ASTM F2707-2010 Standard Safety Performance Specification for Safe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Prevention in Sw.pdf
《ASTM F2707-2010 Standard Safety Performance Specification for Safe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Prevention in Sw.pdf》由会员分享,可在线阅读,更多相关《ASTM F2707-2010 Standard Safety Performance Specification for Safe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Prevention in Sw.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F2707 10Standard Safety Performance Specification forSafe Design and Installation of Field Fabricated Suction-Limiting Vent Systems for Suction Entrapment Prevention inSwimming Pools, Spas, Hot Tubs, and Wading Pools1This standard is issued under the fixed designation F2707; the number
2、immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1
3、This safety performance specification provides require-ments for safety in design and installation when using asuction-limiting vent system for suction entrapment preventionin swimming pools, spas, hot tubs, or wading pools.1.2 The purpose of the vent is to relieve the vacuum at thesuction outlet(s)
4、 caused by any blockage of the suctionoutlet(s). The vent is intended to prevent body entrapment atthe suction outlet(s) and may also mitigate limb entrapment. Itis not intended to prevent other injuries caused by the suctionoutlet(s) such as hair entrapment, mechanical entrapment, orevisceration.1.
5、3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associ
6、ated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ANSI Standards:2ANSI Z535.2 Environmental and facility safety signsANSI Z53
7、5.4 Product safety signs and labelsASME/ANSI A112.19.8 Suction Fittings for Use in Swim-ming Pools, Wading Pools, Spas, and Hot Tubs3. Terminology3.1 Definitions:3.1.1 allowable drawdown, ndrawdown depth corre-sponding to the acceptable removal effort for a particularuncovered sump; it is physically
8、 built into the system.3.1.2 engineer, nregistered professional engineer.3.1.3 field-fabricated vent (FFV), nopen-to-atmospherevent installed between the pool suction outlet(s) and the suctionside of the pump in such a way as to relieve the vacuum causedby a blockage of the suction outlet(s).3.1.4 o
9、perating drawdown, nlowering of the water levelin the vent from the static condition caused by normaloperation.3.1.5 purge test, nplacing a blocking element over thesump to ensure that air enters the vent system.3.1.6 startup surge, ntransient lowering of the water levelin the vent during pump start
10、up.3.1.6.1 DiscussionIf excessive, the pump may lose prime.4. Significance and Use4.1 This performance specification outlines the require-ments needed to design and install a field-fabricated vent forsafety purposes. Vents only address suction outlet body andmay mitigate limb entrapment. Vents have
11、proven effectivewhen installed correctly. It is not intended to prevent otherinjuries caused by suction outlet(s) such as hair entrapment,mechanical entrapment, or evisceration.5. General Requirements5.1 Design and installation instructions for field-fabricatedvents (FFV) shall be certified only by
12、a registered professionalengineer. Multiple systems may be built to the same “ventdesign drawings and specifications” with the approval of theengineer.5.2 The design and installation of the vent is specific to eachpiping system and shall consider all relevant parametersincluding but not limited to:
13、elevations, flow rate, startup surge,minimum and maximum water operating levels, water depth atthe suction outlet(s), pipe fittings, spacing between fittings,atmospheric vent fitting, and suction outlet configurations.5.3 The vent shall be tested in place for proper function. SeeSection 7 for detail
14、s.1This test method is under the jurisdiction of ASTM Committee F15 onConsumer Products and is the direct responsibility of Subcommittee F15.51 onSafety Vacuum Release Systems for Swimming Pools, Spas and Hot Tubs.Current edition approved Nov. 1, 2010. Published March 2011. DOI: 10.1520/F2707-10.2Av
15、ailable fromAvailable from American National Standards Institute (ANSI),25 W. 43rd St., 4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.6. Specific Requirements6.1 The engineer shall
16、specify minimum and maximum flowrates, pipe sizes, and minimum and maximum pipe length(s),including equivalent length of fittings, elevation of criticalfittings with respect to normal pool operating level, as well asthe make and model of the suction outlet approved cover inaccordance with ASME/ANSI
17、A112.19.8, including the headloss at the suction fitting and the make and model of theatmospheric vent termination fitting. Vent termination fittingsare rated by the size of the pipe they can successfully vent. Forlarger pipes, the number of fittings shall equal or exceed theflow area of the large p
18、ipe divided by the flow area of thefittings rated pipe size.6.2 The vent shall be designed to insure that with any or allsuction outlet(s) completely blocked, the sump or vent draw-down shall not exceed the values in Table 1 for the size of agiven suction outlet sump with the vent termination fittin
19、g inplace and with or without the cover in place.6.3 The vent system and atmospheric vent terminationfitting shall be designed so that neither can be disabled withoutthe use of tools.6.4 Under normal operation, the vent system shall notadversely affect pump suction, system flow, or other equipmentpe
20、rformance.6.5 No check valves or valves shall be installed between anysuction outlet and the atmospheric opening of the system.6.6 The vent shall be piped to a location specified by theregistered professional engineer. If the vent is located outsidethe deck area, the vent shall be clearly visible an
21、d above gradeas indicated by the engineer.6.7 If the pool is not equipped with an overflow, the ventopening shall be installed above the highest water levelpossible in the pool it is protecting.6.8 The vent line shall be provided with an atmospherictermination vent fitting as specified by the regist
22、ered profes-sional engineer and installed in accordance with the manufac-turers or engineers instructions (see Fig. 1).6.9 Vent lines shall be Schedule 40 or Schedule 80 polyvi-nyl chloride (PVC) pipe, minimum 112-in. (3.8-cm) iron pipesize (IPS), to assure rapid evacuation and resistance to acci-de
23、ntal damage.6.10 The “maximum allowable drawdown,” derived fromTable 1 (using linear interpolation if needed), shall be specifiedin the documentation for use in field testing.6.11 The requirements of Section 6 shall be incorporated in“vent design drawings and specifications.”7. Field Testing7.1 Purg
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF27072010STANDARDSAFETYPERFORMANCESPECIFICATIONFORSAFEDESIGNANDINSTALLATIONOFFIELDFABRICATEDSUCTIONLIMITINGVENTSYSTEMSFORSUCTIONENTRAPMENTPREVENTIONINSWPDF

链接地址:http://www.mydoc123.com/p-539305.html