《ASTM F1704-2009 Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems《商用厨房排气通风系统的吸气和控制性能的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1704-2009 Standard Test Method for Capture and Containment Performance of Commercial Kitchen Exhaust Ventilation Systems《商用厨房排气通风系统的吸气和控制性能的标准试验方法》.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1704 09An American National StandardStandard Test Method forCapture and Containment Performance of CommercialKitchen Exhaust Ventilation Systems1This standard is issued under the fixed designation F1704; the number immediately following the designation indicates the year oforiginal ado
2、ption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 Characterization of capture and containment perfor-mance of hood, appli
3、ance(s), and replacement air systemduring cooking and non-cooking conditions (idle):1.2 Parametric evaluation of operational or design varia-tions in appliances, hoods, or replacement air configurations.1.3 The test method to determine heat gain to space fromcommercial kitchen ventilation/appliance
4、systems has beenre-designated as Test Method F2474.1.4 The values stated in inch-pound units are to be regardedas standard. No other units of measurement are included in thisstandard.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is there
5、sponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2F1275 Test Method for Performance of GriddlesF1361 Test Method for Performance of Open De
6、ep FatFryersF1484 Test Methods for Performance of Steam CookersF1496 Test Method for Performance of Convection OvensF1521 Test Methods for Performance of Range TopsF1605 Test Method for Performance of Double-SidedGriddlesF1639 Test Method for Performance of Combination OvensF1695 Test Method for Per
7、formance of Underfired BroilersF1784 Test Method for Performance of a Pasta CookerF1785 Test Method for Performance of Steam KettlesF1787 Test Method for Performance of Rotisserie OvensF1817 Test Method for Performance of Conveyor OvensF1991 Test Method for Performance of Chinese (Wok)RangesF1964 Te
8、st Method for Performance of Pressure and KettleFryersF1965 Test Method for Performance of Deck OvensF2093 Test Method for Performance of Rack OvensF2144 Test Method for Performance of Large Open VatFryersF2237 Test Method for Performance of Upright OverfiredBroilersF2239 Test Method for Performance
9、 of Conveyor BroilersF2474 Test Method for Heat Gain to Space Performance ofCommercial Kitchen Ventilation/Appliance Systems2.2 ASHRAE Standards:3ASHRAE Guideline 2-1986 (RA90) Engineering Analysisof Experimental Data2.3 ANSI Standard:4ANSI/ASHRAE 41.2 Standard Methods for LaboratoryAir-Flow Measure
10、mentANSI/ASHRAE 51 and ANSI/AMCA 210 LaboratoryMethod of Testing Fans for RatingNOTE 1The replacement air and exhaust system terms and theirdefinitions are consistent with terminology used by the American Societyof Heating, Refrigeration, and Air Conditioning Engineers, see Ref (1).5Where there are
11、references to cooking appliances, an attempt has beenmade to be consistent with terminology used in the test methods forcommercial cooking appliances. For each energy rate defined as follows,there is a corresponding energy consumption that is equal to the averageenergy rate multiplied by elapsed tim
12、e. Electric energy and rates areexpressed in W, kW, and kWh. Gas Energy consumption quantities andrates are expressed in Btu, kBtu, and kBtu/h. Energy rates for natural1This test method are under the jurisdiction of ASTM Committee F26 on FoodService Equipment and are the direct responsibility of Sub
13、committee F26.07 onCommercial Kitchen Ventilation.Current edition approved Oct. 1, 2009. Published November 2009. Originallyapproved in 1996. Last previous edition approved in 2005 as F1704 05. DOI:10.1520/F1704-09.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM
14、Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA3032
15、9.4Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036.5The boldface numbers in parentheses refer to the list of references at the end ofthese test methods.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 1
16、9428-2959, United States.gas-fueled appliances are based on the higher heating value of natural gas.3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 aspect ratio, nratio of length to width of an openingor grill.3.1.2 energy rate, naverage rate at which an applianceconsumes ener
17、gy during a specified condition (for example,idle or cooking).3.1.3 cooking energy consumption rate, naverage rate ofenergy consumed by the appliance(s) during cooking specifiedin appliance test methods in 2.1.3.1.3.1 DiscussionIn this test method, this rate is mea-sured for heavy-load cooking in ac
18、cordance with the applicabletest method.3.1.4 exhaust flow rate, nvolumetric flow of air (plusother gases and particulates) through the exhaust hood, mea-sured in standard cubic feet per minute, scfm (standard litre persecond, sL/s). This also shall be expressed as scfm per linearfoot (sL/s per line
19、ar metre) of exhaust hood length.3.1.5 fan and control energy rate, naverage rate of energyconsumed by fans, controls, or other accessories associatedwith cooking appliance(s). This energy rate is measured duringpreheat, idle, and cooking tests.3.1.6 hood capture and containment, nability of the hoo
20、dto capture and contain grease-laden cooking vapors, convectiveheat, and other products of cooking processes. Hood capturerefers to the products getting into the hood reservoir from thearea under the hood while containment refers to the productsstaying in the hood reservoir.3.1.7 idle energy consump
21、tion rate, naverage rate atwhich an appliance consumes energy while it is idling, holding,or ready-to-cook, at a temperature specified in the applicabletest method from 2.1.3.1.8 measured energy input rate, nmaximum or peakrate at which an appliance consumes energy measured duringappliance preheat,
22、that is, measured during the period ofoperation when all gas burners or electric heating elements areset to the highest setting.3.1.9 rated energy input rate, nmaximum or peak rate atwhich an appliance consumes energy as rated by the manufac-turer and specified on the appliance nameplate.3.1.10 repl
23、acement air, nair deliberately supplied into thespace (test room), and to the exhaust hood to compensate forthe air, vapor, and contaminants being expelled (typicallyreferred to as make-up air); can be dedicated make-up airdirected locally in the vicinity of the hood, transfer air, or acombination.3
24、.1.11 replacement air configurations, nsee below.3.1.11.1 ceiling diffuser, noutlet discharging supply airparallel to the ceiling either radially or in specific directions(for example, two-way, three-way, or four-way).3.1.11.2 displacement diffuser, noutlet supplying low ve-locity air at or near flo
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF17042009STANDARDTESTMETHODFORCAPTUREANDCONTAINMENTPERFORMANCEOFCOMMERCIALKITCHENEXHAUSTVENTILATIONSYSTEMS

链接地址:http://www.mydoc123.com/p-535453.html