《EPA FED EPA 833-R-92-001-1992 DEVELOPING POLLUTION PREVENTION PLANS AND BEST MANAGEMENT PRACTICES SUMMARY GUIDANCE《环保改进计划和最佳管理实践概要导则》.pdf》由会员分享,可在线阅读,更多相关《EPA FED EPA 833-R-92-001-1992 DEVELOPING POLLUTION PREVENTION PLANS AND BEST MANAGEMENT PRACTICES SUMMARY GUIDANCE《环保改进计划和最佳管理实践概要导则》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、 U.S. Department of Transportation Federal Aviation Administration Advisory Circular Subject: SPECIFICATIONS FOR AIRPORT LIGHTING CIRCUIT SELECTOR SWITCH Date: September 14, 2006 Initiated by: AAS-100 AC No: 150/5345-5B Change: 1. PURPOSE. This advisory circular (AC) contains a specification for a c
2、ircuit selector switch for use in airport lighting circuits. 2. EFFECTIVE DATE. Effective 6 months after the issue date of this advisory circular, only that equipment qualified in accordance with the specifications contained in this AC will be listed in AC 150/5345-53, Airport Lighting Equipment Cer
3、tification Program, current edition. 3. CANCELLATIONS. This AC cancels AC 150/5345-5A, Specification for L-847 Circuit Selector Switch, 5,000 Volt 20 Ampere, dated March 23, 1982. 4. PRINCIPAL CHANGES. The following principal changes are contained in this specification. a. The addition of an optiona
4、l L-847 monitoring contact closure feature. b. The addition of an optional L-847 door interlock switch. c. The “High-Voltage Contact“ cycle switching test was changed from 5,000 cycles to 10,000 cycles. 5. METRIC UNITS. To promote an orderly transition to metric units, this specification includes bo
5、th English and metric dimensions. The metric conversions may not be exact equivalents, and until an official changeover to metric units is effective, the English dimensions will govern. David L. Bennett Director Airport Safety and StandardsProvided by IHSNot for ResaleNo reproduction or networking p
6、ermitted without license from IHS-,-,-AC 150/5345-5B 1. SCOPE AND CLASSIFICATION. 1.1 Scope. This specification covers the requirements for a circuit selector switch to be used for switching the output of a constant current regulator (CCR) to one or more series lighting loops. 1.2 Classification. Th
7、is specification covers four types, two classes, and two sizes of circuit selector switches: 1.2.1 Type. This specification covers circuit selector switches of the following types: Type L-847-1 One circuit control Type L-847-2 Two circuit control Type L-847-3 Three circuit control Type L-847-4 Four
8、circuit control 1.2.2 Classes. This specification covers circuit selector switches of the following classes: Class A Designed for indoor installations Class B Designed for outdoor installations 1.2.3 Ratings. This specification covers circuit selector switches of the following ratings: Rating 1 Desi
9、gned for 6.6 ampere, 5,000 volt circuits Rating 2 Designed for 20 ampere, 5,000 volt circuits 2. APPLICABLE DOCUMENTS. 2.1 General. The following documents, of the issue in effect on the date of application for qualification, form part of this specification and are applicable to the extent specified
10、 herein. 2.2 Federal Aviation Administration (FAA) Documents. 2.2.1 FAA Standard. FAA-STD-012a Paint Systems for Equipment FED-STD-595 Colors Used in Government Procurement 2 Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-AC 150/5345-5B - Copies of
11、FAA Standards may be obtained from: Federal Aviation Administration ATO-W CM - NAS Documentation Control Center 800 Independence Avenue, SW Washington, DC 20591 Phone: (202) 548-5502 Fax: (202) 548-5501 Website: http:/www.faa.gov/cm/dcc/ 2.2.2 FAA Advisory Circular. AC 150/5345-53 Airport Lighting E
12、quipment Certification Program Copies of FAA ACs may be obtained from: Department of Transportation General Services Division M-45 Washington, DC 20590 Phone: (202) 267-3115, -3161, and -8329 Website: http:/www.faa.gov/airports_airtraffic/airports/resources/advisory_circulars/2.3 Military Standard.
13、MIL-STD810C Environmental Test Methods Copies of Military Standards and Specification Publications may be obtained from: DAPS/DODSSP Building 4, Section D 700 Robins Avenue Philadelphia, PA 19111-5094 Phone: (215) 697-2179 Fax: (215) 697-1460 Website: http:/dodssp.daps.dla.mil/ 3 Provided by IHSNot
14、for ResaleNo reproduction or networking permitted without license from IHS-,-,-AC 150/5345-5B 3. REQUIREMENTS. 3.1 General Functional Requirements. The circuit selector switch(es) must be capable of switching the output of a constant current regulator to one or more series lighting circuits (loops),
15、 as illustrated in figure 1. The selector switch must be controllable locally or from a remote location. External control switches for remote operation are to be supplied by others. 3.2 Environmental Requirements. The circuit selector switch(es) must be designed for operations under the following en
16、vironmental conditions: a. An ambient temperature range of -40 F (-40 C) to + 131 F (+55)C b. A pressure altitude range of sea level to 10,000 feet (3,000 m). c. A relative humidity of up to 100 percent from sea level to 10,000 feet (3,000 m) at an ambient temperature of + 131 F (+55)C -. 3.3 Enclos
17、ures. All components must be mounted in an enclosure with a hinged access door capable of being padlocked. Class A selector switch enclosures must be designed for wall mounting and be equal to a National Electrical Manufacturers Association (NEMA) type 1. Class B selector switch enclosures must be d
18、esigned to allow bottom mounting by means of a 2-inch conduit and be equal to a NEMA type 4. All external electrical wiring is to enter the enclosure through conduit. The size of the enclosure must be held to a minimum consistent with good design practices. All high-voltage connections must be made
19、behind a dead front panel so as to be inaccessible when the enclosure door is opened to allow local control operations. The enclosure must be painted in accordance with the applicable section of FAA-STD-012a. Class B enclosures must be painted with aviation orange paint # 12197 per FED-STD-595. 3.4
20、High-Voltage Contacts. The circuits must be switched through a series of high-voltage contacts as shown in figure 1. When a circuit is to be energized, the normally open contacts close first, followed by the opening of the normally closed contact across the constant current regulator input to the sw
21、itch. The reverse procedure is followed when de-energizing the circuit. The contacts must be rated to interrupt a 6.6-ampere circuit for the Rating 1 switch and a 20-ampere circuit for the Rating 2 switch from a constant current regulated power source having a circuit voltage of up to 5,000 volts. A
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- EPAFEDEPA833R920011992DEVELOPINGPOLLUTIONPREVENTIONPLANSANDBESTMANAGEMENTPRACTICESSUMMARYGUIDANCE 环保

链接地址:http://www.mydoc123.com/p-727384.html