ASTM F1869-2016 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride《使用无水氯化钙测量混凝土底层地板的湿气排放率的标准试验方法》.pdf
《ASTM F1869-2016 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride《使用无水氯化钙测量混凝土底层地板的湿气排放率的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1869-2016 Standard Test Method for Measuring Moisture Vapor Emission Rate of Concrete Subfloor Using Anhydrous Calcium Chloride《使用无水氯化钙测量混凝土底层地板的湿气排放率的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1869 16Standard Test Method forMeasuring Moisture Vapor Emission Rate of ConcreteSubfloor Using Anhydrous Calcium Chloride1This standard is issued under the fixed designation F1869; the number immediately following the designation indicates the year oforiginal adoption or, in the case
2、of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the quantitative determinationof the rate of moisture vapor emitted f
3、rom below-grade,on-grade, and above-grade (suspended) bare concrete floors.1.2 This test shall not be used to evaluate the rate ofmoisture vapor emitted by gypsum concrete or floors contain-ing lightweight aggregate.1.3 This test shall not be used to evaluate moisture vaporemissions over coatings on
4、 concrete or through reactivepenetrants or over patching or leveling compounds.1.4 This quantity of moisture shall be expressed as the rateof moisture vapor emission, measured in pounds of moistureover a 1000 ft2area during a 24-h period.1.5 The values stated in inch-pound units are to be regardedas
5、 standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of th
6、is standard to establish appro-priate safety and health practices, and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E1745 Specification for Plastic Water Vapor Retarders Usedin Contact with Soil or Granular Fill under Concrete SlabsE1
7、993 Specification for Bituminous Water Vapor RetardersUsed in Contact with Soil or Granular Fill Under ConcreteSlabsF141 Terminology Relating to Resilient Floor Coverings2.2 Resilient Floor Covering Institute Standard:3Recommended Work Practices2.3 Military Standard:4MIL-PRF-131 Barrier Materials, W
8、aterproof, Greaseproof,Flexible, Heat-Sealable2.4 ICRI Guide:5ICRI Technical Guideline 310.1-1997 Selecting and Speci-fying Concrete Surface Preparation for Sealers, Coatings,and Polymer Overlays3. Terminology3.1 Definitions:See Terminology F141 for definitions of theterms, above-grade (suspended),
9、below-grade, concrete, on-grade, and resilient flooring.3.2 Definitions of Terms Specific to This Standard:3.2.1 moisture vapor emission rate (MVER)amount ofwater vapor in pounds emitted from a 1000 ft2area of concreteflooring during a 24-h period (multiply by 56.51 to convert tog/s m2).4. Significa
10、nce and Use4.1 Use this test method to obtain a quantitative valueindicating the rate of moisture vapor emission from the surfaceof a concrete floor and whether or not that floor is acceptableto receive resilient floor covering. The moisture vapor emissionrate only reflects the condition of the conc
11、rete floor at the timeof the test. All concrete subfloors emit some amount ofmoisture in vapor form. Concrete moisture emission is anatural process driven by environmental conditions. All floorcoverings are susceptible to failure from excessive moisturevapor emissions. The moisture vapor emitted fro
12、m a concreteslab is measured in pounds. This measurement is the equivalentweight of water evaporating from 1000 ft2of concrete surfacein a 24h period. The calcium chloride moisture test has beenthe industry standard for making this determination and is a1This test method is under the jurisdiction of
13、ASTM Committee F06 on ResilientFloor Coverings and is the direct responsibility of Subcommittee F06.40 onPractices.Current edition approved March 1, 2016. Published April 2016. Originallyapproved in 1998. Last previous edition approved in 2011 as F186911. DOI:10.1520/F1869-16.2For referenced ASTM st
14、andards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Resilient Floor Covering Institute, 966 Hungerford Drive, Suite12-B,
15、 Rockville, MD 20850.4Available from Standardization Documents Order Desk, Bldg. 4 Section D, 700Robbins Ave., Philadelphia, PA 19111-5094, Attn: NPODS.5Available from International Concrete Repair Institute, International ConcreteRepair Institute 3166 S. River Road, Suite 132, Des Plaines, IL 60018
16、; www.icri.orgCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1practical, well-established and accepted test of dynamic mois-ture. It will produce quantified results directly applicable toflooring manufacturers specifications. The resu
17、lts obtainedreflect the condition of the concrete floor surface at the time oftesting and may not indicate future conditions.5. Apparatus5.1 Test Unit Contents:5.1.1 Cylindrical Plastic Dish with Lid Containing Anhy-drous Calcium Chloride, heat sealed in a heat sealable bagmeeting the latest version
18、 of MIL-PRF-131, Class 1 or 2, toprotect from moisture intrusion.5.1.1.1 Anhydrous calcium chloride shall be in the form ofprilled beads and shall have a minimum purity of 94 %. Netweight of the anydrous calcium chloride shall be 16 6 1g.5.1.1.2 Dish shall be made of a material that does not absorbm
19、oisture. Dimensions of the dish shall be 2.7 6 0.08 in. (69 62 mm) outside diameter as measured at the bottom area of thedish that contacts the floor, 0.6 to 0.8 in. (15 to 20 mm) heightwithout cover, wall thickness less than 0.08 in. (2 mm). Dishshall be supplied with a tight-fitting lid. The lid s
20、hall be securedto the dish with pressure-sensitive-adhesive backed vinyl tapethat does not absorb moisture, or a mechanical seal shall beprovided such as a screw-top or snap-top lid.5.1.2 Pressure Sensitive Label, to be used to identify thecontainer of calcium chloride and to record the date, time,
21、andcontainer weight when the test is started and completed.5.1.3 Transparent Cover, with 0.5 in. (12 mm) flangesaround the perimeter, approximately 0.5 ft2(460 6 46 cm2), asmeasured between the inside of the flanges, is required to sealthe test area of the floor. The transparent cover shall have ade
22、pth greater than the height of the dish of anhydrous calciumchloride. The height of the transparent cover shall be 1.5 in. 60.125 (38 6 3.2 mm).5.1.4 Strip of Sealant, to secure the plastic cover to the floorin an airtight fashion.5.1.5 Brightly Colored Warning Label, to be placed on thetransparent
23、cover as a protective warning while the test is beingconducted.5.1.6 Optional Mailing Bag, for the return of the sample tothe party responsible for weighing the dish and calculating thetest results.5.2 Gram Scale, capable of measuring 60.1 g. This scalewill be used to weigh the calcium chloride dish
24、 at the start andend of the test. On-site measurement is preferred to mailing thecontainer back to the supplier for results.5.3 Thermometer, capable of measuring room temperature.5.4 Hygrometer, capable of measuring the relative humidityof the test site.6. Conditioning6.1 The test site should be at
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF18692016STANDARDTESTMETHODFORMEASURINGMOISTUREVAPOREMISSIONRATEOFCONCRETESUBFLOORUSINGANHYDROUSCALCIUMCHLORIDE

链接地址:http://www.mydoc123.com/p-535904.html