UL 943B-2017 UL Standard for Safety Appliance Leakage-Current Interrupters (Third Edition).pdf
《UL 943B-2017 UL Standard for Safety Appliance Leakage-Current Interrupters (Third Edition).pdf》由会员分享,可在线阅读,更多相关《UL 943B-2017 UL Standard for Safety Appliance Leakage-Current Interrupters (Third Edition).pdf(53页珍藏版)》请在麦多课文档分享上搜索。
1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 943B Appliance Leakage-Current Interrupters STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERI
2、AL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Appliance Leakage-Current Interrupters, UL 943B Third Edition, Dated December 4, 2017 SUMMARY OF TOPICS: This new edition of ANSI/UL 943B is being issued to address editorial corrections
3、and maintenance of UL Standards for Safety. These changes are considered to be non-substantive and not subject to ULs STP process. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photoco
4、pying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, i
5、ncidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no ev
6、ent shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or jud
7、gment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. DECEMBER 4, 2017 UL 943B tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMIS
8、SION FROM UL DECEMBER 4, 2017 UL 943B tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL DECEMBER 4, 2017 1 UL 943B Standard for Appliance Leakage-Current Interrupters First Edition May, 2001 Second Edition August, 2011
9、Third Edition December 4, 2017 This ANSI/UL Standard for Safety consists of the Third Edition. The most recent designation of ANSI/UL 943B as an American National Standard (ANSI) occurred on October 26, 2017 ANSI approval for a standard does not include the Cover Page, Transmittal Pages, and Title P
10、age. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at https:/. ULs Standards for Safety are copyrighted by UL. Neither a printed
11、 nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2017 UNDERWRITERS LABORATORIES INC. ANSI/UL 943B-2017UL COPYRIGHTED MATERIAL NOT AU
12、THORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL DECEMBER 4, 2017 APPLIANCE LEAKAGE-CURRENT INTERRUPTERS - UL 943B 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scop
13、e .5 2 Glossary .5 3 Components7 4 Units of Measurement .7 5 References.7 CONSTRUCTION 6 Mechanical Assembly .7 7 Enclosure .11 7.1 General 11 7.2 Metal enclosures 11 7.3 Polymeric enclosures 12 7.4 Corrosion resistance .12 8 Accessibility of Uninsulated Live Parts and Film-Coated Wire .12 9 Electri
14、cal Insulation 13 10 Attachment Plug 13 11 Flexible Cord .15 12 Terminations .16 13 Grounding .17 14 Spacings 17 15 Alternate Spacings Clearances and Creepage Distances 19 16 Live Parts20 17 Internal Wiring20 18 Operating Mechanism .21 19 Supervisory Circuit 21 20 Auto-Monitoring Function 22 PROTECT
15、ION AGAINST INJURY TO PERSONS 21 Sharp Edges .22 PERFORMANCE 22 General23 23 Humidity Conditioning .25 24 Leakage Current Test .25 25 Drop Test 26 26 Voltage Surge Test .27 27 Trip Threshold Measurement .28 28 High-Resistance Ground Fault Test .29 29 Dielectric Voltage-Withstand Test .32 30 Resistan
16、ce to False Tripping Test 33 31 Temperature Test.34 32 Overload Test 36 33 Low-Resistance Ground Fault Test .38 34 Endurance Test 39 35 Abnormal Operation.41 DECEMBER 4, 2017 APPLIANCE LEAKAGE-CURRENT INTERRUPTERS - UL 943B 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBU
17、TION WITHOUT PERMISSION FROM UL 36 Extra-Low-Resistance Ground Faults Test .41 37 Short Circuit Test .43 38 Security of Blades Test 43 39 Crushing Resistance Test43 40 Strain-Relief Test .43 41 Security of Terminals44 42 Dust Test 44 43 Auto-Monitoring Function Test44 RATINGS 44 Details.46 MARKINGS
18、45 General46 APPENDIX A Standards for ComponentsA1 DECEMBER 4, 2017 APPLIANCE LEAKAGE-CURRENT INTERRUPTERS - UL 943B 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover appliance leakage-current
19、 interrupters (ALCIs), intended for use only in 2- or 3- wire alternating-current circuits wherein one of the wires is grounded in accordance with the National Electrical Code, ANSI/NFPA 70. They are intended to interrupt the electric circuit to the load when a fault current to ground exceeds some p
20、redetermined value that is less than that required to operate the overcurrent protective device of the supply circuit. An ALCI trips when the current to ground reaches a value in the range of46mA. 1.2 These requirements cover 2-wire appliance leakage-current interrupters for use only in cord-connect
21、ed appliances intended for connection to alternating-current circuits of 250 V or less. An additional ground conductor may be provided. They are not to be provided with a general-purpose outlet receptacle, cord-connector body, or similar devices. Devices complying with these requirements are accepta
22、ble for use as components in an end product where the acceptability of the combination is to be determined. 1.3 The acceptability of an appliance leakage-current interrupter in any particular application depends upon its ability to be used continuously under the conditions that prevail in actual ser
23、vice. Accordingly, for a particular application, an appliance leakage-current interrupter may be affected by the requirements for the equipment it is used in, and it may be necessary to additionally evaluate features or performance characteristics that are not specied in this standard. 1.4 This stan
24、dard does not cover ground-fault circuit-interrupters, which are covered by the Standard for Ground-Fault Circuit-Interrupters, UL 943. 2 Glossary 2.1 For the purpose of this standard, the following denitions shall apply: 2.2 ACCESSIBLE PART A part so located that it can be contacted by a person, ei
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 1人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- UL943B2017ULSTANDARDFORSAFETYAPPLIANCELEAKAGECURRENTINTERRUPTERSTHIRDEDITIONPDF

链接地址:http://www.mydoc123.com/p-1069071.html