NAVY MIL-DTL-24643 55 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +90 DEGREE C TYPE LS4NW《LS4NW型 -20 ℃~+90 ℃电缆》.pdf
《NAVY MIL-DTL-24643 55 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +90 DEGREE C TYPE LS4NW《LS4NW型 -20 ℃~+90 ℃电缆》.pdf》由会员分享,可在线阅读,更多相关《NAVY MIL-DTL-24643 55 F-2009 CABLE ELECTRICAL -20 DEGREE C TO +90 DEGREE C TYPE LS4NW《LS4NW型 -20 ℃~+90 ℃电缆》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、 INCH-POUND MIL-DTL-24643/55F 1 October 2009 SUPERSEDING MIL-DTL-24643/55E 22 August 2002 DETAIL SPECIFICATION SHEET CABLE, ELECTRICAL, -20 C TO +90 C, TYPE LS4NW This specification is approved for use by all Departments and Agencies of the Department of Defense. The requirements for acquiring the p
2、roduct described herein shall consist of this specification sheet and MIL-DTL-24643. Construction, Non-Watertight First - Copper conductor, coated or uncoated 8 AWG, Class B stranding, ASTM B8. Second - Separator may be used at manufacturers option where required to provide free-stripping insulation
3、. Third - Thermoset insulation with 0.045-inch minimum average thickness. Standard identification code shall be applied by Method 1 or Method 3. If Method 1 is used, the insulation color shall be black. Fourth - Four conductors cabled together with a lay in accordance with 3.4.4 of MIL-DTL-24643. Fi
4、llers may be used as necessary to form a firm well-rounded assembly. Fifth - An optional binder. Sixth - Cross-linked polyolefin jacket. Minimum average wall thickness of 0.050 inch. Maximum overall cable diameter 0.740 inch. NOTE: LS4NW-8 military part number M24643/55-01UN. AMSC N/A FSC 6145 Provi
5、ded by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-24643/55F REQUIREMENTS: Qualification required. INSPECTION: Basic Electricals: Conductor resistance (ohms/1000 feet at 25 C, max.) 0.679 Voltage withstand (volts, root mean square, min.) Conductor to
6、 conductor 4500 Insulation resistance (megohms/1000 feet, min.) Conductor to conductor 4200 Conductor continuity No failure Group A: Visual and dimensional No failure Group B: Cold bending cable No failure Thermoset proof test (percent, max.) Insulation 50 Jacket (when tested at 200 C) 50 Physicals
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- NAVYMILDTL2464355F2009CABLEELECTRICAL20DEGREECTO90DEGREECTYPELS4NWLS4NW 20 90 电缆 PDF

链接地址:http://www.mydoc123.com/p-978683.html