1、AMSC N/A FSC 6145 INCH-POUND MIL-DTL-38359E 27 September 2011 SUPERSEDING MIL-DTL-38359D 24 January 2011 DETAIL SPECIFICATION CABLE, POWER, ELECTRICAL, AIRPORT LIGHTING, CROSS-LINKED, POLYETHYLENE (XLP) This specification is approved for use by all Departments and Agencies of the Department of Defen
2、se. 1. SCOPE 1.1 Scope. This specification covers 8 AWG single conductor electric power cable of two voltage ranges intended primarily for use in airport lighting series circuits. 1.2 Classification. Cables are of the following classes, as specified: Class 1 3,000 V rms Class 2 5,000 V rms 1.2.1 Par
3、t or Identifying Number (PIN). PINs are of the following form, as specified: Class 1 M38359-3K Class 2 M38359-5K 2. APPLICABLE DOCUMENTS 2.1 General. The documents listed in this section are specified in sections 3, 4 or 5 of this specification. This section does not include documents cited in other
4、 sections of this specification or recommended for additional information or as examples. While every effort has been made to ensure the completeness of this list, document users are cautioned that they must meet all specified requirements of documents cited in sections 3, 4 or 5 of this specificati
5、on, whether or not they are listed. Comments, suggestions, or questions on this document should be addressed to DLA Land and Maritime, ATTN: VAI, P.O. Box 3990, Columbus, Ohio 43218-3990, or email to WireCabledla.mil. Since contact information can change, you may want to verify the currency of this
6、address information using the ASSIST Online database at https:/assist.daps.dla.mil. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MIL-DTL-38359E 2 2.2 Government documents. 2.2.1 Specifications, standards and handbooks. The following specifications
7、, standards and handbooks form a part of this document to the extent specified herein. Unless otherwise specified, the issues of these documents are those listed in cited in the solicitation or contract. DEPARTMENT OF DEFENSE STANDARDS MIL-STD-810 - Environmental Engineering Considerations and Labor
8、atory Tests (Copies of these documents are available online at https:/assist.daps.dla.mil/quicksearch/ or from the Standardization Document Order Desk, 700 Robbins Avenue, Building 4D, Philadelphia, PA 19111-5094.) 2.3 Non-Government publications. The following documents form a part of this document
9、 to the extent specified herein. Unless otherwise specified, the documents are the issues of the documents cited in the solicitation or contract. INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO) ISO 10012-1 - Equipment, Quality Assurance Requirements for Measuring - Part 1 Metrological Confirmat
10、ion System for Measuring Equipment (Copies of these documents are available online at http:/www.iso.ch or from the International Organization for Standardization American National Standards Institute, 11 West 42ndStreet, 13thFloor, New York, NY 10036.) NCSL INTERNATIONAL NCSL Z540.3 - General Requir
11、ements for Calibration of Measuring and Test Equipment (Copies of these documents are available online at http:/www.ncsli.org or from NCSL International, 2995 Wilderness Place, Suite 107 Boulder, Colorado 80301-5404) NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION, (NEMA) NEMA WC 71 Standard for Non-S
12、hielded Power Cables Rated 2001 5000 Volts for Use in the Distribution of Electrical Energy Copies of these documents are available online at http:/www.nema.org or from the National Electrical Manufacturers Association, 1300 North 17th Street, Suite 1847, Rosslyn, VA 22209.) 2.4 Order of precedence.
13、 In event of a conflict between the text of this document and the references cited herein, the text of this document takes precedence. Nothing in this document, however, supersedes applicable laws and regulations unless a specific exemption has been obtained. Provided by IHSNot for ResaleNo reproduc
14、tion or networking permitted without license from IHS-,-,-MIL-DTL-38359E 3 3. REQUIREMENTS 3.1 First article. Cables specified under this specification shall be subjected to a first article inspection (see 6.6). First article inspection shall be performed at laboratory acceptable to the procuring ac
15、tivity on sample units produced with equipment and procedures used in production. 3.2 Materials. The materials for the principal components of the cable shall be as specified herein. Prior approval to use substitute material must be obtained from the qualifying activity. When a definite material is
16、not specified, a material shall be used that will enable the finished products to meet the performance requirements of this specification. Acceptance or approval of any constituent material shall not be construed as a guaranty of the acceptance of the finished product. All materials used in the manu
17、facture of cables furnished to comply with this specification shall be of such quality and form that the finished product conforms to the requirements of this specification. 3.3 Design and construction. The cable shall be designed and constructed for use in airport lighting systems. It shall be cons
18、tructed for continuous outdoor service under all weather conditions while on the surface of the ground, buried directly in the ground, installed in conduit, or submerged in fresh or salt water. The voltage rating, high potential withstanding voltage, wire size, and average thickness of the insulatio
19、n for the cables specified herein shall be as specified in table I. TABLE I. Combined cable characteristics. Characteristic Class 1 Class 2 Voltage rating 3,000 V rms 5,000 V rms High potential withstanding voltage 7,500 V rms (5 minutes) 11,000 V rms (5 minutes) Insulation thickness (average) .075
20、inch (1.91 mm) .11 inch (2.79 mm) Diameter: Minimum .31 inch (7.87 mm) .38 inch (9.65 mm) Nominal .32 inch (8.13 mm) .39 inch (9.91 mm) Maximum .34 inch (8.64 mm) .41 inch (10.41 mm) 3.3.1 Conductors. The conductor shall conform to type C, number 8 AWG, class B, tin coated. 3.3.1.1 Splices. Splices
21、in the conductor shall be such that each splice will not increase the diameter of the conductor. No splice shall be made in the conductor as a whole. Not more than one strand shall be spliced in any one foot of conductor. 3.3.1.2 Resistance. The resistance of the conductor of 1,000 feet of completed
22、 cable at +20 C shall not be greater than .65 ohm. 3.3.1.3 Conductor shield. A semiconducting layer or tape shall be applied directly over the stranded conductor, over which the cable insulation shall be applied. The conductor shield shall have a minimum thickness of .005 inch (0.13 mm). 3.3.1.4 Mar
23、ker threads. Nonhygroscopic-type marker threads shall be provided in the conductor strands or directly along the conductor for identification purposes. The color and number of threads used shall be identical with those used by the manufacturer on his other products. Provided by IHSNot for ResaleNo r
24、eproduction or networking permitted without license from IHS-,-,-MIL-DTL-38359E 4 3.3.2 Insulation. The insulation shall consist of a black cross-linked thermoplastic polyethylene (XLP) compound which meets the requirements for the insulation specified in NEMA WC 71 and all the requirements specifie
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- DLAMILDTL38359E2011CABLEPOWERELECTRICALAIRPORTLIGHTINGCROSSLINKEDPOLYETHYLENEXLPPDF

链接地址:http://www.mydoc123.com/p-690664.html