AHRI 1251 SI-2014 Performance Rating of Walk-in Coolers and Freezers.pdf
《AHRI 1251 SI-2014 Performance Rating of Walk-in Coolers and Freezers.pdf》由会员分享,可在线阅读,更多相关《AHRI 1251 SI-2014 Performance Rating of Walk-in Coolers and Freezers.pdf(66页珍藏版)》请在麦多课文档分享上搜索。
1、 2014 Standard for Performance Rating of Walk-in Coolers and Freezers AHRI Standard 1251 (SI) Price $10.00 (Members) $20.00 (Non-Members) Copyright 2014, by Air-Conditioning, Heating, and Refrigeration Institute Printed in U. S.A. Registered United States Patent and Trademark Office IMPORTANT SAFETY
2、 DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled,
3、installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not cer
4、tify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes AHRI Standard 1251 (SI)-2009 For I-P ratings, see ANSI/AHRI Standard 1250 (I-P)-2014. i TABLE OF CONTENTS PAGE Section 1 Purpose 1 Section 2 Scope . 1 Sec
5、tion 3 Definitions . 1 Section 4 Test Requirements . 3 Section 5 Rating Requirements . 5 Section 6 Calculation for Walk-in Box Load 19 Section 7 Calculation for Annual Walk-in Energy Factor . 20 Section 8 Symbols and Subscripts 42 Section 9 Minimum Data Requirements for Published Ratings 45 Section
6、10 Marking and Nameplate Data . 45 Section 11. Conformance Conditions. 45 TABLES Table 1 Instrumentation Accuracy . 3 Table 2 Test Operating and Test Condition Tolerances for Steady-state Test . 4 Table 3 Fixed Capacity Matched Refrigerator System, Condensing Unit Located Indoor 5 Table 4 Fixed Capa
7、city Matched Refrigerator System, Condensing Unit Located Outdoor . 5 Table 5 Two Capacity Matched Refrigerator System, Condensing Unit Located Outdoor . 6 Table 6 Variable Capacity Matched Refrigerator System, Condensing Unit Located Outdoor . 8 Table 7 Fixed Capacity Matched Freezer System, Conden
8、sing Unit Located Indoor 10 Table 8 Fixed Capacity Matched Freezer System, Condensing Unit Located Outdoor . 10 Table 9 Two Capacity Matched Freezer System, Condensing Unit Located Outdoor . 11 Table 10 Variable Capacity Matched Freezer System, Condensing Unit Located Outdoor . 14 Table 11 Fixed Cap
9、acity Refrigerator Condensing Unit, Condensing Unit Located Indoor 16 Table 12 Fixed Capacity Refrigerator Condensing Unit, Condensing Unit Located Outdoor 16 Table 13 Fixed Capacity Freezer Condensing Unit, Condensing Unit Located Indoor 17 Table 14 Fixed Capacity Freezer Condensing Unit, Condensin
10、g Unit Located Outdoor 17 ii TABLES (continued) PAGE Table 15 Refrigerator Unit Cooler . 18 Table 16 Freezer Unit Cooler . 18 Table 17 EER for Remote Commercial Refrigerated Display Merchandisers and Storage Cabinets 31 Table 18 Unit Cooler Nominal Values for Condensing Unit Energy Calculations 34 F
11、IGURES Figure 1 Schematic of the Operation for Units with Single Capacity Compressor . 21 Figure 2 Schematic of the Various Modes of Operation for Units with Two Capacity or Two-Stage Compressors 23 Figure 3 Schematic of the Various Modes of Operation for units with Variable Speed Compressors 26 APP
12、ENDICES Appendix A. References Normative 46 Appendix B. References Informative 48 Appendix C. Methods of Testing Walk-in Cooler and Freezer Systems Normative . 49 Appendix D. Weather Data in Region IV Normative 62 TABLES FOR APPENDICES Table C1 Test Readings 51 Table C2 Data to be Recorded 53 Table
13、C3 Unit Cooler Nominal Values for Condensing Unit Energy Calculations 61 Table D1 Bin Temperatures and Corresponding Bin Hours for AWEF Calculation 62 FIGURES FOR APPENDICES Figure C1 Method 1: DX-Dual Instrumentation 54 Figure C2 Method 2: DX- Calibrated Box 55 AHRI STANDARD 1251 (SI)-2014 1 PERFOR
14、MANCE RATING OF WALK IN COOLERS AND FREEZERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for walk-in coolers and freezers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and namep
15、late data and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, designers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope
16、 2.1 Scope. This standard applies to mechanical refrigeration equipment consisting of an integrated single package refrigeration unit, or separate Unit Cooler and condensing unit sections, where the condensing section can be located either outdoor or indoor. Controls may be integral, or can be provi
17、ded by a separate party as long as performance is tested and certified with the listed mechanical equipment accordingly. 2.2 Exclusions. This standard does not apply to: 2.2.1 Enclosures used for telecommunications switch gear or other equipment requiring cooling 2.2.2 Enclosures designed for medica
18、l, scientific or research purposes 2.2.3 Performance testing and efficiency characterization of large parallel rack refrigeration systems (condensing unit) Section 3. Definitions All terms in this document will follow the standard industry definitions in the ASHRAE Wikipedia website (https:/www.ashr
19、ae.org/resources-publications/free-resources/ashrae-terminology) unless otherwise defined in this section. 3.1 Annual Walk-in Energy Factor (AWEF). A ratio of the total heat, not including the heat generated by the operation of refrigeration systems, removed, in watt-hours, from a walk-in box during
20、 one year period of usage for refrigeration to the total energy input of refrigeration systems, in watt-hours, during the same period. 3.2 Coefficient of Performance (COP). A ratio of the Net Refrigeration Capacity in W to the power input values in W at any given set of Rating Conditions expressed i
21、n W/W. 3.3 Forced-circulation Free-Delivery Unit Coolers (Unit Coolers). A factory-made assembly, including means for forced air circulation and elements by which heat is transferred from air to refrigerant without any element external to the cooler imposing air resistance. These may also be referre
22、d to as Air Coolers, Cooling Units, Air Units or Evaporators. 3.4 Gross Refrigeration Capacity. The heat absorbed by the refrigerant, W. This is the sum of the Net Refrigeration Capacity and the heat equivalent of the energy required to operate the Unit Cooler. This includes both sensible and latent
23、 cooling. 3.5 Load Factor. A ratio of the Total Walk-in System Heat Load to the steady-state net refrigeration capacity. 3.6 Load Period. A twenty-four hour day. 3.6.1 High Load Period. The period of the day corresponding to frequent door openings, product loading events, and other design Load Facto
24、rs. For the purposes of this standard, this period shall be 8 continuous hours. AHRI STANDARD 1251 (SI)-2014 2 3.6.2 Low Load Period. The period of the day other than the High Load Period. For the purposes of this standard, this period shall be the remaining 16 continuous hours of the total Load Per
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AHRI1251SI2014PERFORMANCERATINGOFWALKINCOOLERSANDFREEZERSPDF

链接地址:http://www.mydoc123.com/p-422491.html