NF E51-719-2008 Ventilation for buildings - Air handling units - Mechanical performance 《建筑物通风 空气调节装置 机械性能》.pdf
《NF E51-719-2008 Ventilation for buildings - Air handling units - Mechanical performance 《建筑物通风 空气调节装置 机械性能》.pdf》由会员分享,可在线阅读,更多相关《NF E51-719-2008 Ventilation for buildings - Air handling units - Mechanical performance 《建筑物通风 空气调节装置 机械性能》.pdf(38页珍藏版)》请在麦多课文档分享上搜索。
1、NF EN 1886janvier 2008Ce document est usage exclusif et non collectif des clients Saga Web.Toute mise en rseau, reproduction et rediffusion, sous quelque forme que ce soit,mme partielle, sont strictement interdites.This document is intended for the exclusive and non collective use of Saga Web custom
2、ers.All network exploitation, reproduction and re-dissemination,even partial, whatever the form (hardcopy or other media), is strictly prohibited.Saga Web Pour SHANGHAI INTERNAT SCIENCE b) units for residential buildings; c) units producing ventilation air mainly for a manufacturing process. Except
3、for the thermal and acoustic performance of the casing, the test methods and requirements are applicable to both complete units and any separate sections. The filter bypass test is not applicable to the testing of high efficiency particulate air filters (HEPA). NOTE HEPA filters are recommended to b
4、e installed downstream of the air handling unit. Such installations should be leak tested in accordance with the appropriate filter standards. The test method for the thermal performance of the casing is applicable to the comparison of different constructions, but not to the calculation of thermal l
5、osses through casing or the risk of condensation. Similarly, the test method for the acoustic performance of the casing is applicable to the comparison of different constructions, but not to the provision of accurate acoustic data for specific units. 2 Normative references The following referenced d
6、ocuments are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 779, Particulate air filters for general ventilation Determination of th
7、e filtration performance EN 1507, Ventilation for buildings Sheet metal air ducts with rectangular section Requirements for strength and leakage EN 12237, Ventilation for buildings Ductwork Strength and leakage of circular sheet metal ductsEN 12792:2003, Ventilation for buildings Symbols, terminolog
8、y and graphical symbolsEN 13053:2001, Ventilation for buildings - Air handling units Ratings and performance for units, components and sectionsEN 13501-1, 1Fire classification of construction products and building elements Part : Classification using test data from reaction to fire testsEN 61310-1,
9、1Safety of machinery Indication, marking and actuation Part : Requirements for visual, auditory and tactile signals 6131011995(IEC -: )EN ISO 3743 (all parts), Acoustics Determination of sound power levels of noise sources Engineering methods for small, movable sources in reverberant fields EN ISO 3
10、744, Acoustics Determination of sound power levels of noise sources using sound 37441994pressure Engineering method in an essentially free field over a reflecting plane (ISO : ) EN 1886:2007 (E) 8EN ISO 11546-2, Acoustics Determination of sound insulation performances of enclosures 2 1154621995Part
11、: Measurements in situ (for acceptance and verification purposes) (ISO -: ) EN ISO 12100-2, 2Safety of machinery Basic concepts, general principles for design Part : 1210022003Technical principles (ISO -: )3 Terms and definitions For the purposes of this European Standard, the terms and definitions
12、given in EN 12792:2003 and EN 13053:2001 and the following apply. 3.1air handling unit real unitfactory made encased unit serving as a prime mover of a ventilation or air conditioning installation where outdoor air, recirculated air or extract air is treated, consisting of a fan section where a filt
13、er section and heat exchanger may be connected. In addition the unit may consist of an inlet section with one or more louvres and dampers, a mixing section, heat recovery section, one or more heating and cooling coils, humidifiers, sound attenuators and additional equipment such as controls, measuri
14、ng sections etc. 3.2air handling unit model boxspecial test unit (defined in 8.3.2) used to execute measurements for general classification, comparison or categorisation of series or individual casings 4 Usage of real units and/or model boxes for the verification of mechanical performances For clear
15、 and non-ambiguous differentiation, it shall always be indicated whether the measurement has been made on the real unit or on the model box by using the letter “M“ for the model box and “R“ for the real unit in documentation. Test criteria of model boxes and real units are presented in Table 1. EN 1
16、886:2007 (E) 9Table 1 Test criteria of model box and real unit Kind of casing Test criteria Model box (M) Real unit (R) Mechanical strength General classification of casing construction Particular classification of casing construction and individual evaluationAir leakage General classification of ca
17、sing construction Particular classification of casing construction and individual evaluationFilter bypass leakage General classification of casing construction Particular classification of casing construction and individual evaluationThermal transmittance General classification of casing constructio
18、n -Thermal bridging General classification of casing construction -Acoustic insulation General classification of casing construction -5 Mechanical strength of casing 5.1 Requirements and classification Air handling unit casings shall be categorised into classes in accordance to Table 2. Table 2 Casi
19、ng strength classification of air handling units Casing class Maximum relative deflection mm m-1D1D2D3410exceeding 10 NOTE The leakage test shall be done after the strength test. For clear and non-ambiguous differentiation it shall always be indicated whether the measurement was made on the real uni
20、t or on the model box by using letter “M“ for the model box and “R“ for the real unit in documentation. EXAMPLE D1 (M) Class D1 and Class D2 casings shall be designed and selected so that the maximum deflection of any span of the panels and/or frames does not exceed the limits in Table 2 (see Figure
21、 2). EN 1886:2007 (E) 10The casings of class D1, D2 and D3 have to withstand the maximum fan pressure (not shock pressure) at the selected design fan speed. No permanent deformation (hysteresis maximum 2,0 mm per m frame/panel span) of the structural parts (structures and supports) or damage of the
22、casing may occur. Table 3 Test pressures Kind of casing Test criteria Model box (M) Real unit (R) Deflection 1 000 Pa Normal operating conditions at selected design fan speed Withstand maximum fan pressure 2 500 Pa Maximum fan pressure at selected design fan speed Parts of the real unit, which are r
23、unning under positive pressure, shall be tested under positive pressure. Parts of the real unit, which are running under negative pressure, shall be tested under negative pressure. Deviating test pressures shall be specified between the manufacturer and purchaser. EN 1886:2007 (E) 11Key A Panel defl
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NFE517192008VENTILATIONFORBUILDINGSAIRHANDLINGUNITSMECHANICALPERFORMANCE 建筑物 通风 空气调节 装置 机械性能 PDF

链接地址:http://www.mydoc123.com/p-1000773.html