AASHTO M 86M M 86-2017 Standard Specification for Nonreinforced Concrete Sewer Storm Drain and Culvert Pipe.pdf
《AASHTO M 86M M 86-2017 Standard Specification for Nonreinforced Concrete Sewer Storm Drain and Culvert Pipe.pdf》由会员分享,可在线阅读,更多相关《AASHTO M 86M M 86-2017 Standard Specification for Nonreinforced Concrete Sewer Storm Drain and Culvert Pipe.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Standard Specification for Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe AASHTO Designation: M 86M/M 86-171Technical Section: 4a, Rigid Pipe Release: Group 2 (June 2017) ASTM Designation: C14M-15a and C14-15a American Association of State Highway and Transportation Officials 444 North
2、Capitol Street N.W., Suite 249 Washington, D.C. 20001TS-4a M 86M/M 86-1 AASHTO Standard Specification for Nonreinforced Concrete Sewer, Storm Drain, and Culvert Pipe AASHTO Designation: M 86M/M 86-171Technical Section: 4a, Rigid Pipe Release: Group 2 (June 2017) ASTM Designation: C14M-15a and C14-15
3、a 1. SCOPE 1.1. This specification covers nonreinforced concrete pipe intended to be used for the conveyance of sewage, industrial wastes, storm water, and for the construction of culverts. 1.2. This specification is applicable for orders in either SI units (M 86M) or in inch-pound units (M 86). SI
4、units and inch-pound units are not necessarily equivalent. Inch-pound units are shown in brackets in the text for clarity, but they are the applicable values when the material is ordered to M 86. Note 1This specification is a manufacturing and purchasing specification only and does not include requi
5、rements for bedding, backfill, or the relationship between field load conditions and the strength classification of pipe. However, experience has shown that the successful performance of this product depends on the proper selection of the class of pipe, type of bedding and backfill, and care that th
6、e installation conforms to the construction specifications. Owners are cautioned that they must correlate the field requirements with the class of pipe specified and provide for or require inspection at the construction site. 2. REFERENCED DOCUMENTS 2.1. AASHTO Standards: M 6, Fine Aggregate for Hyd
7、raulic Cement Concrete M 80, Coarse Aggregate for Hydraulic Cement Concrete M 85, Portland Cement M 157, Ready-Mixed Concrete M 194M/M 194, Chemical Admixtures for Concrete M 240M/M 240, Blended Hydraulic Cement M 262, Concrete Pipe and Related Products M 295, Coal Fly Ash and Raw or Calcined Natura
8、l Pozzolan for Use in Concrete M 302, Slag Cement for Use in Concrete and Mortars T 280, Concrete Pipe, Manhole Sections, or Tile 2017 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of applicable law.TS-4a M 86M/M 86-2 AASHTO
9、 2.2. ASTM Standards: C309-03, Standard Specification for Liquid Membrane-Forming Compounds for Curing Concrete C989/C989M, Standard Specification for Slag Cement for Use in Concrete and Mortars C990-09, Standard Specification for Joints for Concrete Pipe, Manholes, and Precast Box Sections Using Pr
10、eformed Flexible Joint Sealants C1116/C1116M, Standard Specification for Fiber-Reinforced Concrete 3. TERMINOLOGY 3.1. DefinitionsFor definitions of terms relating to concrete pipe, see M 262. 4. CLASSIFICATION 4.1. Pipe manufactured according to this specification shall be of three classes identifi
11、ed as “Class 1 Nonreinforced Concrete Pipe,” “Class 2 Nonreinforced Concrete Pipe,” and “Class 3 Nonreinforced Concrete Pipe.” The corresponding strength requirements are prescribed in Table 1. Table 1Physical and Dimensional Requirements for Nonreinforced Concrete Pipea Class 1 Class 2 Class 3 Inte
12、rnal Designated Diameter Minimum Thickness of Wall Minimum Strength, Three-Edge Bearing Minimum Thickness of Wall Minimum Strength, Three-Edge Bearing Minimum Thickness of Wall Minimum Strength, Three-Edge Bearing mm in. mm in. kN/ linear m lbf/ linear ft mm in. kN/ linear m lbf/ linear ft mm in. kN
