1、Designation: F479 06 (Reapproved 2011)Standard Specification forIn-Service Care of Insulating Blankets1This standard is issued under the fixed designation F479; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revis
2、ion. A number in parentheses indicates the year of last reapproval. A superscriptepsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the in-service care, inspection,testing, and use voltage of insulating blankets for protection ofworke
3、rs from accidental contact with live electrical conduc-tors, apparatus, or circuits. The product requirements andacceptance testing are as shown in Specification D1048.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions
4、 to SI units that are provided for information onlyand are not considered standard.1.3 This standard does not purport to address all of thesafety problems, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and
5、determine the applica-bility of regulatory limitations prior to use. See Section 6 and8.2 for specific precautionary statements.2. Referenced Documents2.1 ASTM Standards:2D1048 Specification for Rubber Insulating BlanketsD2865 Practice for Calibration of Standards and Equipmentfor Electrical Insulat
6、ing Materials TestingF819 Terminology Relating to Electrical Protective Equip-ment for Workers2.2 ANSI Standard:3C39.5 Safety Requirements for Electrical and ElectronicMeasuring and Controlling InstrumentationC84.1 Voltage Ratings for Electric Power Systems andEquipment (60 Hz)3. Terminology3.1 Defi
7、nitions:3.1.1 breakdownthe electrical discharge or arc occurringbetween the electrodes and through the equipment being tested.3.1.2 compatiblenot injurious to or changing the physicalor electrical characteristics of the blankets or affecting theirapplication, use, or acceptability.3.1.3 designated p
8、ersonan individual who is qualified byexperience or training to perform an assigned task.3.1.4 electrical testing facilitya location with qualifiedpersonnel, testing equipment, and procedures for the inspectionand electrical testing of electrical insulating protective equip-ment.3.1.5 electrodethe e
9、nergized or grounded conductor por-tion of electrical test equipment which is placed near or incontact with the material or equipment being tested.3.1.6 flashoverthe electrical discharge or arc occurringbetween electrodes and over or around, but not through, theequipment being tested.3.1.7 insulated
10、separated from other conducting surfacesby a dielectric substance (including air space) offering a highresistance to the passage of current.3.1.7.1 DiscussionWhen any object is said to be insu-lated, it is understood to be insulated in a suitable manner forthe conditions to which it is subjected. Ot
11、herwise, it is, withinthe purposes of this definitions, uninsulated. Insulating cover-ing of conductors is one means of making the conductorinsulated.3.1.8 ozonea very active form of oxygen that may beproduced by corona, arcing, or ultraviolet rays.3.1.9 ozone cutting and checkingthe cracks produced
12、 byozone in a material under mechanical stress.3.1.10 retestthe tests given after the initial acceptance testusually performed at regular periodic intervals or as requiredbecause of physical inspection.3.1.11 unassigned blanketsblankets that are in storageprior to being issued for use.3.1.11.1 volta
13、ge, maximum usethe ac voltage (rms), clas-sification of the protective equipment that designates themaximum nominal design voltage of the energized system that1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsib
14、ility ofSubcommittee F18.25 on Insulating Cover-Up Equipment.Current edition approved Dec. 1, 2011. Published January 2012. Originallyapproved in 1976. Last previous edition approved in 2006 as F47906. DOI:10.1520/F0479-06R11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orco
15、ntact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyrig
16、ht ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.may be safely worked. The nominal design voltage is equal tothe phase-to-phase voltage on multiphase circuits.3.1.11.2 DiscussionIf there is no multiphase exposure in asystem area, and the volt
17、age exposure is limited to the phase(polarity on dc systems) to ground potential, the phase (polarityon dc systems) to ground potential shall be considered to be thenominal design voltage.3.1.11.3 DiscussionIf electrical equipment and devicesare insulated or isolated, or both, such that the multipha
18、seexposure on a grounded wye circuit is removed, then thenominal design voltage may be considered as the phase-to-ground voltage on that circuit.3.1.11.4 DiscussionThe work practices and methods as-sociated with removing multiphase exposures at any givenwork site are not addressed in the ASTM standa
19、rds. The usersof ASTM standards should reference appropriate industryconsensus standards for proper work practices.3.1.12 voltage, maximum retestthe voltage, either ac rmsor dc avg, that is equal to the proof test voltage for newprotective equipment.3.1.13 voltage, nominal designa nominal value cons
20、istentwith ANSI C84.1-2001, assigned to the circuit or system forthe purpose of conveniently designating its voltage class.3.1.14 voltage, retestthe voltage, either ac rms or dc avg,that used protective equipment must be capable of withstand-ing for a specified test period without breakdown.3.2 For
21、definitions of other terms, refer to TerminologyF819.4. Significance and Use4.1 Compliance with this specification should continue toprovide personnel with insulating blankets of known andacceptable quality after initial acceptance in accordance withSpecification D1048. The standards herein are to b
22、e consideredas minimum requirements.5. Classification5.1 Blankets covered under this specification shall be des-ignated as Type I or Type II; Class 0, Class 1, Class 2, Class 3,or Class 4; Style A or Style B.5.2 Type I, not resistant to ozone, made from a high-gradecis-1,4-polyisoprene rubber compou
23、nd of natural or syntheticorigin, properly vulcanized.5.3 Type II, ozone-resistant, made of any elastomer orcombination of elastomeric compounds.5.4 The class designation shall be based on the electricalproperties as shown in Specification D1048.5.5 Style A, constructed of the elastomers indicated u
24、nderType I or Type II, shall be free of any reinforcement.5.6 Style B, constructed of the elastomers indicated underType I or Type II, shall incorporate a reinforcement. Thisreinforcement shall not affect adversely the dielectric charac-teristics of the blankets.6. Safety Precautions6.1 A margin of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF47920062011STANDARDSPECIFICATIONFORINSERVICECAREOFINSULATINGBLANKETS 绝缘 涂层 使用 维护 标准 规范 PDF

链接地址:http://www.mydoc123.com/p-536752.html