1、Designation: F 479 06Standard Specification forIn-Service Care of Insulating Blankets1This standard is issued under the fixed designation F 479; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in
2、 parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the in-service care, inspection,testing, and use voltage of insulating blankets for protection ofworkers from acciden
3、tal contact with live electrical conduc-tors, apparatus, or circuits. The product requirements andacceptance testing are as shown in Specification D 1048.1.2 This standard does not purport to address all of thesafety problems, if any, associated with its use. It is theresponsibility of the user of t
4、his standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. See Section 6 and8.2 for specific precautionary statements.2. Referenced Documents2.1 ASTM Standards:2D 1048 Specification for Rubber Insulating BlanketsD 2865
5、Practice for Calibration of Standards and Equip-ment for Electrical Insulating Materials TestingF 819 Terminology Relating to Electrical Protective Equip-ment for Workers2.2 ANSI Standard:3C 39.5 Safety Requirements for Electrical and ElectronicMeasuring and Controlling InstrumentationC 84.1 Voltage
6、 Ratings for Electric Power Systems andEquipment (60 Hz)3. Terminology3.1 Definitions:3.1.1 breakdownthe electrical discharge or arc occurringbetween the electrodes and through the equipment being tested.3.1.2 compatiblenot injurious to or changing the physicalor electrical characteristics of the bl
7、ankets or affecting theirapplication, use, or acceptability.3.1.3 designated personan individual who is qualified byexperience or training to perform an assigned task.3.1.4 electrical testing facilitya location with qualifiedpersonnel, testing equipment, and procedures for the inspectionand electric
8、al testing of electrical insulating protective equip-ment.3.1.5 electrodethe energized or grounded conductor por-tion of electrical test equipment which is placed near or incontact with the material or equipment being tested.3.1.6 flashoverthe electrical discharge or arc occurringbetween electrodes
9、and over or around, but not through, theequipment being tested.3.1.7 insulatedseparated from other conducting surfacesby a dielectric substance (including air space) offering a highresistance to the passage of current.3.1.7.1 DiscussionWhen any object is said to be insu-lated, it is understood to be
10、 insulated in a suitable manner forthe conditions to which it is subjected. Otherwise, it is, withinthe purposes of this definitions, unisulated. Insulating coveringof conductors is one means of making the conductor insulated.3.1.8 ozonea very active form of oxygen that may beproduced by corona, arc
11、ing, or ultra-violet rays.3.1.9 ozone cutting and checkingthe cracks produced byozone in a material under mechanical stress.3.1.10 retestthe tests given after the initial acceptance testusually performed at regular periodic intervals or as requiredbecause of physical inspection.3.1.11 unassigned bla
12、nketsblankets that are in storageprior to being issued for use.3.1.12 voltage, maximum usethe ac voltage (rms), classi-fication of the protective equipment that designates the maxi-mum nominal design voltage of the energized system that maybe safely worked. The nominal design voltage is equal to the
13、phase-to-phase voltage on multiphase circuits.3.1.12.1 If there is no multiphase exposure in a system area,and the voltage exposure is limited to the phase (polarity on dcsystems) to ground potential, the phase (polarity on dc sys-tems) to ground potential shall be considered to be the nominaldesign
14、 voltage.1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee F18.25 on Insulating Cover-up Equipment.Current edition approved September 1, 2006. Published September 2006.Originally approved
15、in 1976. Last previous edition approved in 2001 asF 479 95(2001).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM webs
16、ite.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.1.12.2 If electrical equipment and devices are insul
17、ated orisolated, or both, such that the multiphase exposure on agrounded wye circuit is removed, then the nominal designvoltage may be considered as the phase-to-ground voltage onthat circuit.3.1.12.3 DiscussionThe work practices and methods as-sociated with removing mulitphase exposures at any give
18、nwork site are not addressed in the ASTM standards. The usersof ASTM standards should reference appropriate industryconsensus standards for proper work practices.3.1.13 voltage, maximum retestthe voltage, either ac rmsor dc avg, that is equal to the proof test voltage for newprotective equipment.3.1
19、.14 voltage, retestthe voltage, either ac rms or dc avg,that used protective equipment must be capable of withstand-ing for a specified test period without breakdown.3.1.15 voltage, nominal designa nominal value consistentwith ANSI C 84.1-2001, assigned to the circuit or system forthe purpose of con
20、veniently designating its voltage class.3.2 For definitions of other terms, refer to TerminologyF 819.4. Significance and Use4.1 Compliance with this specification should continue toprovide personnel with insulating blankets of known andacceptable quality after initial acceptance in accordance withS
21、pecification D 1048. The standards herein are to be consid-ered as minimum requirements.5. Classification5.1 Blankets covered under this specification shall be des-ignated as Type I or Type II; Class 0, Class 1, Class 2, Class 3,or Class 4; Style A or Style B.5.2 Type I, not resistant to ozone, made
22、 from a high-gradecis-1,4-polyisoprene rubber compound of natural or syntheticorigin, properly vulcanized.5.3 Type II, ozone-resistant, made of any elastomer orcombination of elastomeric compounds.5.4 The class designation shall be based on the electricalproperties as shown in Specification D 1048.5
23、.5 Style A, constructed of the elastomers indicated underType I or Type II, shall be free of any reinforcement.5.6 Style B, constructed of the elastomers indicated underType I or Type II, shall incorporate a reinforcement. Thisreinforcement shall not affect adversely the dielectric charac-teristics
24、of the blankets.6. Safety Precautions6.1 A margin of safety shall be provided between themaximum use voltage on which the blankets are used and thevoltage at which they are retested. The relationship betweenretest voltage and maximum use voltage at which the blanketsshall be used is shown in Table 1
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF4792006STANDARDSPECIFICATIONFORINSERVICECAREOFINSULATINGBLANKETS 绝缘 涂层 使用 维护 标准 规范 PDF

链接地址:http://www.mydoc123.com/p-536751.html