EN 60156-1995 en Insulating Liquids Determination of the Breakdown Voltage at Power Frequency Test Method《绝缘液 工业频率下击穿电压的测定 试验方法(IEC 156-1995)》.pdf
《EN 60156-1995 en Insulating Liquids Determination of the Breakdown Voltage at Power Frequency Test Method《绝缘液 工业频率下击穿电压的测定 试验方法(IEC 156-1995)》.pdf》由会员分享,可在线阅读,更多相关《EN 60156-1995 en Insulating Liquids Determination of the Breakdown Voltage at Power Frequency Test Method《绝缘液 工业频率下击穿电压的测定 试验方法(IEC 156-1995)》.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、- CENELEC *EN*bOL5b 95 = 3404583 OL7l105b 872 BRITISH STANDARD Insulating liquids - Determination of the breakdown voltage at power frequency - Test method The European Standard EN 60156 : 1995 has the status of a British Standard ICs 29.040.20 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED B
2、Y COPYRIGHT LAW 3s EN i0156 : 1996 EC 156 : 1995 BS EN 60166 : 1996 CENELEC +ENtbOL5b 95 34045133 OL7L057 709 Committees responsible for this British Standard The preparation of this British Standard was entrusted to Technicd Committee GW10, Flui the instrument then used shall be calibrated against
3、a standard up to the full voltage which it is desired to measure. A method of calibration which has been found satisfactory is the use of a transfer standard. This is an auxiliary measuring device which is connected in place of the test cell between the high-voltage terminals to which it presents th
4、e same impedance as the filled test cell. The auxiliary device is separately calibrated against a primary standard, for example, a sphere gap in accordance with IEC 52 (see also IEC 60). 4 Test assembly 4.1 Test cell The volume of the cell shall be between 350 ml and 600 ml. The cell shall be made o
5、f material that is electrically insulating, transparent and chemically inert, resistant to the insulating liquid and the cleaning agents which may be used. The cell shall be provided with a cover and shall be designed to permit easy removal of the electrodes for cleaning and maintenance. Examples of
6、 suitable cell designs are given in figures 1 and 2. 4.2 Electrodes The electrodes shall be made either of brass, bronze or austenitic stainless steel. They shall be polished and, in shape, either spherical (123 mm to 13,O mm diameter) as shown in figure 1 or partially spherical of the shape and dim
7、ensions given in figure 2. The axis of the electrode system shall be horizontal, and at least 40 mm below the surface of the test liquid in the cell. No part of the electrode shall be closer than 12 mm to the cell wall or stirrer. The gap between the electrodes shall be 250 mm * 0,05 mm. CENELEC *EN
8、*h015b 75 W 3404583 OL7LObb 711 = Page 7 EN 60156 : 1995 The electrodes shall be examined frequently for pitting or other damage, and shall be maintained or replaced as soon as such damage is observed. 4.3 Stirring (optional) The test may be conducted with or without stirring. Differences between te
9、sts with or without stirring have not been found statistically significant. A stirrer, however, may be convenient especially with apparatus capable of automatic operation. Stirring may be achieved by means of a two-bladed impeller of effective diameter 20 mm to 25 mm, axial depth 5 mm to 10 mm, rota
10、ting at a speed of 250 r.p.m to 300 r.p.m. The impeller shall not entrain air bubbles and preferably rotate in such a direction that the resulting liquid flow is directed downward. It shall be constructed so that it is easily cleaned. Stirring by means of a magnetic bar (20 mm to 25 mm in length and
11、 5 mm to 10 mm in diameter) is an acceptable alternative when there is no risk of removing magnetic particles. The dimensions of the stirring device shall conform to the ctearance requirements in 4.2. 5 Preparation of electrodes New electrodes, pitted electrodes, electrodes which have not been prope
12、rly stored for a considerable time shall be cleaned by the following procedure: - clean all surfaces with a suitable volatile solvent and allow the solvent to evaporate; - polish with fine abrasive powder (for example, jewellers rouge) or abrasive paper or cloth (for example, crocus cloth); - after
13、polishing, clean with petroleum spirit (reagent quality: boiling range 60 OC - 80 OC) followed by acetone (reagent quality); - assemble the electrodes in the cell, fill with a clean, unused insulating liquid of the type to be tested next, and raise the electrode voltage to breakdown 24 times. 6 Test
14、 assembly preparation It is recommended that a separate test cell assembly be reserved for each insulating liquid tY Pe- Test assemblies shall be stored in a dry place, covered and filled with dry insulating liquid of the type in regular use in the cell. On change of the type of liquid under test, r
15、emove all residues of the previous liquid with an appropriate solvent, rinse the assembly with clean, dry liquid of the same type as that to be tested, drain and refill. CENELEC *EN*bO156 95 = 3404583 0173067 658 Page 8 EN 60156 : 1995 7 Sampling 7.1 Sample containers Sample size should be approxima
16、tely three times the capacity of the test cell. Appropriate sample containers shall comply with IEC 475. An amber glass bottle is the preferred container. Clear glass bottles may be used but they shall be shielded from direct light until ready to be tested. Plastic containers which are not attacked
17、by the liquid to be tested may be used, but these shall not be used more than once. For sealing, screw caps with polyolefine or polytetrafluoroethylene insert are preferred. . Containers and caps shall be cleaned by washing with a suitable solvent to remove residues of an earlier sample. Containers
18、shall next be rinsed with acetone, traces of which shall be removed by blowing with warm air. After cleaning, containers shall be immediately capped and kept sealed until used. 7.2 Sampling technique Sampling of new and used insulating liquids shall be carried out in full compliance with procedures
19、detailed in IEC 475. When sampling, containers should be almost filled with sample, leaving about 3 70 of the container volume as free air space. Breakdown voltage is extremely sensitive to the slightest contamination of the sample by water and particulate matters. Special reference is made to preca
20、utions necessary to avoid contamination of the sample and the need for trained personnel and experienced supervision. Unless otherwise required, the sample is taken where the liquid is likely to be most contaminated, usually at the lowest point of the container holding it. 8 Condition of the sample
21、The test is carried out, unless otherwise specified, on the sample as received without drying or degassing. At the time of test, the temperatures of the test liquid and ambient air shall not differ by more than 5 OC and for referee tests the liquid temperature shall be 20 OC f 5 OC. 9 Test procedure
22、 9.1 Sample preparation Immediately before filling the test cell, the sample container is gently agitated and turned over several times in such a way as to ensure as far as possible a homogeneous distribution of the impurities contained in the liquid without causing the formation of air bubbles. Unn
23、ecessary exposure to the ambient air of the sample shall be avoided. Page 9 EN 60156 : 1995 CENELEC *EN*b015b 95 3YOY583 0171Ob8 594 H 9.2 Filling of the cell Immediately before commencing the test, drain the test cell and rinse the walls, electrodes and other component parts, with the test sample.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- EN601561995ENINSULATINGLIQUIDSDETERMINATIONOFTHEBREAKDOWNVOLTAGEATPOWERFREQUENCYTESTMETHOD 绝缘 工业 频率 击穿

链接地址:http://www.mydoc123.com/p-717668.html