ITU-T SERIES L SUPP 8-2014 ITU-T L 1300 C Supplement on potential for primary energy savings in TLC ICT centres through free cooling (Study Group 5)《ITU-T L 1300 在薄层色谱 信息通信技术(ICT)中.pdf
《ITU-T SERIES L SUPP 8-2014 ITU-T L 1300 C Supplement on potential for primary energy savings in TLC ICT centres through free cooling (Study Group 5)《ITU-T L 1300 在薄层色谱 信息通信技术(ICT)中.pdf》由会员分享,可在线阅读,更多相关《ITU-T SERIES L SUPP 8-2014 ITU-T L 1300 C Supplement on potential for primary energy savings in TLC ICT centres through free cooling (Study Group 5)《ITU-T L 1300 在薄层色谱 信息通信技术(ICT)中.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、 I n t e r n a t i o n a l T e l e c o m m u n i c a t i o n U n i o n ITU-T Series L TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Supplement 8 (12/2014) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT ITU-T L.1300 Supplement on potential for prim
2、ary energy savings in TLC/ICT centres through free cooling ITU-T L-series Recommendations Supplement 8 L series Supplement 8 (12/2014) i Supplement 8 to ITU-T L-series Recommendations ITU-T L.1300 Supplement on potential for primary energy savings in TLC/ICT centres through free cooling Summary Supp
3、lement 8 to the L series of Recommendations refers to the best practices defined in Recommendation ITU-T L.1300. More precisely, this Supplement first provides an introduction of potential for primary energy savings in TLC/ICT centres through the free cooling solution. Then, a probabilistic model fo
4、r the inlet conditions is defined, and finally an analysis on room temperature and energy consumption is reported. History Edition Recommendation Approval Study Group Unique ID* 1.0 ITU-T L Suppl. 8 2014-12-19 5 11.1002/1000/12436 Keywords Best practice, data centre, energy efficient, information an
5、d communication technology and climate change (ICT a probabilistic model for the inlet conditions; and a room temperature and energy analysis. 2 Definitions This Supplement uses the following term: 2.1 power density: The energy consumption of ICT equipment per rack cabinet of floor area of a server
6、room. 3 Abbreviations and acronyms This Supplement uses the following abbreviations and acronyms: COP Coefficient Of Performance RH Relative Humidity 4 Introduction The growth of modern society is characterized by dynamism in communications, and in recent years the field of telecommunications has ac
7、hieved great importance in the socio-economic development of many countries. Such a trend requires increased power installation in data centres that serve to allocate routers, switches, computers, and many other equipment that have high energy requirements. Such data centres generate heat that must
8、be dissipated. To give an example, the mean value of electrical power density installed in Italian telecommunication plants is about 450 W/m2 and all this electrical power is converted into endogenous power. In 2007, electrical energy consumption for Italian telecommunications was 4000 GWh, which is
9、 1.25% of global electrical energy consumption for that year. Moreover, data shows that the global demand for electrical energy has increased by 0.4% with respect to 2006 data, but that the increase in telecommunications was 1.5%. The most important Italian telecommunication company is the second na
10、tional user for energy consumption; with 0.7% of total national energy demand (the largest user is the national railway transport company). More than half of the energy consumption is used for fixed network and mobile equipment, and approximately 16% of this part is used for cooling. In total, elect
11、rical energy purchased or generated by the group in 2007 amounts to 2.15 TWh, i.e., about 2.3% more than energy used in 2006, and 7.36% more than energy used in 2005. Equipment in data centres have to operate within defined temperature and humidity conditions, because their internal circuits are sen
12、sitive to excessively high or low temperature and humidity. Furthermore, the equipment cannot be switched off because data must be transmitted from centre to centre 24 hours a day, 7 days per week. ETSI standard b-EN 300 019-1-3 establishes the upper and lower limits for temperature and humidity in
13、which equipment must operate. 2 L series Supplement 8 (12/2014) To maintain correct operating conditions, the cooling system must operate continuously, absorbing large amounts of electricity. To contribute to energy saving policies, such as the 20/20/20 objectives established by the European Commiss
14、ion, the use of alternative cooling systems for data centres air conditioning is crucial. Free cooling consists of the direct use of external air to cool the environment. The temperature of external air can be reduced by injecting water spray, if the external humidity is lower than 100%. This is cal
15、led adiabatic free cooling. Free cooling is a rational option for the telecommunication sector, as the temperature tolerated in data centres is usually above outdoor temperature and because of the non-stop operation of the equipment. Knowledge of typical external temperature and relative humidity is
16、 particularly important for a correct design of a free cooling system. Such information is available for various locations, and otherwise a model may be used. A possible model is presented in the next clause. This is particularly useful because of the small number of parameters required for its appl
17、ication to a location. In addition, it provides a general behaviour that should be adopted for compact representation of the suitability of free cooling systems in a location. This Supplement describes a general approach to the energy analysis of free cooling systems and its application to telecommu
18、nication centres located in Italy. In the mid-term it could also be applied to data centres. First, a probabilistic model for ambient temperature and relative humidity is presented. This is the basis for predicting the air inlet condition. Then some theoretical and experimental data obtained from me
19、asurements in the Telecom Italia telecommunication laboratory are presented. These data allow one to relate the inlet air condition to the operating conditions of the equipment. Ultimately, the energy savings that can be achieved through use of free cooling systems in Italy is calculated. Italian lo
20、cations are classified in terms of energy saving due to free cooling and adiabatic free cooling use, and the opportunity of using such a technique is highlighted through a pictorial representation on the Mollier diagram, where the limits of the ETSI standard are also drawn. With respect to the ETSI
21、diagram, here the properties of the probabilistic model of temperature and relative humidity are used for a more compact representation. 5 Probabilistic model for the inlet conditions External air temperature and relative humidity (RH) define the applicability of free cooling. If the temperature is
22、too high, a large air mass flow rate may be necessary to keep the internal temperature within acceptable limits. However, it may be impossible if the external temperature is above the maximum internal temperature. A model that represents the daily temperature (and RH) trend, allows temperature distr
23、ibution to be foreseen for an assigned geographical site on the basis of little data, generally available for most locations. This model is composed of two parts. The first part is an equation that makes it able to describe hourly temperature and RH in the average day of each month. Then a stochasti
24、c model is applied in order to account for expected deviations. 5.1 Temperature model The model is aimed at obtaining an average daily temperature trend for an assigned site and an assigned time step; temperature distribution has been described by simplified mathematical functions that require the l
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ITUTSERIESLSUPP82014ITUTL1300CSUPPLEMENTONPOTENTIALFORPRIMARYENERGYSAVINGSINTLCICTCENTRESTHROUGHFREECOOLINGSTUDYGROUP5ITUTL1300

链接地址:http://www.mydoc123.com/p-803359.html