《ASTM F2707-2010(2018)e1 Standard Safety Performance Specification for Safe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Preventio.pdf》由会员分享,可在线阅读,更多相关《ASTM F2707-2010(2018)e1 Standard Safety Performance Specification for Safe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Preventio.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F2707 10 (Reapproved 2018)1Standard Safety Performance Specification forSafe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Prevention inSwimming Pools, Spas, Hot Tubs, and Wading Pools1This standard is issued under the fixed designation
2、 F2707; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reap
3、proval.1NOTEEditorially corrected Referenced Documents in June 2018.1. Scope1.1 This safety performance specification provides require-ments for safety in design and installation when using asuction-limiting vent system for suction entrapment preventionin swimming pools, spas, hot tubs, or wading po
4、ols.1.2 The purpose of the vent is to relieve the vacuum at thesuction outlet(s) caused by any blockage of the suctionoutlet(s). The vent is intended to prevent body entrapment atthe suction outlet(s) and may also mitigate limb entrapment. Itis not intended to prevent other injuries caused by the su
5、ctionoutlet(s) such as hair entrapment, mechanical entrapment, orevisceration.1.3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 Thi
6、s standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limitations prior to use.1.5 Th
7、is international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade
8、 (TBT) Committee.2. Referenced Documents2.1 ANSI Standards:2ANSI Z535.2 Environmental and facility safety signsANSI Z535.4 Product safety signs and labelsANSI/APSP 16 Standard Suction Fittings for Use in Swim-ming Pools, Wading Pools, Spas, and Hot Tubs3. Terminology3.1 Definitions:3.1.1 allowable d
9、rawdown, ndrawdown depth corre-sponding to the acceptable removal effort for a particularuncovered sump; it is physically built into the system.3.1.2 engineer, nregistered professional engineer.3.1.3 field-fabricated vent (FFV), nopen-to-atmospherevent installed between the pool suction outlet(s) an
10、d the suctionside of the pump in such a way as to relieve the vacuum causedby a blockage of the suction outlet(s).3.1.4 operating drawdown, nlowering of the water levelin the vent from the static condition caused by normaloperation.3.1.5 purge test, nplacing a blocking element over thesump to ensure
11、 that air enters the vent system.3.1.6 startup surge, ntransient lowering of the water levelin the vent during pump startup.3.1.6.1 DiscussionIf excessive, the pump may lose prime.4. Significance and Use4.1 This performance specification outlines the require-ments needed to design and install a fiel
12、d-fabricated vent forsafety purposes. Vents only address suction outlet body andmay mitigate limb entrapment. Vents have proven effective1This test method is under the jurisdiction of ASTM Committee F15 onConsumer Products and is the direct responsibility of Subcommittee F15.51 onSafety Vacuum Relea
13、se Systems for Swimming Pools, Spas and Hot Tubs.Current edition approved May 1, 2018. Published June 2018. Originallyapproved in 2010. Last previous edition approved in 2010 as F2707 10. DOI:10.1520/F2707-10R18E01.2Available fromAvailable from American National Standards Institute (ANSI),25 W. 43rd
14、 St., 4th Floor, New York, NY 10036, http:/www.ansi.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established i
15、n the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1when installed correctly. It is not intended to prevent otherinjuries caused by suction outlet(s) such as hair en
16、trapment,mechanical entrapment, or evisceration.5. General Requirements5.1 Design and installation instructions for field-fabricatedvents (FFV) shall be certified only by a registered professionalengineer. Multiple systems may be built to the same “ventdesign drawings and specifications” with the ap
17、proval of theengineer.5.2 The design and installation of the vent is specific to eachpiping system and shall consider all relevant parametersincluding but not limited to: elevations, flow rate, startup surge,minimum and maximum water operating levels, water depth atthe suction outlet(s), pipe fittin
18、gs, spacing between fittings,atmospheric vent fitting, and suction outlet configurations.5.3 The vent shall be tested in place for proper function. SeeSection 7 for details.6. Specific Requirements6.1 The engineer shall specify minimum and maximum flowrates, pipe sizes, and minimum and maximum pipe
19、length(s),including equivalent length of fittings, elevation of criticalfittings with respect to normal pool operating level, as well asthe make and model of the suction outlet approved cover inaccordance with ANSI/APSP 16, including the head loss at thesuction fitting and the make and model of the
20、atmospheric venttermination fitting. Vent termination fittings are rated by thesize of the pipe they can successfully vent. For larger pipes, thenumber of fittings shall equal or exceed the flow area of thelarge pipe divided by the flow area of the fittings rated pipesize.6.2 The vent shall be desig
21、ned to insure that with any or allsuction outlet(s) completely blocked, the sump or vent draw-down shall not exceed the values in Table 1 for the size of agiven suction outlet sump with the vent termination fitting inplace and with or without the cover in place.6.3 The vent system and atmospheric ve
22、nt terminationfitting shall be designed so that neither can be disabled withoutthe use of tools.6.4 Under normal operation, the vent system shall notadversely affect pump suction, system flow, or other equipmentperformance.6.5 No check valves or valves shall be installed between anysuction outlet an
23、d the atmospheric opening of the system.6.6 The vent shall be piped to a location specified by theregistered professional engineer. If the vent is located outsidethe deck area, the vent shall be clearly visible and above gradeas indicated by the engineer.TABLE 1 Allowable Drawdown for Circular and S
24、quare Open SumpKcircLT9= KcircGT9= KsqLT9= KsqGT9=Diam (in.) Drawdown (in.) Diam (in.) Drawdown (in.) Side (in.) Drawdown (in.) Side (in.) Drawdown (in.)2 132.4 9 6.5 2 104.0 9 5.12.25 104.6 9.25 6.7 2.25 82.1 9.25 5.32.5 84.7 9.5 7.0 2.5 66.5 9.5 5.52.75 70.0 9.75 7.1 2.75 55.0 9.75 5.63 58.8 10 7.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF270720102018E1STANDARDSAFETYPERFORMANCESPECIFICATIONFORSAFEDESIGNANDINSTALLATIONOFFIELDFABRICATEDSUCTIONLIMITINGVENTSYSTEMSFORSUCTIONENTRAPMENTPREVENTIOPDF

链接地址:http://www.mydoc123.com/p-539306.html