1.1 This standard is intended for the guidance of the industry, including manufacturers, engineers, in
2、stallers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to factory-made residential, commercial and industrial ground water-source heat pumps, as defined in Section 3. 2.1.
3、1 Energy Source. This standard applies only to electrically-driven, mechanical compression type systems. 2.1.2 Alternative Applications. Equipment designed for rating under this standard may not be suitable for alternative applications covered in related ARI Standards 320 and 330. 2.2 Exclusions. Th
4、is standard does not apply to individual assemblies for separate use. Section 3. Definitions 3.1 Definitions. Ali terms in this document will follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air- conditioning and Repigeration unless other
5、wise defined this section. 3.2 Coefficient of Performance (COP). A ratio of the heating capacity in watts w, excluding supplementary resistance heat, to the power input in watts Wl at any given set of rating conditions expressed in wattslwatt Wnv. (The international community uses the term EER as eq
6、uivalent to cooling COP.) 3.2.1 Standard Coefficient of Performance. A ratio of the capacity to power input obtained at Standard Rating Heating Conditions. 3.3 Enew EBcienCy Ratio (EER). A ratio of the cooling capacity in Bairn to the power input in watts w at any given set of rating conditions, exp
7、ressed in Btu/W*h WN. 3.3.1 Standard Energy Efficiency Ratio. A ratio of the capacity to power input values obtained at Standard Rating Conditions. 3.4 Ground Water-Source Heat Pump. A ground water- source heat pump typically uses water pumped from a well, lake or stream as a heat sourceheat sink. T
8、he temperature of the water is related to climatic conditions and usually rangeshm45“Fto 75F 7.2“C to 23.9“CI for deep wells. Rated efficiencies include an allowance for power to pump the water. A pund water-source heat pump consists of one or more faory-made assemblies which normally include an ind
9、oor conditioning coil with air moving means, compressor(s) and refrigerant-to-water heat exchanger(s), including means to provide a heating function and may include a cooling function. When such equipment is provided in more than one assembly, the separated assemblies shall be designed to be used to
10、gether, and the requirements of rating outlined in the standard are based upon the use of matched assemblies. 3.4.1 Functions. Ground water-source heat pumps shall provide the function of heating with controlled temperature, and may include the functions of water heating, air-cooling, air-circulatin
11、g, air-cleaning, dehumiwng or humiwng. 3.5 Published Rating. A statement of the assigned values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) p
12、roduced by the same manufacturer. As used herein, the term “published rating“ includes the raing of all performance characteristics shown on the heat pump or published in specifications, advertising or other literature controlled by the manufacturer, at stated rating conditions. 3.5.1 Standard Ratin
13、g. A rating based on tests performed at Standard Rating Conditions. 3.5.2 Application Rating. A rating based on tests performed at application rating conditions (other than Standard Rating Conditions). 1 COPYRIGHT Air-Conditioning and Refrigeration InstituteLicensed by Information Handling ServicesA
14、R1 STANDARD 325-1 998 3.6 Rating Conditions. Any set of operating conditions under which a single level of performance results, and which causes only that level of performance to occur. 3.6.1 Standard Rating Condtiork. Rating conditions used as the basis of comparison of performance characteristics.
15、 3.7 “Shall,“ “should, Recommended“ or 7t Is Recommended “Shall,“ should, “recommended“ or “it is recommended“ shall be interpreted as follows: 3.7.1 Shall. Where “shail“ or “shall not“ is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.7.2 S
16、hould, Recommended or It Is Recommended. “Should,“ “recommended“ or “it is recommended“ is used to indicate provisions which are not mandatory but which are desirable as good practice. Section 4. Classification 4.1 Classijkation. Normaily, ground water-source heat pumps wihin the scope of this stand
17、ard may be classified as shown in Table 1. Section 5. Testing and Rating Requirements 5.1 Standard Rating. Siandard ratings shall be established at the Standard Rating Conditions specified in 5.1.4. All standardratings shall be verifed by tests conducted in accordance with ASHRAE Standard 37, and wi
18、th the test methods and procedures as describe in this standard exceptthat the total cooling and heating capacity shall be the average of the Air-Enthalpy Method and the Water Coil Method. Standard Ratings relating to cooling or heating capacities shall be net values, including the effects of circul
19、ating-fan heat, but not including supplemenmy heat. Power input shall be the total power input to the compressor(s), fm(s), pump penalty (see 5.1.3), plus controls and other items included as part of the model number). Standard Ratings of units which do not have indoor air- circulating fans fimished
20、 as part of the model, i.e., split system with indoor coil alone (see Table i), shall be established by subtracting from the total cooling capacity 1250 Btu/h per 1000 scfm 0.775 watts per m3/s, and by adding the same amount to the heating capacity. Total power input for both heating and cooling sha
21、ll be increased by 365 wattdl000 scfm 0.775 watts per m3k of indoor air handled. 5.1.1 Values of Standard Capacity Ratings. These raings shali be expressed only in terms of Btu/h WJ in multiples of 100 Btu/h 10 w. 5.1.2 Values of Pressure Drop Ratings. Water flow rate) and pressure drop(s) shall be
22、determined at each Standard Rating Condition specified in 5.1.4. Water pressure drop through the unit for the rated standard flow rate(s) shall be expressed in multiples of 0.5 psi 3.5 Wal. Single Package + A sutKx of “O“ following any of the above classifications indicates equipment not intended fo
23、r use with * Denotes cooling mode function. field-instailed duct systems (see 5.1.4.5). 2 COPYRIGHT Air-Conditioning and Refrigeration InstituteLicensed by Information Handling ServicesSTD-AR1 325-ENGL 1998 33521217 0011LL6L ALT H AR1 STANDARD 325-1998 Water flow rate) shall be expressed in gpm PSI
24、in multiples of 0.1 gpm to 10 gpm and 0.5 gpm for over 10 gpm Standard coefficients of performance for hating, whenever published, shali be expressed in multiples of the nearest O. 1. in caiculating EERs or COPS, a penaity for the water pump effect sha be added to the measured power input and determ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ARI3251998GROUNDWATERSOURCEHEATPUMPS 地下 水资源 蒸汽 PDF

链接地址:http://www.mydoc123.com/p-429434.html