13、/ linear m lbf/ linear ft 100 4 16 5/8 22.0 1500 19 3/429.0 2000 19 3/435.0 2400 150 6 16 5/8 22.0 1500 19 3/429.0 2000 22 7/835.0 2400 200 8 19 3/422.0 1500 22 7/829.0 2000 29 11/835.0 2400 250 10 22 7/823.5 1600 25 1 29.0 2000 32 11/435.0 2400 300 12 25 1 26.5 1800 35 13/833.0 2250 44 13/438.0 260
14、0 375 15 32 11/429.0 2000 41 15/838.0 2600 47 17/842.0 2900 450 18 38 11/232.0 2200 50 2 44.0 3000 57 21/448.0 3300 525 21 44 13/435.0 2400 57 21/448.0 3300 69 23/456.0 3850 600 24 54 21/838.0 2600 75 3 52.5 3600 85 33/864.0 4400 675 27 82 31/441.0 2800 94 33/457.5 3950 94 33/467.0 4600 750 30 88 31
15、/244.0 3000 107 41/463.0 4300 107 41/469.5 4750 825 33 94 33/446.0 3150 113 41/264.0 4400 113 41/271.0 4875 900 36 100 4 48.0 3300 119 43/465.5 4500 119 43/473.0 5000 a Subject to tolerance in Section 11. 5. BASIS OF ACCEPTANCE 5.1. The acceptability of the pipe shall be determined by the results of
16、 the test prescribed in this section, when required, and by inspection to determine whether the pipe conform to this specification as to design and freedom from defects. 2017 by the American Association of State Highway and Transportation Officials.All rights reserved. Duplication is a violation of
17、applicable law.TS-4a M 86M/M 86-3 AASHTO 5.2. Acceptance as to Strength PropertiesPipe shall be acceptable under the strength tests when they have met the requirements as prescribed in Section 10.3. 5.3. Acceptance as to Absorption PropertiesPipe shall be acceptable under the absorption test when th
18、ey have met the requirements as prescribed in Section 10.4. 5.4. Acceptance as to Permeability PropertiesPipe shall be acceptable under the permeability test when they have met the requirements as prescribed in Section 10.5. Note 2Prior to purchase, the owner has the option to specify the hydrostati
19、c test prescribed in Section 10.6 instead of the permeability test. 5.5. Acceptance as to Hydrostatic PropertiesPipe shall be acceptable under the hydrostatic test when they have met the requirements as prescribed in Section 10.6. 6. MATERIALS 6.1. ConcreteThe concrete shall consist of cementitious
20、materials, mineral aggregates, and water. 6.2. Cementitious Materials: 6.2.1. CementCement shall conform to the requirements for portland cement of M 85 or shall be portland blast-furnace slag cement or slag modified portland cement, or portland-pozzolan cement conforming to the requirements of M 24
21、0M/M 240, except that the pozzolan constituent in the Type IP portland-pozzolan cement shall be fly ash. 6.2.2. Fly AshFly ash shall conform to the requirements of M 295, Class F or Class C. 6.2.3. Ground Granulated Blast-Furnace Slag (GGBFS)GGBFS shall conform to the requirements of Grade 100 or 12
22、0 of ASTM C989/C989M. 6.2.4. Allowable Combinations of Cementitious MaterialsThe combination of cementitious materials used in the concrete shall be one of the following: 6.2.4.1. Portland cement only, 6.2.4.2. Portland blast-furnace slag cement only, 6.2.4.3. Slag modified portland cement only, 6.2
23、.4.4. Portland-pozzolan cement only, or 6.2.4.5. A combination of portland cement and fly ash. 6.2.4.6. A combination of portland cement and ground granulated blast-furnace slag, or 6.2.4.7. A combination of portland cement, fly ash (not to exceed 25 percent of the total cementitious weight), and gr
24、ound granulated blast-furnace slag (not to exceed 25 percent of the total cementitious weight). 6.3. AggregatesAggregates shall conform to M 6 and M 80, except that the requirement for gradation shall not apply. 6.4. Admixtures and BlendsAdmixtures and blends shall conform to M 194M/M 194. 2017 by t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- AASHTOM86MM862017STANDARDSPECIFICATIONFORNONREINFORCEDCONCRETESEWERSTORMDRAINANDCULVERTPIPEPDF

链接地址:http://www.mydoc123.com/p-417840.html